background image

036-21618-002 Rev. A (1004)

2

Unitary Products Group

* Models available in LoNOx.

FRONT

LEFT SIDE

RIGHT SIDE

D

B

20

40

A

28-1/2

3/4

14-3/4

5-3/8

(VENT CONNECTIONS)

POWER WIRING
7/8” HOLE

2-1/2

ACCESS
WIRING
7/8” K.O.

16

8-3/4

T’STAT WIRING
7/8” K.O.

1-1/8

2-1/4

14

23-1/2

32-1/2

2

20

B

C

A

3/4”
FLANGE

BOTTOM IMAGE

(FRONT)

TOP IMAGE

(FRONT)

VENT
CONNECTION
(Vent Size)

D

F

E

28-1/2

23

13-3/4

GAS INLET
1-1/4 x 2-1/2

CABINET AND DUCT DIMENSIONS

BTUH 

Input/Output

CFM 

Cabinet

Size

Cabinet Dimension

A

B

C

D

E

F

40/32* 

1200  

14 1/2 

13 1/4 

10 1/8 

4.0 

10 1/8

3 3/4 

60/48*

1200  

14 1/2 

13 1/4 

10 1/8 

4.0 

10 1/8

3 3/4 

80/64*

1200 

14 1/2 

13 1/4 

10 1/8 

4.0 

10 1/8

3 3/4 

80/64*

1600  

17 1/2 

16 1/4 

13 1/8 

4.0 

11 5/8

3 3/4 

80/64*

2200  

21 

19 3/4 

16 5/8 

4.0 

13 3/8

3 3/4 

100/80*

1200 

17 1/2 

16 1/4 

13 1/8 

4.0 

11 5/8

3 3/4 

100/80*

1600

17 1/2 

16 1/4 

13 1/8 

4.0 

11 5/8

3 3/4 

100/80*

2000 

21 

19 3/4 

16 5/8 

4.0 

13 3/8

3 3/4 

115/92

1600  

21 

19 3/4 

16 5/8 

4.0 

13 3/8

3 3/4 

115/92*

2000  

21 

19 3/4 

16 5/8 

4.0 

13 3/8

3 3/4 

130/104*

2000  

24 1/2 

23 1/4 

20 1/8 

4.0 

15 1/8

3 3/4 

HORIZONTAL VENTING-MUST USE FIELDS CONTROL MODELS SWG-4Y OR TJERENLAND MODEL GPAK-JT FIELD 
SUPPLIED POWER VENTING KITS

Heating

Heating

Furnace

Horizontal Vent Length Ft (m) with 4 Elbows

Input

Output

Airflow

Pipe Size

Min. Vent Length

Max. Vent Length

BTU/H

BTU/H

CFM

Inches

Feet

Feet

40,000

32,000

1200

4

4.5

34.5

60,000

48,000

1200

4

4.5

34.5

80,000

64,000

1200

4

4.5

34.5

80,000

64,000

1600

4

4.5

34.5

80,000

64,000

2200

4

4.5

34.5

100,000

80,000

1200

4

4.5

34.5

100,000

80,000

1600

4

4.5

34.5

100,000

80,000

2000

4

4.5

34.5

115,000

92,000

1600

4

4.5

34.5

115,000

92,000

2000

4

4.5

34.5

130,000

104,000

2000

4

4.5

34.5

Summary of Contents for GY8S

Page 1: ...ble and economical installation and operation These units are Category I listed and may be common vented with another gas appliance as allowed by the National Fuel Gas Code WARRANTY 20 year limited wa...

Page 2: ...3 8 3 3 4 100 80 1200 B 17 1 2 16 1 4 13 1 8 4 0 11 5 8 3 3 4 100 80 1600 B 17 1 2 16 1 4 13 1 8 4 0 11 5 8 3 3 4 100 80 2000 C 21 19 3 4 16 5 8 4 0 13 3 8 3 3 4 115 92 1600 C 21 19 3 4 16 5 8 4 0 13...

Page 3: ...0 40 70 100 80 1600 17 1 2 80 0 35 65 100 80 2000 21 80 0 25 55 115 92 1600 21 80 0 35 65 115 92 2000 21 80 0 30 60 130 104 2000 24 1 2 80 0 35 65 Input MBH Max Outlet Air Temp F Blower Blower Size I...

Page 4: ...2410 2320 2230 2130 2030 1900 1790 1630 1470 Medium High 2120 2060 2000 1970 1840 1730 1680 1570 1460 1260 Medium Low 1720 1700 1670 1620 1570 1500 1430 1310 1160 1000 Low 1410 1390 1360 1330 1280 12...

Page 5: ...2200 C High 2710 2640 2560 2480 2360 2260 2160 2010 1860 1650 Medium High 2110 2110 2070 2030 1980 1910 1850 1710 1570 1300 Medium Low 1690 1690 1650 1610 1540 1480 1410 1280 1170 1030 Low 1350 1330 1...

Page 6: ...the total system static falls between ESP values in the table i e 0 58 w c 144 Pa 0 75 w c 187 Pa etc the static pres sure may be rounded to the nearest value in the table determin ing the airflow usi...

Page 7: ...S YES NO UPFLOW B VENT 1 3 0 0 0 1 COMBUSTIBLE YES YES YES NO HORIZONTAL 1 6 0 0 3 6 COMBUSTIBLE NO YES YES YES1 HORIZ B VENT 1 3 0 0 0 1 COMBUSTIBLE NO YES YES YES1 1 Line contact only permitted betw...

Page 8: ...e without notice Printed in U S A 036 21618 002 Rev A 1004 Copyright by Unitary Products Group 2004 All rights reserved Supersedes 036 21618 001 Rev A 0804 Unitary 5005 Norman Products York OK Group D...

Reviews: