Table 15: 

AIR FLOW DATA - (HEAT PUMP MODELS)

Models

F2RP/F2FP

F3RP(T)/F3FP(T)

Blower

Motor

Speed

230 Volt

208 Volt

CFM

@ External Static Pressure - IWG

0.10

0.20

0.30

0.40

0.50

0.10

0.20

0.30

0.40

0.50

018

High

855

810

765

710

650

770

729

689

639

585

Med.

765

730

695

650

590

689

657

626

585

531

Low

645

620

590

555

505

581

558

581

500

455

024

High

950

910

865

835

775

855

819

779

752

698

Med.

845

815

785

745

705

760

733

706

670

634

Low

650

630

605

575

540

585

567

545

518

486

030

High

1,270

1,210

1,150

1,085

1,015

1,143

1,089

1,035

977

914

Med

1,050

1,040

995

930

855

941

936

895

837

770

Low

855

820

780

735

680

770

738

702

662

612

036

High

-

1310

1250

1175

1120

1235

1179

1125

1058

1008

Med

1200

1150

1100

1040

985

1080

1035

990

936

887

Low

1060

1015

970

925

860

954

914

873

833

774

040

High

-

1575

1500

1420

1350

1400

1418

1350

1278

1215

Med

1460

1295

1330

1260

1190

1314

1166

1197

1135

1071

Low

1250

1200

1155

1100

1050

1125

1080

1040

990

945

042

High

-

1575

1500

1420

1350

1400

1418

1350

1278

1215

Med

1460

1295

1330

1260

1190

1314

1166

1197

1135

1071

Low

1250

1200

1155

1100

1050

1125

1080

1040

990

945

045

High

1575

1535

1475

1390

1310

1418

1382

1328

1251

1179

Med-high

1375

1315

1255

1185

1110

1238

1184

1130

1067

999

Med-low

1210

1160

1110

1050

980

1089

1044

999

945

882

Low

1035

990

940

890

825

932

891

846

801

743

048

High

1,855

1,795

1,730

1,670

1,605

1,670

1,616

1,557

1,503

1,445

Med

1,685

1,630

1,575

1,520

1,470

1,517

1,467

1,418

1,368

1,323

Low

1,465

1,435

1,405

1,370

1,335

1,319

1,292

1,265

1,233

1,202

060

High

2,285

2,195

2,105

2,015

1,920

2,057

1,976

1,895

1,814

1,728

Med

2,125

2,020

1,910

1,805

1,705

1,913

1,818

1,719

1,625

1,535

Low

1,655

1,605

1,550

1,500

1,450

1,490

1,445

1,395

1,350

1,305

1.

Includes return air filter, wet coil and largest electric heater.

Table 16: 

AIR FLOW DATA - (COOLING MODELS)

MODELS

F2RC/F2FC

BLOWER

MOTOR

SPEED

230 VOLT

208 VOLT

CFM

1

 @ External Static Pressure - IWG

0.10

0.20

0.30

0.40

0.50

0.10

0.20

0.30

0.40

0.50

024

High

925

885

850

805

750

833

797

765

725

675

Med.

820

800

765

720

680

738

720

688

648

612

Low

645

620

595

570

535

581

558

536

513

482

030

High

1205

1150

1090

1025

990

1085

1035

981

923

891

Med

1020

1010

960

895

825

919

909

864

805

742

Low

840

805

760

715

660

756

725

684

644

594

036

High

1305

1250

1195

1150

1065

1175

1125

1076

1035

959

Med

1225

1175

1125

1070

1000

1103

1058

1013

963

900

Low

1055

1015

980

930

880

950

914

882

837

792

1.

Includes return air filter, wet coil and largest electric heater.

Summary of Contents for F2RP018

Page 1: ...TS GENERAL INFORMATION 2 INSPECTION 2 REFERENCE 2 LIMITATIONS 2 LOCATION 3 HORIZONTAL DRAIN PAN INSTALLATION CONVERSION 4 DIMENSIONS DUCT CONNECTORS 5 AIR FILTERS 6 SUSPENSION KITS 6 COIL METERING DEVICES 6 REFRIGERANT LINE CONNECTION 7 ELECTRIC HEATERS OPERATING CONTROLS 8 LOW VOLTAGE CONTROL CONNECTION 8 LINE POWER CONNECTIONS 8 BLOWER SPEED CONNECTIONS 8 DRAIN CONNECTIONS 19 MAINTENANCE 19 COIL...

Page 2: ...ibutor for more information Also check to be sure all accessories such as heater kits or suspension kits are available Installation of these accesso ries or field conversion of the unit should be accomplished before setting the unit in place or connecting any wiring elec tric heat ducts or piping REFERENCE Use this instruction in conjunction with the instructions for the appropriate indoor unit ai...

Page 3: ...e trapped and piped to a location that will give the occu pant a visual warning that the primary drain is clogged If the secondary drain is not used it must be capped 7 Proper electrical supply must be available 8 Clearances must also be taken into consideration and provided for as follows a Refrigerant piping and connections are located in the front b Maintenance and servicing through the front o...

Page 4: ...ife if not previously cut out 8 Re position and replace access panels DO NOT TRY TO KNOCK OUT Models F 2 3 FP045 048 060 have a coil baffle and support bracket factory installed for right hand hori zontal application refer to Figure 4C For left hand applications the coil support bracket must be moved to the right side of the coil and the coil baffle must be rotated to avoid water blow off To rotat...

Page 5: ...is unit is not designed for non ducted freeblow applications Size outlet plenum or transition to discharge opening sizes shown in Figure 5 Duct work should be fabricated and installed in accordance with local and or national codes This includes the standards of the National Fire Protection Association for Installation of Air Conditioning and Ventilating Systems NFPA No 90B MODEL F2RP F2FP F3RP T F...

Page 6: ...U is a valid system match for the AC or HP unit installed The TXV is fully brazed into the coil assembly of this Air Han dler unit at the factory The temperature sensing bulb will need to be attached to the coil suction header line after the line set is brazed to the coil Make sure the TXV bulb is outside of the Air Handler cabinet Excess tubing should remain inside the cabi net Take caution not t...

Page 7: ... orifice with a small diameter wire or paper clip 2 Remove the new orifice from the packet and verify that it is the correct number required Install this orifice with the rounded end toward the coil and the flat end outward per Figure 9 3 Thread the liquid line fitting back in place on the coil Tighten the fitting hand tight and turn an additional 1 8 turn to seal NOTE This procedure should be don...

Page 8: ...Figure 10 LOW VOLTAGE CONTROL CONNECTION The 24 volt power supply is provided by an internally wired low voltage transformer which is standard on all models However if the unit is connected to a 208 volt power supply the low voltage transformer must be rewired to the 208 volt tap See the unit wiring label Field supplied low voltage wiring can exit the unit on the top right hand corner or the right...

Page 9: ...POWER SUPPLY 3 GND LUG POWER SUPPLY GND LUG POWER WIRING 208 230 1 60 NOTE USE ONLY COPPER CONDUCTORS FIGURE 12 Control Board FIGURE 13 Blower Speed Connections R Y G W2 W1 O C 2 4 V A C BREAK TAB FOR VARIABLE SPEED MOTOR L 2 F A N L 1 L 2 L 1 L2 H L L 1 2 3 4 K2 T9A K1 T9A 5 A M P M A X 2 SPEED LTRIP ECM FAN LIM PWR LIM HEAT COM TEST HEAT 2 DRV HEAT 4 DRV HEAT 3 DRV FAN RELAY FAN CONNECTIONS TRAN...

Page 10: ...1085 1100 Voltage 208 230 Amps Full Load 208 230 2 5 2 2 4 4 3 8 3 0 2 7 3 4 3 3 50 Hz 2 4 4 5 4 4 50 Hz 5 7 Locked Rotor 208 230 6 2 5 5 11 9 10 3 4 8 4 1 4 6 4 0 8 4 7 3 Filter1 Type DISPOSABLE OR PERMANENT Size 16 x 20 x 1 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 22 x 20 x 1 Permanent Type Kit 1PF602BK 1PF602BK 1PF603BK 1PF603BK 1PF603BK Shipping Operating Weight lbs RP FP 121 115 115 121 150 144 14...

Page 11: ...5 0 2HK 6500806B LO 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B LO 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B HI 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 042 N H 06 2HK 6500506B 0 5 LO 3 8 5 0 13 0 17 1 3 8 5 0 3 8 5 0 3 8 5 0 2HK 6500806B LO 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B LO 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B LO 11 3 1...

Page 12: ... 3 95 2 90 100 3 3 040H06 2HK 6500506B 20 8 25 8 28 7 30 30 10 10 2HK 6500806B 31 3 36 7 41 7 40 45 8 8 2HK 6501006B 41 7 48 1 54 7 50 60 8 6 2HK16501506B 62 5 70 9 80 8 80 90 4 3 042 N H 06 2HK 6500506B 20 8 28 1 30 5 30 35 10 8 2HK 6500806B 31 3 38 9 43 6 40 45 8 8 2HK 6501006B 41 7 50 3 56 6 60 60 6 6 2HK16501506B 62 5 73 2 82 6 80 90 4 3 045H06 2HK 6500506B 20 8 26 6 29 3 30 30 10 10 2HK 65008...

Page 13: ... 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 030 N H 06 2HK06501025B 0 5 LO 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK06501525B 0 5 HI 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 036 N H 06 2HK06501025B 0 5 LO 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK06501525B 0 5 HI 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 040H06 2HK06501025B 0 5 LO 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK06...

Page 14: ...0 25 0 71 7 85 3 4 2 5 0 12 6 15 0 21 0 25 0 F2RP060N93 2HK 6500506B 0 5 LO 4 2 5 0 14 3 17 1 4 2 5 0 4 2 5 0 4 2 5 0 2HK 6500806B LO 6 3 7 5 21 5 25 6 4 2 5 0 6 3 7 5 6 3 7 5 2HK 6501006B LO 8 4 10 0 28 7 34 1 4 2 5 0 8 4 10 0 8 4 10 0 2HK16501506B LO 12 6 15 0 43 0 51 2 4 2 5 0 8 4 10 0 12 6 15 0 2HK16502006B LO 16 8 20 0 57 3 68 3 4 2 5 0 8 4 10 0 16 8 20 0 2HK16502506B LO 21 0 25 0 71 7 85 3 4...

Page 15: ...REE PHASE HEATERS Model Heater Model Min CFM Max Static Total Heat1 KW Staging KW MBH W1 Only W2 Only W1 W2 Static Tap 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V F2RP024N93 2HK06501025B 0 5 LO 8 4 10 0 28 7 34 1 4 2 5 0 8 4 10 0 8 4 10 0 F2RP036N93 2HK06501025B 0 5 LO 8 4 10 0 28 7 34 1 4 2 5 0 8 4 10 0 8 4 10 0 2HK06501525B MED 12 6 15 0 43 0 51 2 4 2 5 0 8 4 10 0 12 6 15 0 F2RP048N93 2HK0...

Page 16: ...igh 1575 1535 1475 1390 1310 1418 1382 1328 1251 1179 Med high 1375 1315 1255 1185 1110 1238 1184 1130 1067 999 Med low 1210 1160 1110 1050 980 1089 1044 999 945 882 Low 1035 990 940 890 825 932 891 846 801 743 048 High 1 855 1 795 1 730 1 670 1 605 1 670 1 616 1 557 1 503 1 445 Med 1 685 1 630 1 575 1 520 1 470 1 517 1 467 1 418 1 368 1 323 Low 1 465 1 435 1 405 1 370 1 335 1 319 1 292 1 265 1 23...

Page 17: ...264 Med 2125 3613 2020 3434 1910 3247 1805 3069 1705 2899 Low 1655 2814 1605 2729 1550 2635 1500 2550 1450 2465 MODEL Blower Motor Speed 220 Volt 50 HZ CFM or M3 H External Static Pressure IWG or PA 0 10 25 0 20 50 0 30 75 0 40 100 0 50 125 CFM M3 H CFM M3H CFM M3H CFM M3H CFM M3H F2RP024N93 High 855 1454 819 1392 779 1324 752 1278 698 1187 Med 760 1292 733 1246 706 1200 670 1139 634 1078 Low 585 ...

Page 18: ...AT PUMP FIELD INSTALLED JUMPER TERMINAL NOT AVAILABLE ON ALL THERMOSTATS FAN COIL UNIT R Y G W2 W1 O C O R Y G T E W O X R B Y W NOTE TO CHANGE HEAT QUANTITY DURING DEFROST REVERSE CONNECTIONS AT W1 W2 L or X C or B W1 66 FIGURE 16 Heat Pump Wiring Demand Defrost Only HEAT PUMP THERMOSTAT OUTDOOR UNIT O R Y G W T E O X R B Y W 66 60 53 TERMINAL NOT AVAILABLE ON ALL THERMOSTATS FAN COIL UNIT R Y G ...

Page 19: ...ds to be cleaned or replaced it should be washed with Calgon coilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted surfaces LUBRICATION The bearings of the blower motor are permanently lubricated CONDENSATE DRAINS During the cooling season check the conde...

Page 20: ...e without notice Printed in U S A 035 14520 001 Rev B 0803 Copyright by York International Corp 2003 All rights reserved Supersedes 035 14520 001 Rev A 0902 Unitary 5005 Norman Products York OK Group Drive 73069 NOTES ...

Reviews: