TABLE 12:
Airflow Data
1
for 208 Volt - Heat Pump Models
1. Includes Return Air Filter and Largest Electric Heater.
All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.
Models
Blower Motor
Speed
208 Volt
CFM @ External Static Pressure - IWC
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
F4FP024H06T**
High
855
819
779
752
698
657
596
531
452
360
Med.
760
733
706
670
634
589
535
472
395
310
Low
585
567
545
518
486
457
405
344
257
142
F4FP030H06T**
High
1143
1089
1035
977
914
851
776
692
581
451
Med.
941
936
895
837
770
724
643
562
445
328
Low
770
738
702
662
612
561
495
402
300
171
F4FP036H06T**
High
1235
1179
1125
1058
1008
947
885
804
701
580
Med.
1080
1035
990
936
887
840
791
716
640
528
Low
954
914
873
833
774
728
666
595
515
408
F4FP040H06T**
High
1143
1089
1035
977
914
851
776
692
581
451
Med.
941
936
895
837
770
724
643
562
445
328
Low
770
738
702
662
612
561
495
402
300
171
F4FP042H06T**
High
1400
1418
1350
1278
1215
1145
1073
991
897
784
Med.
1314
1266
1197
1135
1071
1012
947
864
758
625
Low
1125
1080
1040
990
945
901
838
766
676
568
F4FP045H06T**
High
1418
1382
1328
1251
1179
1120
1032
927
807
661
Med-high
1238
1184
1130
1067
999
936
850
763
659
545
Med-low
1089
1044
999
945
882
829
760
663
576
480
Low
932
891
846
801
743
693
628
554
472
389
F5FP048H06T**
High
2209 2140 2093 2000 1939 1864
1746
1724
1655
1587
Med
High
1945 1906 1871 1819 1784 1741
1667
1640
1595
1550
Med
1739 1690 1640 1602 1559 1516
1470
1431
1387
1343
Med
Low
1506 1464 1415 1369 1325 1283
1238
1193
1139
1100
Low
1301 1248 1197 1151 1095 1054
1005
958
909
860
F5FP060H06T**
High
2134 2124 2052 1979 1861 1756
1639
1597
1512
1427
Med
High
1916 1875 1838 1777 1744 1671
1594
1584
1537
1490
Med
1716 1671 1613 1569 1523 1475
1429
1384
1337
1290
Med
Low
1494 1435 1390 1341 1284 1241
1194
1139
1087
1036
Low
1276 1223 1168 1115 1068 1009
965
902
847
792
NOTE: Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is
limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.