background image

GENERAL

These completely assembled indoor units include a well-
insulated cabinet, a copper tube/aluminum fin coil, throw-
away filters, a centrifugal blower, a blower motor, an adjust-
able V-belt drive, a blower motor contactor and a small
holding charge of an inert gas. They also include a filter-
drier, an expansion valve and a distributor that are only used
during the cooling cycle plus a check valve to provide the
proper flow of refrigerant through the coil during both the
cooling and heating cycles.

Supplemental resistance heaters, a supply air plenum, a return
air grille and a base are available as accessories for field instal-
lation.

The units are shipped in the vertical position ready for field in-
stallation. For horizontal installation, reverse the solid bottom
panel and the return air duct flange on the front of the unit.

REFERENCE

This instruction covers the installation of the indoor unit. For in-
formation on the installation and operation of the matching out-
door unit, refer to Form 035-15410-002.

Renewal Parts:

Refer to Parts Manual for complete listing of replacement
parts on this equipment.

All forms referenced in this instruction may be ordered from:

Standard Register
Toll Free Tel.: 877-318-9675
Toll Free Fax: 877-379-7920

Installer should pay particular attention to the words: NOTE,
CAUTION and WARNING. Notes are intended to clarify or
make the installation easier. Cautions are given to prevent
equipment damage. Warnings are given to alert the installer
that personal injury and/or equipment damage may result if the
installation procedure is not handled properly.

INSPECTION

As soon as a unit is received, it should be inspected for possi-
ble damage during transit. If damage is evident, the extent of
the damage should be noted on the carrier's freight bill. A sepa-

MODELS F3EH090 & F4EH120

(50 and 60 Hz)

INSTALLATION
MANUAL

Supersedes:  515.41-N2Y (692)/035-09651-000

035-09651-001-A-0304

SPLIT-SYSTEM HEAT PUMPS

INDOOR UNITS

CAUTION

THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE
WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND
ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES
INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL,
AND MECHANICAL CODES.

WARNING

IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION,
SERVICE OR MAINTENANCE CAN CAUSE INJURY OR
PROPERTY DAMAGE. REFER TO THIS MANUAL.

FOR

ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A
QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS
SUPPLIER.

Summary of Contents for F3EH090

Page 1: ...ipment All forms referenced in this instruction may be ordered from Standard Register Toll Free Tel 877 318 9675 Toll Free Fax 877 379 7920 Installer should pay particular attention to the words NOTE...

Page 2: ...Mounting Assembly 7 9 Hole Locations for Pressure Drop 8 10 Pressure Drop vs Supply Air CFM 8 11 Field Wiring 10 12 Unit Dimensions Clearances 11 TABLES Table No Description Page 1 Physical Data 3 2...

Page 3: ...of installation The packaging consists of a bottom wooden skid that can be lifted with a fork truck from any direction a cardboard container that covers the entire unit and strapping that secures the...

Page 4: ...rming up the conditioned space after a long shutdown TABLE 2 APPLICATION DATA Model Accessory Based on a Standard Blower Motor Center of Gravity Dimensions In Weight Distribution Lbs A B W1 W2 W3 W4 T...

Page 5: ...to minimize the transmission of noise and vibration Insulate all ductwork running through unconditioned areas to prevent moisture condensation and to provide more economi cal operation The return air...

Page 6: ...siderations INSTALLING REFRIGERANT MAINS WARNING Provisions for recovering refrigerant releases must be available during all phases of installation leak testing and charging Do NOT release refrig eran...

Page 7: ...e mount ing plate and retightened after the mounting plate has been moved to the proper position 4 All pulleys are factory aligned 5 All supply air motor pulleys are factory set 3 turns open After the...

Page 8: ...500 0 22 0 43 0 41 0 16 0 48 0 46 0 08 0 53 0 50 542 0 30 0 47 0 45 0 25 0 53 0 50 0 18 0 58 0 55 0 10 0 63 0 60 550 0 32 0 48 0 46 0 27 0 54 0 51 0 20 0 59 0 56 0 12 0 64 0 61 0 01 0 70 0 66 600 0 4...

Page 9: ...Thermostat to Indoor Unit ____________ 4 Indoor Unit to Outdoor Unit ___________ 5 Outdoor Unit to Elec Heater __________ Total Circuit Length __________ Model Motor HP Blower RPM Adjustable Motor Pu...

Page 10: ...in lieu of the unit Refer to electric heat instruction Form 035 16602 002 for additional installation information NOTE Motors are wired for a 460V power supply Refer to the wiring diagram inside the m...

Page 11: ...with RETURN AIR opening 24 Side with SUPPLY AIR opening 24 1 Side with PIPING CONNECTIONS 52 2 Side opposite PIPING CONNECTIONS 12 Side with access for both POWER CONTROL WIRING 3 Bottom 4 1 Overall...

Page 12: ...sur faces This is recommended to prevent any loss in capacity and efficiency DRAIN PAN The condensate drain pan should be inspected regularly to as sure proper drainage FILTERS The filters must be rep...

Reviews: