background image

A 7/8" OD drain connection extends through right hand side of
cabinet. Refer to Fig. 7 for recommended drain piping.

The drain connection is located on the same side of the unit as
the refrigerant connections. The line should be insulated where
moisture drippage will be objectionable or cause damage to the
area.

The 3" dimension must equal or exceed the negative static
pressure developed by the supply air blower. If it does not, the
condensate will not drain properly and may overflow the drain
pan. The trap must be at least 2-1/2" deep to maintain a water
seal under all operating conditions, especially during blower
start-up.

NOTE: The unit may have to be raised off the floor to allow

enough height for the trap.

SUPPLY AIR BLOWER ADJUSTMENT

The RPM of the supply air blower will depend on the required
CFM, the unit accessories and the static resistances of both the
supply and the return air duct systems. With this information,
the RPM for the supply air blower can be determined from the
blower performance in Table 4.

Knowing the required blower RPM and the blower motor HP,
the setting (turns open) for the supply air motor pulley can be
determined from Table 3.

Each motor pulley has:

1. A threaded barrel with two flats (or notched recesses) 180

degrees apart.

2. A movable flange with one set screw.

After the movable flange has been rotated to the proper
number of “turns open”, the set screw should be tightened
against the flat on the barrel to lock the movable flange in place.
If the pulley includes a locking collar, the locking collar must be
loosened to adjust the setting of the movable flange.

Note the following:

1. The supply air CFM must be within the limitations shown in

Table 2.

2. All pulleys can be adjusted in half turn increments.

3. The tension on the belt should be adjusted for a deflection

of 3/16 of an inch per foot of belt span with an applied force
of 2 to 3 pounds. This adjustment is made by moving the
blower motor mounting plate. Refer to Figure 8. Turning the
adjustment bolt (B) moves the motor mounting plate up or
down.

NOTE:

Never loosen the two nuts (C).

Two hex nuts (A) have to be loosened to move the mount-
ing plate and retightened after the mounting plate has been
moved to the proper position.

4. All pulleys are factory aligned.

5. All supply air motor pulleys are factory set 3 “turns open”.

After the supply air blower motor is operating, adjust the resis-
tances in both the supply and the return duct systems to bal-
ance the air distribution throughout the conditioned space. The
job specifications may require that this balancing be done by
someone other than the equipment installer.

To check the supply air CFM after the initial balancing has been
completed:

1. Drill two 5/16 inch holes in the side panel as shown in Fig-

ure 9.

2. Insert at least 6" of 1/4 inch tubing into each of these holes

for sufficient penetration into the air flow on both sides of
the indoor coil.

NOTE:

The tubes must be inserted and held in a position
perpendicular to the air flow so that velocity pres-
sure will not affect the static pressure readings.

3. Using an inclined manometer, determine the pressure drop

across a dry indoor coil. Since moisture on the coil may
vary greatly, measuring the pressure drop across a wet coil
under field conditions would be inaccurate. To assure a dry
coil, the heat pump system should be de-activated while
the test is being run.

4. Knowing the pressure drop across a dry coil, the actual

CFM through the unit can be determined from the curve in
Figure 10.

If the CFM is above or below the specified value, the supply air
motor pulley may have to be readjusted. After one hour of op-
eration, check the belt and pulleys for tightness and alignment.

WARNING: Failure to properly adjust the total system CFM

can result in extensive blower damage.

After readings have been obtained, remove the tubes and seal
up the drilled holes in the side panel. Dot plugs (5/16" - P/N
029-13880-000) are available through normal parts ordering
procedures.

NOTE: Shut down the heat pump system before taking any

test measurements to assure a dry indoor coil.

035-09651-001-A-0304

Unitary Products Group

7

FIG. 8 - TYPICAL MOTOR MOUNTING ASSEMBLY

TURNS

OPEN*

MODEL

F3EH090

60 Hz

F3EH090

50 Hz

F4EH120

60 Hz

F4EH120

50 Hz

5

655 RPM

542 RPM

700RPM

581 RPM

4

760

580

750

622

3

745

618

800

663

2

790

656

850

704

1

835

694

900

745

0

880

732

950

786

*

Pulleys can be adjusted in half-turn increments.

TABLE 3 - SUPPLY AIR BLOWER MOTOR

PULLEY ADJUSTMENT

Summary of Contents for F3EH090

Page 1: ...ipment All forms referenced in this instruction may be ordered from Standard Register Toll Free Tel 877 318 9675 Toll Free Fax 877 379 7920 Installer should pay particular attention to the words NOTE...

Page 2: ...Mounting Assembly 7 9 Hole Locations for Pressure Drop 8 10 Pressure Drop vs Supply Air CFM 8 11 Field Wiring 10 12 Unit Dimensions Clearances 11 TABLES Table No Description Page 1 Physical Data 3 2...

Page 3: ...of installation The packaging consists of a bottom wooden skid that can be lifted with a fork truck from any direction a cardboard container that covers the entire unit and strapping that secures the...

Page 4: ...rming up the conditioned space after a long shutdown TABLE 2 APPLICATION DATA Model Accessory Based on a Standard Blower Motor Center of Gravity Dimensions In Weight Distribution Lbs A B W1 W2 W3 W4 T...

Page 5: ...to minimize the transmission of noise and vibration Insulate all ductwork running through unconditioned areas to prevent moisture condensation and to provide more economi cal operation The return air...

Page 6: ...siderations INSTALLING REFRIGERANT MAINS WARNING Provisions for recovering refrigerant releases must be available during all phases of installation leak testing and charging Do NOT release refrig eran...

Page 7: ...e mount ing plate and retightened after the mounting plate has been moved to the proper position 4 All pulleys are factory aligned 5 All supply air motor pulleys are factory set 3 turns open After the...

Page 8: ...500 0 22 0 43 0 41 0 16 0 48 0 46 0 08 0 53 0 50 542 0 30 0 47 0 45 0 25 0 53 0 50 0 18 0 58 0 55 0 10 0 63 0 60 550 0 32 0 48 0 46 0 27 0 54 0 51 0 20 0 59 0 56 0 12 0 64 0 61 0 01 0 70 0 66 600 0 4...

Page 9: ...Thermostat to Indoor Unit ____________ 4 Indoor Unit to Outdoor Unit ___________ 5 Outdoor Unit to Elec Heater __________ Total Circuit Length __________ Model Motor HP Blower RPM Adjustable Motor Pu...

Page 10: ...in lieu of the unit Refer to electric heat instruction Form 035 16602 002 for additional installation information NOTE Motors are wired for a 460V power supply Refer to the wiring diagram inside the m...

Page 11: ...with RETURN AIR opening 24 Side with SUPPLY AIR opening 24 1 Side with PIPING CONNECTIONS 52 2 Side opposite PIPING CONNECTIONS 12 Side with access for both POWER CONTROL WIRING 3 Bottom 4 1 Overall...

Page 12: ...sur faces This is recommended to prevent any loss in capacity and efficiency DRAIN PAN The condensate drain pan should be inspected regularly to as sure proper drainage FILTERS The filters must be rep...

Reviews: