APPLYING FILTER PRESSURE DROP TO 
DETERMINE SYSTEM AIRFLOW

To determine the approximate airflow of the unit with a filter in
place, follow the steps below:

1.

Select the filter type.

2.

Determine the External System Static Pressure (ESP) 
without the filter.

3.

Select a filter pressure drop from the table based upon 
the number of return air openings or return air opening 
size and add to the ESP from Step 3 to determine the 
total system static.

4.

If total system static matches a ESP value in the airflow 
table (i.e. 0.20, 0.60, etc,) the system airflow corre-
sponds to the intersection of the ESP column and Model/
Blower Speed row.

5.

If the total system static falls between ESP values in the 
table (i.e. 0.58, 0.75, etc.), the static pressure may be 
rounded to the nearest value in the table determining the 
airflow using Step 5 or calculate the airflow by using the 
following example.

Example:

  For a 120,000 Btuh furnace operating on high

speed blower, it is found that total system static is 0.58" w.c.
To determine the system airflow, complete the following
steps:

1.

Obtain the airflow values at 0.50" & 0.60" ESP.

Airflow @ 0.50":  2152 CFM

Airflow @ 0.60":  2042 CFM

2.

Subtract the airflow @ 0.50" from the airflow @ 0.60" to 
obtain airflow difference.

2042 - 2152 = -110 CFM

3.

Subtract the total system static from 0.50" and divide this 
difference by the difference in ESP values in the table, 
0.60" - 0.50", to obtain a percentage.

(0.58 - 0.50) / (0.60 - 0.50) = 0.8

4.

Multiply percentage by airflow difference to obtain airflow 
reduction.

(0.8) x (-110) = -88

5.

Subract airflow reduction value to airflow @ 0.50" to 
obtain actual airflow @ 0.58" ESP.

2152 - 88 = 2064

ACCESSORIES

PROPANE (LP) CONVERSION KIT - 

1NP0347 - All units

This accessory conversion kit may be used to convert natural
gas (N) units for propane (LP) operation. Conversions must
be made by qualified distributor or dealer personnel.

CONCENTRIC VENT TERMINATION -

 

1CT0302 (2")

1CT0303 (3")

For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole. Elimi-
nates unslightly elbows for a cleaner installation.

SIDEWALL VENT TERMINATION KIT - 

1HT0901 (3")
1HT0902 (2")

For use on sidewall, two-pipe installations only. Provide a
more attractive termination for locations where the terminal is
visable on the side of the home.

COMBUSTIBLE FLOOR BASE - 

1CB0314 - 14 1/2” Cabinet

1CB0317 - 17 1/2” Cabinet

1CB0321 - 21” Cabinet

1CB0324 - 24” Cabinet

COIL TRANSITION KIT - 

1TK0914 - 14” Furnace
1TK0917 - 17” Furnace
1TK0921 - 21” Furnace
1TK0924 - 24” Furnace
These kits are required in downflow application when using
G*F* series coils. These kits are not required with MC/FC
series coils, but please ensure that the coil and furnace are
secured and that there are noair leaks.

CONDENSATE NEUTRALIZER KIT - 

1NK0301

Neutralizer cartidge has a 1/2" plastic tube fittings for installa-
tion in the drain line. Calcium carbonate refill media is also
avaiable from the Source 1 Parts (p/n 026-30228-000).

HIGH ALTITUDE PRESSURE SWITCHES - 

For installation where the altitude is less than 8,000 feet it is 
not required that the pressure switch be changed. For alti-
tudes above 8,000 feet see kits below. Conversion must be 
made by qualified distributor or dealer personnel.

1PS0901 - 060, 100, 120 MBH
1PS0902 - 080/1200 MBH
1PS0903 - 080/1600 MBH
1PS0904 - 040 MBH

ROOM THERMOSTATS 

- A wide selection of compatible

thermosets are available to provide optimum performance
and features for any installation.

1H/1C, manual change-over electronic non-programmable 
thermostat.

1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.

1H/1C, auto/manual changeover, electronic programmable.

* For the most current accessory information, refer to the
price book or consult factory.

Summary of Contents for GM9S040A12DH11

Page 1: ...stal lation date to subsequent purchaser 10 year warranty on the heat exchanger in commercial appli cations 5 year limited parts warranty FEATURES Compact easy to install ideal height 40 cabinet Blowe...

Page 2: ...G 7 8 K O HORIZONTAL CONDENSATE DRAIN OPENING 1 3 4 HORIZONTAL CONDENSATE DRAIN OPENING 1 3 4 JUNCTION BOX HOLE 7 8 GAS PIPE ENTRY 1 1 2 CONDENSATE DRAIN HOLE 7 8 40 A FRONT CABINET AND DUCT DIMENSION...

Page 3: ...odels Input Cabinet Output Nominal Airflow Cabinet Width Total Unit AFUE Air Temp Rise MBH MBH CFM In Amps F GM9S040A12DH11 40 A 37 1200 14 1 2 9 94 35 65 GM9S060B12DH11 60 B 55 1200 17 1 2 9 92 35 65...

Page 4: ...1203 1177 1142 1094 1026 939 874 Medium Low 977 982 976 955 934 899 843 791 738 686 Low 775 777 757 733 698 663 627 584 549 490 GM9S080C16DH11 High 2071 2026 1981 1935 1864 1796 1713 1625 1532 1401 Me...

Page 5: ...DED FILTER SIZES CFM Cabinet Size Top Return Filter in 1200 A 2 14 x 20 1200 B 2 14 x 20 1600 C 2 14 x 20 2000 C 2 14 x 20 2000 D 2 14 x 20 FILTER PERFORMANCE PRESSURE DROP INCHES W C AND KPA Airflow...

Page 6: ...ool Y Y2 Single Second Stage Cool Y Single Stage Cool DN11C00124 C 24 Volt Common C 24 Volt Common Optional w Batteries BN11C01124 DP11C40124 PSC FURNACE CONTROL SINGLE STAGE AIR CONDITIONING BN11C001...

Page 7: ...t natural gas N units for propane LP operation Conversions must be made by qualified distributor or dealer personnel CONCENTRIC VENT TERMINATION 1CT0302 2 1CT0303 3 For use through rooftop sidewall Al...

Page 8: ...without notice Printed in U S A 278177 BTG A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 246730 036 21561 003 Rev A 1205 Unitary 5005 Norman Products York OK Group D...

Reviews: