JOHNSON CONTROLS
16
FORM 100.50-EG5 (108)
Physical Data
TABLE 6 –
PHYSICAL DATA - COMPRESSORS
Compressors Utilized
Compressor Nominal Tons
% Capacity Per Stage
System 1
System 2
System 1
System 2
“Compr
# 1”
“Compr
# 2”
“Compr
# 3”
“Compr
# 4”
“Compr
# 1”
“Compr
# 2”
“Compr
# 3”
“Compr
# 4”
“Stage
1”
“Stage
2”
“Stage
3”
“Stage
4”
Model
050
ZP137
ZP120
ZP137
ZP120
13.58
12.53
13.58
12.53
26.0
52.0
76.0
100.0
051
ZP137
ZP137
ZP137
ZP137
13.58
13.58
13.58
13.58
25.0
50.0
75.0
100.0
060
ZP182
ZP137
ZP182
ZP137
17.95
13.30
17.95
13.30
28.7
57.4
78.7
100.0
061
ZP182
ZP137
ZP182
ZP154
17.95
13.30
17.60
14.86
28.2
55.8
76.7
100.0
TABLE 5 –
PHYSICAL DATA – UNIT EER
EER
Model
Supply Blower
Type
Cooling Only
Gas Heat
YPAL050
Forward-Curved
10.3
10.0
Air Foil
10.3
10.1
YPAL051
Forward-Curved
10.2
9.9
Air Foil
10.2
10.0
YPAL060
Forward-Curved
10.1
9.8
Air Foil
10.1
9.9
YPAL061
Forward-Curved
10.1
9.8
Air Foil
10.1
9.9
TABLE 4 –
EFFICIENCY RATINGS
CV
IEER
VAV
IEER
Model
IPLV
YPAL050
10.9
11.3
13.5
YPAL051
10.6
11.2
13.1
YPAL060
10.4
11.0
13.4
YPAL061
10.3
10.8
13.2