15
JOHNSON CONTROLS
FORM 100.50-SU3 (1207)
“VAV OCCUPIED HEATING SETPOINT”
– Must be
set using Parameter 27 under the PROGRAM key on
the Simplicity control board or under the HEATING
SETUP tab in the Simplicity PC software package.
Settable between 40.0º F and 85.0º F. The default value
is 68.0º F.
“MORNING WARM-UP / VAV RETURN AIR TEMP
SETPOINT”
– Must be set using Parameter 29 under
the PROGRAM key on the Simplicity control board or
under the COOLING SETUP tab in the Simplicity PC
software package. Settable between 50.0º F and 85.0º
F. The default value is 70.0º F.
“SPACE SENSOR FAULT OVERRIDE ENABLED”
– Must be set to ON using Parameter 8 under the
PROGRAM key on the Simplicity control board or
under the SYSTEM OPTIONS tab in the Simplicity
PC software package.
“STAGES OF HEATING AVAILABLE”
- Must be set
using Parameter 81 under the PROGRAM key on the
Simplicity control board or under the HEATING SETUP
tab in the Simplicity PC software package.
“DUCT PRESSURE SETPOINT”
– Must be set
using Parameter 30 under the PROGRAM key on the
Simplicity control board or under the FAN tab in the
Simplicity PC software package. Settable between 0.0
and 5.0 INWC. The default value is 1.5 INWC.
“DUCT PRESSURE SHUTDOWN SETPOINT”
– Must
be set under the FAN tab in the Simplicity PC software
package. Settable between 0.0 and 5.0 INWC. The
default value is 4.5 INWC.