background image

035-14520-001 Rev.  B (0803)

4

Unitary Products Group

HORIZONTAL DRAIN PAN INSTALLATION / 
CONVERSION

These air handler units are supplied ready to be installed in a
right hand horizontal position when a horizontal pan is factory
installed. If unit requires field installation of a horizontal pan or
requires left hand positioning, the unit must have the pan
installed in the correct position.

NOTE: 

Models bearing a “H” indicates the unit has horizontal

drain pan factory installed in position “A”. (See Figure 4).

1.

Remove blower access, coil access, and center access 
panels.

NOTE: 

Conversion must be made before brazing the refriger-

ant connections to the coil.

2.

See Figure 4, remove two screws from horizontal drain 
pan, to remove pan from position “A” if factory installed.

3.

Position horizontal pan, as required in either “A” or “B” 
position, locking it into the vertical drain pan as shown.

4.

Horizontal drain pans have 4 plugged drains. Remove 
plugs from connections being used.

NOTE: 

If this step is overlooked, it can lead to a water prob-

lem later.

5.

Use removed plug to plug primary of upflow drain pan.

6.

Attach horizontal pan with 2 screws removed in step no. 
2 or supplied with the unit. Ensure that the drain pan is 
lying flat against the insulation of the cabinet.

7.

Horizontal drain cutout in the center access panel should 
be removed by using a utility knife (if not previously cut 
out).

8.

Re-position and replace access panels.

DO NOT TRY TO KNOCK OUT.

Models F(2,3)FP045,048,060 have a coil baffle and
support bracket factory installed for right hand hori-
zontal application (refer to Figure 4C). For left hand
applications the coil support bracket must be moved
to the right side of the coil, and the coil baffle must
be rotated to avoid water blow-off.

To rotate baffle, remove the coil assembly from the
unit (remove front two screws holding the coil sup-
port bracket and the two screws holding the drain
pan). Remove four screws in coil baffle and remove
the coil baffle and rotate ends.

Resecure the baffle and reinstall the coil assembly
ensuring that the rear of the drain pan is secured
under the back flange of the unit. Reinstall the coil
support bracket on the right side of the coil.

 FIGURE 4 : 

Filter Access & Drain Pan Conversion / Coil Baffle

FILTER

4B - SIDE VIEW

"S" BRACKET MUST BE USED TO

FASTEN DUCT WORK TO FRONT OF UNIT

RETURN AIR DUCT

3/4" PVC SOCKETS

FOR HORIZONTAL

DRAIN APPLICATION

HORIZONTAL

DRAIN PAN

POSITION "A”

HORIZONTAL

DRAIN PAN

POSITION "B”

PRIMARY DRAIN UPFLOW

3/4” THREADED

SECONDARY

DRAIN UPFLOW

3/4" THREADED

BLOWER

HOUSING

COIL COMPARTMENT

(ACCESS PANEL REMOVED)

FILTER

BLOWER

COMPARTMENT

(ACCESS PANEL

REMOVED)

CENTER ACCESS PANEL

PRIMARY

DRAIN

SECONDARY

DRAIN

VERTICAL

DRAIN PAN

SECONDARY

DRAIN

PRIMARY

DRAIN

4C - FRONT VIEW

4A - FRONT VIEW

DUCT WORK MAY BE FASTENED

CAUTIOUSLY WITH SCREWS TO

THE SIDES AND REAR OF UNIT

SUPPORT

BRACKET

060 COIL BAFFLE

(SHOWN IN

RIGHT-HORIZONTAL

POSITION)

Summary of Contents for F2FC018

Page 1: ...S GENERAL INFORMATION 2 INSPECTION 2 REFERENCE 2 LIMITATIONS 2 LOCATION 3 HORIZONTAL DRAIN PAN INSTALLATION CONVERSION 4 DIMENSIONS DUCT CONNECTORS 5 AIR FILTERS 6 SUSPENSION KITS 6 COIL METERING DEVI...

Page 2: ...butor for more information Also check to be sure all accessories such as heater kits or suspension kits are available Installation of these accesso ries or field conversion of the unit should be accom...

Page 3: ...trapped and piped to a location that will give the occu pant a visual warning that the primary drain is clogged If the secondary drain is not used it must be capped 7 Proper electrical supply must be...

Page 4: ...fe if not previously cut out 8 Re position and replace access panels DO NOT TRY TO KNOCK OUT Models F 2 3 FP045 048 060 have a coil baffle and support bracket factory installed for right hand hori zon...

Page 5: ...s unit is not designed for non ducted freeblow applications Size outlet plenum or transition to discharge opening sizes shown in Figure 5 Duct work should be fabricated and installed in accordance wit...

Page 6: ...is a valid system match for the AC or HP unit installed The TXV is fully brazed into the coil assembly of this Air Han dler unit at the factory The temperature sensing bulb will need to be attached t...

Page 7: ...orifice with a small diameter wire or paper clip 2 Remove the new orifice from the packet and verify that it is the correct number required Install this orifice with the rounded end toward the coil a...

Page 8: ...igure 10 LOW VOLTAGE CONTROL CONNECTION The 24 volt power supply is provided by an internally wired low voltage transformer which is standard on all models However if the unit is connected to a 208 vo...

Page 9: ...OWER SUPPLY 3 GND LUG POWER SUPPLY GND LUG POWER WIRING 208 230 1 60 NOTE USE ONLY COPPER CONDUCTORS FIGURE 12 Control Board FIGURE 13 Blower Speed Connections R Y G W2 W1 O C 2 4 V A C BREAK TAB FOR...

Page 10: ...085 1100 Voltage 208 230 Amps Full Load 208 230 2 5 2 2 4 4 3 8 3 0 2 7 3 4 3 3 50 Hz 2 4 4 5 4 4 50 Hz 5 7 Locked Rotor 208 230 6 2 5 5 11 9 10 3 4 8 4 1 4 6 4 0 8 4 7 3 Filter1 Type DISPOSABLE OR PE...

Page 11: ...0 2HK 6500806B LO 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B LO 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B HI 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 042 N H 06 2HK 6...

Page 12: ...95 2 90 100 3 3 040H06 2HK 6500506B 20 8 25 8 28 7 30 30 10 10 2HK 6500806B 31 3 36 7 41 7 40 45 8 8 2HK 6501006B 41 7 48 1 54 7 50 60 8 6 2HK16501506B 62 5 70 9 80 8 80 90 4 3 042 N H 06 2HK 6500506...

Page 13: ...5 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 030 N H 06 2HK06501025B 0 5 LO 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK06501525B 0 5 HI 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 036 N H 06 2HK06501025...

Page 14: ...25 0 71 7 85 3 4 2 5 0 12 6 15 0 21 0 25 0 F2RP060N93 2HK 6500506B 0 5 LO 4 2 5 0 14 3 17 1 4 2 5 0 4 2 5 0 4 2 5 0 2HK 6500806B LO 6 3 7 5 21 5 25 6 4 2 5 0 6 3 7 5 6 3 7 5 2HK 6501006B LO 8 4 10 0...

Page 15: ...E PHASE HEATERS Model Heater Model Min CFM Max Static Total Heat1 KW Staging KW MBH W1 Only W2 Only W1 W2 Static Tap 220V 240V 220V 240V 220V 240V 220V 240V 220V 240V F2RP024N93 2HK06501025B 0 5 LO 8...

Page 16: ...gh 1575 1535 1475 1390 1310 1418 1382 1328 1251 1179 Med high 1375 1315 1255 1185 1110 1238 1184 1130 1067 999 Med low 1210 1160 1110 1050 980 1089 1044 999 945 882 Low 1035 990 940 890 825 932 891 84...

Page 17: ...64 Med 2125 3613 2020 3434 1910 3247 1805 3069 1705 2899 Low 1655 2814 1605 2729 1550 2635 1500 2550 1450 2465 MODEL Blower Motor Speed 220 Volt 50 HZ CFM or M3 H External Static Pressure IWG or PA 0...

Page 18: ...T PUMP FIELD INSTALLED JUMPER TERMINAL NOT AVAILABLE ON ALL THERMOSTATS FAN COIL UNIT R Y G W2 W1 O C O R Y G T E W O X R B Y W NOTE TO CHANGE HEAT QUANTITY DURING DEFROST REVERSE CONNECTIONS AT W1 W2...

Page 19: ...s to be cleaned or replaced it should be washed with Calgon coilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Soluti...

Page 20: ...without notice Printed in U S A 035 14520 001 Rev B 0803 Copyright by York International Corp 2003 All rights reserved Supersedes 035 14520 001 Rev A 0902 Unitary 5005 Norman Products York OK Group D...

Reviews: