404912-UIM-A-0508

Johnson Controls Unitary Products

13

TABLE 12: 

Airflow Data

1

 for 208 Volt - Heat Pump Models

1. Includes Return Air Filter and Largest Electric Heater.

All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.

Models

Blower Motor 

Speed

208 Volt

CFM @ External Static Pressure - IWC

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

F4FP024H06T**

High

855

819

779

752

698

657

596

531

452

360

Med.

760

733

706

670

634

589

535

472

395

310

Low

585

567

545

518

486

457

405

344

257

142

F4FP030H06T**

High

1143

1089

1035

977

914

851

776

692

581

451

Med.

941

936

895

837

770

724

643

562

445

328

Low

770

738

702

662

612

561

495

402

300

171

F4FP036H06T**

High

1235

1179

1125

1058

1008

947

885

804

701

580

Med.

1080

1035

990

936

887

840

791

716

640

528

Low

954

914

873

833

774

728

666

595

515

408

F4FP040H06T**

High

1143

1089

1035

977

914

851

776

692

581

451

Med.

941

936

895

837

770

724

643

562

445

328

Low

770

738

702

662

612

561

495

402

300

171

F4FP042H06T**

High

1400

1418

1350

1278

1215

1145

1073

991

897

784

Med.

1314

1266

1197

1135

1071

1012

947

864

758

625

Low

1125

1080

1040

990

945

901

838

766

676

568

F4FP045H06T**

High

1418

1382

1328

1251

1179

1120

1032

927

807

661

Med-high

1238

1184

1130

1067

999

936

850

763

659

545

Med-low

1089

1044

999

945

882

829

760

663

576

480

Low

932

891

846

801

743

693

628

554

472

389

F5FP048H06T**

High

2209 2140 2093 2000 1939 1864 

1746 

1724 

1655 

1587 

Med 

High

1945 1906 1871 1819 1784 1741 

1667 

1640 

1595 

1550 

Med

1739 1690 1640 1602 1559 1516 

1470 

1431 

1387 

1343 

Med 

Low

1506 1464 1415 1369 1325 1283 

1238 

1193 

1139 

1100 

Low

1301 1248 1197 1151 1095 1054 

1005 

958 

909 

860 

F5FP060H06T**

High

2134 2124 2052 1979 1861 1756 

1639 

1597 

1512 

1427 

Med 

High

1916 1875 1838 1777 1744 1671 

1594 

1584 

1537 

1490 

Med

1716 1671 1613 1569 1523 1475 

1429 

1384 

1337 

1290 

Med 

Low

1494 1435 1390 1341 1284 1241 

1194 

1139 

1087 

1036 

Low

1276 1223 1168  1115 1068 1009 

965 

902 

847 

792 

NOTE: Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is 
limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.

Summary of Contents for F4FP024H06T3X

Page 1: ...ectrical Data For Multi Source Power Supply Copper Wire 1 208 230 1 601 10 Electrical Data 3 208 230 3 60 11 Electrical Data For Single Source Power Supply Copper Wire 3 208 230 3 60 11 Airflow Data f...

Page 2: ...used for cooling or heat pump operation with or without electric heat BRAND LABEL available from Distribution can be applied to center of the blower access panel The unit can be positioned for bottom...

Page 3: ...ed with the unit Ensure that the drain pan is lying flat against the insulation of the cabinet 7 Horizontal drain cutout in the center access panel should be removed by using a utility knife if not pr...

Page 4: ...Sizes SHIPPING BRACKET REMOVE PRIOR TO INSTALLATION 2 SCREWS 10 3 8 J DRAIN CONNECTIONS FOR HORIZONTAL APPLICATIONS 4 D VAPOR OPENING LIQUID OPENING 2 B FILTER ACCESS DRAIN CONNECTIONS FOR UPFLOW APP...

Page 5: ...model num bers 1PF0601 602 603BK See Table 3 for filter size SUSPENSION KITS A suspension kit is available Models 1BH0601 unit sizes 018 060 is designed specifically for the units contained in this i...

Page 6: ...d be sound isolated by using the appropriate hangers or strapping When field supplied lines are used be sure to insulate the suction line only ELECTRIC HEATERS AND OPERATING CONTROLS The low voltage t...

Page 7: ...orator coil electric heat and outdoor unit Speed tap adjustments are made at the motor terminal block See Figure 11 Airflow data is shown in Tables 6 and 11 Higher efficiencies will be obtained if the...

Page 8: ...08 230 4 4 3 8 3 0 2 7 7 6 7 6 Locked Rotor 208 230 11 9 10 3 4 8 4 1 NA NA Filter1 Type DISPOSABLE OR PERMANENT Size 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 22 x 20 x 1 Permanent Type Kit 1PF0602BK 1PF06...

Page 9: ...5 0 042 2HK 6500506B 0 5 Low 3 8 5 0 13 0 17 1 3 8 5 0 3 8 5 0 3 8 5 0 2HK 6500806B Low 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B Low 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501...

Page 10: ...13 8 110 125 2 1 2HK16502506B 104 2 124 3 139 9 125 150 1 1 0 060 2HK 6500506B 20 8 32 8 35 6 35 40 8 8 2HK16500806B 31 3 42 9 48 3 45 50 8 8 2HK16501006B 41 7 55 3 61 6 60 70 6 4 2HK16501506B 62 5 78...

Page 11: ...6501525B 0 5 Med Low 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 060 2HK06501025B 0 5 Med 7 5 10 0 25 6 34 1 3 8 5 0 7 5 5 0 7 5 10 0 2HK06501525B 0 5 Med 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3...

Page 12: ...1 575 1 500 1 420 1 350 1 273 1 192 1 102 996 871 Med 1 460 1 395 1 330 1 260 1 190 1 125 1 052 960 842 695 Low 1 250 1 200 1 155 1 100 1 050 1 001 931 851 751 631 F4FP045H06T High 1 575 1 535 1 475...

Page 13: ...T High 1400 1418 1350 1278 1215 1145 1073 991 897 784 Med 1314 1266 1197 1135 1071 1012 947 864 758 625 Low 1125 1080 1040 990 945 901 838 766 676 568 F4FP045H06T High 1418 1382 1328 1251 1179 1120 10...

Page 14: ...trol Wiring Typical A C Cooling only Applications Y Y G G W1 O C HUM X Y1 Y2 CFM selection board only on F4FV model 1 Air Handler Control Wiring Typical A C with Electric Heat Applications THERMOSTAT...

Page 15: ...ced it should be washed with Calgon CalClean mix one part CalClean to ten parts water or other non acidic cleaners Allow solution to remain on coil for 30 minutes before rinsing with clean water Solut...

Page 16: ...nge without notice Printed in U S A 404912 UIM A 0508 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 292043 UIM B 0707 Johnson Controls Unitary Products 5005 York Drive Norman O...

Reviews: