FORM 100.50-EG5 (108)

21

JOHNSON CONTROLS

Cooling Performance Data — 

060 Model

TABLE 10

 – COOLING PERFORMANCE DATA* - 60 TON (STANDARD CAPACITY )

Air on 

Evaporator Coil

Temperature of Air on Condenser Coil

85°F

95°F

CFM

WB 

(°F)

Total 

Cap.

1

 

(MBH)

Total

2

 

Input 

(kW)

Sensible Capacity (MBH)

Return Dry Bulb (°F)

Total 

Cap.

1

 

(MBH)

Total

2

 

Input 

(kW)

Sensible Capacity (MBH)

Return Dry Bulb (°F)

86

83

80

77

74

71

68

86

83

80

77

74

71

68

12000

73

802

55

456

416

375

336

295

-

-

768

60

441

402

361

322

281

-

-

67

722

53

539

499

459

419

379

338

296

691

59

524

484

444

404

364

323

282

62

664

52

612

571

529

488

448

407

366

636

57

598

556

514

473

433

392

352

56

644

51

644

626

-

-

-

-

-

621

57

621

604

586

-

-

-

-

14000

73

830

55

486

441

394

348

301

-

-

793

61

471

426

380

333

286

-

-

67

749

54

583

537

491

445

398

351

303

715

59

568

522

476

429

383

336

288

62

692

53

671

622

572

525

478

431

384

663

58

656

606

559

510

463

416

369

56

685

52

685

666

646

627

578

530

480

660

57

660

641

622

603

563

514

465

16000

73

852

56

515

464

412

359

306

-

-

813

61

500

449

397

344

291

-

-

67

769

54

625

573

521

469

416

362

308

736

59

613

558

505

453

401

347

293

62

722

53

722

672

616

560

507

454

401

695

58

695

656

602

544

491

438

385

56

721

52

721

700

679

658

623

566

510

694

58

694

673

653

633

607

551

494

18000

73

869

56

543

486

428

369

310

-

-

828

61

528

470

413

354

295

-

-

67

788

54

670

608

550

491

433

373

313

751

60

654

592

534

476

417

357

297

62

752

53

752

720

658

594

535

475

416

724

59

724

702

643

581

519

460

400

56

751

53

751

729

707

685

663

602

539

723

58

723

701

679

658

637

587

522

20000

73

883

56

570

507

444

379

313

-

-

841

62

554

491

428

363

298

-

-

67

804

55

714

642

578

514

449

383

316

766

60

697

628

562

497

433

367

301

62

779

54

779

755

699

630

562

496

430

749

59

749

726

683

613

545

480

414

56

778

53

778

754

731

708

685

638

569

748

59

748

725

702

680

657

622

552

22000

73

894

57

596

527

458

388

317

-

-

852

62

580

511

443

372

301

-

-

67

816

55

753

680

605

535

464

392

320

780

60

738

663

589

518

448

376

304

62

803

54

803

778

739

663

588

516

444

772

59

771

747

721

648

571

500

428

56

802

54

802

777

753

728

705

672

595

771

59

770

746

722

699

676

652

580

24000

73

904

57

621

547

472

396

320

-

-

860

62

605

531

456

380

304

-

-

67

831

55

796

712

631

555

479

402

323

793

60

778

698

614

539

462

386

308

62

824

54

824

798

772

696

612

535

457

791

60

791

766

741

680

595

519

441

56

823

54

823

797

771

746

722

697

623

790

60

790

765

740

716

692

668

608

105°F

115°F

12000

73

730

66

425

386

345

306

265

-

-

688

74

408

369

329

289

249

-

-

67

657

65

508

468

428

388

348

308

266

619

72

490

450

411

371

331

291

250

62

604

64

581

539

497

457

417

376

336

571

71

564

522

481

439

399

359

319

56

596

63

596

579

562

543

501

458

417

568

70

568

552

535

519

484

442

400

14000

73

753

67

455

410

364

318

271

-

-

709

74

437

392

347

300

254

-

-

67

678

65

550

505

459

413

367

320

272

640

72

535

487

441

395

349

302

255

62

634

64

634

590

541

493

446

400

353

604

71

604

572

524

475

428

382

335

56

633

64

633

614

596

577

546

497

448

603

71

603

585

567

549

528

479

430

16000

73

770

67

483

432

381

328

275

-

-

724

74

465

414

363

311

258

-

-

67

697

66

595

540

488

436

384

330

277

657

73

579

522

470

418

366

313

259

62

665

64

666

639

584

527

474

421

368

633

72

633

614

566

511

456

403

350

56

664

64

664

644

624

605

585

533

477

632

71

632

613

593

574

555

516

460

18000

73

784

68

511

453

396

338

278

-

-

737

75

492

435

378

320

261

-

-

67

713

66

639

574

517

458

400

341

281

671

73

621

559

498

440

382

323

263

62

693

65

693

671

626

563

501

442

383

658

72

658

638

607

546

483

424

365

56

692

65

692

670

649

628

608

570

507

657

72

657

637

616

596

576

551

488

20000

73

796

68

537

474

411

347

282

-

-

747

75

519

456

393

329

264

-

-

67

727

66

681

612

544

480

416

350

284

684

73

662

592

525

461

397

332

267

62

716

65

716

694

665

597

527

462

397

680

72

680

658

637

580

508

444

378

56

715

65

715

693

671

649

627

603

535

679

72

679

657

636

615

594

573

516

22000

73

805

68

563

494

425

355

285

-

-

755

75

544

476

407

337

268

-

-

67

741

66

722

648

571

501

431

360

288

700

73

700

628

551

482

412

342

270

62

737

65

737

713

690

631

552

482

410

699

73

699

677

654

612

537

463

391

56

736

65

736

713

689

666

644

621

562

698

73

699

676

653

631

609

587

544

24000

73

813

68

588

513

439

363

287

-

-

762

75

569

495

421

345

270

-

-

67

756

67

756

679

596

521

445

369

291

717

74

717

662

582

502

426

350

272

62

755

66

755

731

707

663

581

501

423

716

73

716

693

669

642

562

482

404

56

754

66

755

730

706

682

659

635

590

715

73

715

692

668

646

623

600

569

* Rated performance is at sea level. Cooling capaciites are gross cooling capacity.

Summary of Contents for ECO HFC-410A

Page 1: ...Packaged Rooftop Air Conditioning Units Simplicity Elite with HFC 410a refrigerant 50 THROUGH 65 TONS FORM 100 50 EG5 108 TM MEA 231 02 E ASHRAE 90 1 COMPLIANT 00873VIP...

Page 2: ...cess doors spa cious compartments and supportive floors improves serviceability Note that modulating heat is not offered with Elite controller option Simplicity Elite controller Option Better Ecology...

Page 3: ...Data 051 Model 20 10 Cooling Performance Data 060 Model 21 11 Cooling Performance Data 061 Model 22 12 Supply Fan Performance Forward Curved 23 13 Supply Fan Performance Airfoil 23 14 Component Stati...

Page 4: ...onnect switch This option is the same the single point with terminal block option except it includes a unit mounted through the door manual non fused disconnect switch with an external lockable handle...

Page 5: ...elief Optional building air exhaust shall be accomplished through barometric relief dampers in stalled in the return air plenum The dampers will open relative to the building pressure The opening pres...

Page 6: ...ompressor should ever fail on one circuit the other circuit will remain operational to work to maintain occu pied loads The Eco2 system has 2 circuits in a unit Condenser Fan Motors The condenser fan...

Page 7: ...ide an alarm when the filters require cleaning Magnahelic Filter Pressure Gauge On units equipped with downstream filtration a magnahelic filter gauge is included and visible on the exterior of the un...

Page 8: ...the roof top unit away from sound sensitive areas such as conference rooms auditoriums and executive offices and any other room that may have potential for tenant occupancy Pos sible locations could...

Page 9: ...esign and construction is a must in today s market in order to insure safe and sound applications of HVAC equipment The Eco2 has been designed for spe cific application of horizontal supply and return...

Page 10: ...ers wet bro mide chlorine and fluorine in concentrations greater than 100 ppm Any of the above suitable options should be selected based on the particular project design parameters and related environ...

Page 11: ...power fans For VAV applications VFDs are used instead of inlet guide vanes Additional sound attenuation can be obtained using compressor sound blankets and field supplied sound attenuators when necess...

Page 12: ...JOHNSON CONTROLS 12 FORM 100 50 EG5 108 This page intentionally left blank...

Page 13: ...A 6 460 3 60 A Standard Product Simplicity Elite L Scroll 0 6 1 65 Ton Capacity 8 575 3 60 B Special Product Simplicity Elite C V F F B Bottom Return C R Rear Return L Left Return n r u t e R e d i S...

Page 14: ...2 1 2 1 2 1 2 1 Type FC FC FC FC Size 18 18 18 18 18 18 18 18 Motor Size Range HP 5 20 5 20 5 20 5 20 Air Flow Range CFM 4 000 22 500 4 000 22 500 4 000 24 000 4 000 24 000 Static Pressure Range Total...

Page 15: ...1 4 9 1 4 9 Size length x width in 16x20 25x16 25x20 16x20 25x16 25x20 16x20 25x16 25x20 16x20 25x16 25x20 Total Filter Face Area square feet 43 0 43 0 43 0 43 0 Filters 12 rigid 95 2 30 prefilter pre...

Page 16: ...8 13 58 25 0 50 0 75 0 100 0 060 ZP182 ZP137 ZP182 ZP137 17 95 13 30 17 95 13 30 28 7 57 4 78 7 100 0 061 ZP182 ZP137 ZP182 ZP154 17 95 13 30 17 60 14 86 28 2 55 8 76 7 100 0 TABLE 5 PHYSICAL DATA UNI...

Page 17: ...at high altitude is less dense less static pressure will be generated and less power will be required than a similar application at sea level Air density correction factors are shown in Table 7 and F...

Page 18: ...JOHNSON CONTROLS 18 FORM 100 50 EG5 108 FIG 2 ALTITUDE TEMPERATURE CONVERSION FACTOR...

Page 19: ...627 606 585 531 664 49 664 643 621 601 580 560 518 24000 73 751 46 535 468 401 332 264 715 51 521 454 388 319 252 67 708 45 708 637 548 478 409 340 269 680 50 680 626 534 465 396 327 256 62 707 44 708...

Page 20: ...37 54 547 477 405 333 261 67 726 48 726 655 573 500 427 353 278 697 53 697 642 558 486 413 339 265 62 726 47 726 703 680 640 556 482 407 697 52 697 674 652 625 546 468 393 56 725 47 725 702 680 657 63...

Page 21: ...531 456 380 304 67 831 55 796 712 631 555 479 402 323 793 60 778 698 614 539 462 386 308 62 824 54 824 798 772 696 612 535 457 791 60 791 766 741 680 595 519 441 56 823 54 823 797 771 746 722 697 623...

Page 22: ...59 628 553 479 402 326 876 64 611 537 462 386 310 67 844 57 801 718 638 561 485 407 329 806 62 784 703 620 545 468 391 313 62 836 56 836 809 780 702 618 541 463 803 61 803 777 752 685 601 524 446 56...

Page 23: ...5 36 9 830 24000 15 7 496 20 8 586 26 8 700 33 752 40 832 26000 19 1 522 24 5 607 30 5 686 37 3 762 TABLE 13 28 AIRFOIL FAN Total Static Pressure inches of water column CFM STD AIR 1 0 2 0 3 0 4 0 5 0...

Page 24: ...0 08 0 10 0 12 0 15 0 19 0 22 Filters 2 Throwaway 0 07 0 08 0 09 0 11 0 12 0 13 0 15 0 16 2 Cleanable 0 01 0 01 0 02 0 03 0 03 0 04 0 05 0 07 2 Pleated 0 06 0 07 0 08 0 10 0 12 0 14 0 16 0 19 2 Carbon...

Page 25: ...pressure determine the brake horsepower and RPM of the exhaust fan TABLE 15 FORWARD CURVED FAN CFM STD AIR Total Static Pressure inches of water column 0 3 0 5 0 8 1 BHP RPM BHP RPM BHP RPM BHP RPM 6...

Page 26: ...5 x LOAD1 LOAD2 LOAD3 LOAD4 MOP 2 25 x LOAD1 LOAD2 LOAD3 LOAD4 If the MOP does not equal a standard current rating of an overcurrent protective device then the marked maximum rating is to be the next...

Page 27: ...5 18 9 25 66 0 62 0 31 0 23 8 25 63 3 60 0 30 0 24 2 30 84 0 72 0 36 0 29 0 30 74 1 70 0 35 0 28 0 40 106 0 98 0 49 0 38 8 40 97 5 92 0 46 0 37 4 TABLE 19 SUPPLY AND EXHAUST FAN MOTOR DATA TEFC High...

Page 28: ...nected to and operated by a Building Automation System BAS The Rooftop Unit controller is equipped with a Modbus RTU communica tion Optional BACnet MSTP is available with a Modlinc translator which al...

Page 29: ...utside Air is deemed suitable for economizing when the Outside Air enthalpy is determined to be less than the Return Air enthalpy and the Outside Air tem perature is less than the reference temperatur...

Page 30: ...he refrigeration system discharge pressure and controls the speed of the first stage condenser fan If the discharge pressure falls the speeds of the condenser fan is re duced to maintain acceptable co...

Page 31: ...unit remains idle until it receives a stage call from the thermostat If G is called from the thermostat the Supply Fan will start Ventilation functions if equipped will be permitted to run with an oc...

Page 32: ...are Folded Inside Unit for Shipment SECTION DESCRIPTIONS EE Economizer FE Fan Exhaust _F Filter Segments CC Cooling Coils FS Supply Fan DP Discharge Plenum CO Condenser Section 46 00 60 00 1 1 4 FPT D...

Page 33: ...for Shipment SECTION DESCRIPTIONS EE Economizer FE Fan Exhaust _F Filter Segments CC Cooling Coils FS Supply Fan DP Discharge Plenum CO Condenser Section LD08296 76 48 7 76 6 36 36 28 66 00 227 25 19...

Page 34: ...Economizer FE Fan Exhaust _F Filter Segments CC Cooling Coils FS Supply Fan DP Discharge Plenum CO Condenser Section LD08370 6 28 38 37 49 94 4 79 GAS BURNERS GAS LINE CONNECTION 2 1 2 GAS OUTLET 1 1...

Page 35: ...nit fit up leak integrity or sound level for installation using field fabricated roof curbs 4 The YPAL unit does not have a base pan under the condensing section of the unit Field fabricated roof curb...

Page 36: ...n Perimeter Curb 544 544 544 544 Condenser Coil Wire Guard 64 64 64 64 Copper Evaporator Coils additional 312 312 416 416 Copper Condenser Coils additional 516 516 773 773 12 Rigid Filters additional...

Page 37: ...w Econ Heating 2118 2521 2041 1715 2118 2521 2041 1715 Basic Unit w Econ Heating Power Exhaust 2366 2751 2034 1750 2366 2751 2034 1750 Model 060 061 A B C D A B C D Basic Unit 1894 2244 1986 1676 1893...

Page 38: ...rts for units 2 Roof curb transition 3 Piping size and connection header locations 4 Electrical power requirements and wire conduit and overcurrent protection sizes 5 All costs incurred to modify the...

Page 39: ...all be continuously caulked and covered with formed galvanized seam caps All panel fasteners shall be secured through standing seams to prevent fastener penetrations that are exposed to the air stream...

Page 40: ...d with standard hydraulic grease fittings and lube lines extended to the motor side of the fan Fan drives shall be selected for a 1 5 service factor and antistatic belts shall be furnished All drives...

Page 41: ...r failure Discharge Plenum SELECT ONE OF THE FOLLOWING HEAT NO HEAT CONFIGURATIONS 1 Cooling Only The discharge air temperature sen sor shall be located in the discharge plenum and be located such tha...

Page 42: ...means of isolating the refrigerant charge in the system so that the refrigeration system may be serviced without removing the charge of the unit Controls Simplicity Elite 1 Enclosure Unit shall be shi...

Page 43: ...t with weath erproof enclosures variable frequency drives and end devices shall be effectively covered for protec tion against rain snow wind dirt sun fading road salt chemicals rust and corrosion dur...

Page 44: ...861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by Johnson Controls 2007 ALL RIGHTS RESERVED Form 100 50 EG5 108 Supersede...

Reviews: