404912-UIM-A-0508
12
Johnson Controls Unitary Products
All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.
TABLE 11:
Airflow Data for 230 Volt - Heat Pump Models
1
1. Includes Return Air Filter and Largest Electric Heater.
Models
Blower Motor
Speed
230 Volt
CFM @ External Static Pressure - IWC
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
F4FP024H06T**
High
950
910
865
835
775
730
662
590
502
400
Med
845
815
785
745
705
654
594
524
439
344
Low
650
630
605
575
540
508
450
383
285
158
F4FP030H06T**
High
1,270
1,210
1,150
1,085
1,015
946
862
769
645
502
Med
1,050
1,040
995
930
855
804
714
624
494
364
Low
855
820
780
735
680
624
550
447
333
190
F4FP036H06T**
High
-
1,310
1,250
1,175
1,120
1,053
983
894
779
645
Med
1,200
1,150
1,100
1,040
985
933
879
795
711
587
Low
1,060
1,015
970
925
860
809
740
661
572
453
F4FP040H06T**
High
1,270
1,210
1,150
1,085
1,015
946
802
769
645
502
Med
1,050
1,040
995
930
855
804
714
624
494
364
Low
855
820
780
735
680
624
550
447
333
190
F4FP042H06T**
High
-
1,575
1,500
1,420
1,350
1,273
1,192
1,102
996
871
Med
1,460
1,395
1,330
1,260
1,190
1,125
1,052
960
842
695
Low
1,250
1,200
1,155
1,100
1,050
1,001
931
851
751
631
F4FP045H06T**
High
1,575
1,535
1,475
1,390
1,310
1,245
1,147
1,030
897
735
Med High
1,375
1,315
1,255
1,185
1,110
1,040
944
848
732
606
Med Low
1,210
1,160
1,110
1,050
980
921
844
737
640
533
Low
1,035
990
940
890
825
770
698
616
524
432
F5FP048H06T**
High
2223
2158
2090
2029
1929
1861
1788
1679
1594
1501
Med High
1948
1904
1801
1815
1777
1741
1681
1618
1539
1453
Med
1741
1690
1649
1606
1564
1516
1476
1436
1387
1353
Med Low
1499
1454
1415
1370
1328
1269
1228
1191
1132
1093
Low
1286
1233
1177
1142
1092
1039
987
960
888
842
F5FP060H06T**
High
2195
2145
2070
2008
1920
1852
1754
1663
1570
1462
Med High
1938
1899
1873
1824
1791
1724
1679
1603
1521
1420
Med
1726
1681
1641
1607
1560
1517
1485
1433
1402
1349
Med Low
1525
1483
1441
1383
1356
1291
1253
1208
1169
1123
Low
1306
1254
1204
1160
1114
1061
1008
980
914
876
NOTE: Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is
limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.