TECHNICAL GUIDE

STEALTH

SPLIT-SYSTEM HEAT PUMP

15 SEER

MODELS: E4TS030 THRU 060

(2.5 THRU 5 NOMINAL TONS)

Due to continuous product improvement, specific
tions are subject to change without notice.

Visit us on the web at www.york.com for the most 
up-to-date technical information.

Additional rating information can be found at 
www.ariprimenet.org.

LISTED

ISO 9001

Certified Quality

Management System

CERTIFICATION APPLIES ONLY

WHEN THE COMPLETE

SYSTEM IS LISTED

WITH ARI.

U

N

IT

AR

Y

HE

AT

P

U

M

P

T

E QUI P ME N

R

S E CT

I O

N S

A T I O N

E

RT

I F I

C

C

O

F

D

S T A N D A R

I

AR

2 4

0

M

A

N

U

F

A

C

TU

R

E

R

CE

RT

I F I

E D

C

LY

OM

P

I

NG

T O A R I AS

DESCRIPTION

The ETS Stealth series heat pump units use Twin Single

compressor technology to provide cooling efficiencies up to
15.7 SEER and heating efficiencies up to 9.3 HSPF. They are
to be installed with the matching variable speed Enhancer air
handler or Diamond furnace, a corresponding coil and sweat
connect lines. A factory specified balanced port hard shut-off
TXV kit must be used for proper installation and optimum per-
formance.

WARRANTY

5-year limited parts warranty.
10-year limited compressor warranty.

FEATURES

QUALITY CONDENSER COILS  -  The coil is constructed of
copper tube and hardened aluminum fins for durability and long
lasting efficient operation. The fins on the unit are protected
with a decorative grille.
DURABLE FINISH - Cabinet is made of powder painted steel
over pre-painted primer. The pre-treated flat galvanized steel
provides a better paint to steel bond, which resists corrosion
and rust creep. Special primer formulas and glossy earth tone
finish insure less fading when exposed to sunlight. This finish
has been tested to provide 1/3 greater protection than conven-
tional units.
PROTECTED COMPRESSORS - The Twin Single

™ 

compres-

sor is protected against high pressure. Hard start components
are included to ensure start-up under adverse conditions. All
models

 

have standard crankcase heat for added protection.

OPTIMUM PERFORMANCE - The solid-state electronic con-
trolboard optimizes the compressor staging based on load
requirements, provides a 5-minute anti-short cycle timer, and
simplifies troubleshooting with built in self diagnostics.
LOWER INSTALLED COST - Installation time and costs are
reduced by easy power and control wiring connections. All
units contain enough refrigerant for the smallest matching
indoor coil and 15 feet of interconnecting piping. The small
base dimension means less space is required on the ground or
roof.
EFFECTIVE HUMIDITY CONTROL - The inherent design of
the Stealth system and the staging operation of the Twin Sin-
gle

™ 

compressor provide effective humidity control at the low-

est possible operating cost. An optional dehumidification
control accessory is available to maintain the humidity at a set
desired level.
TOP DISCHARGE - The warm air from the top mounted fan is
blown up away from the structure and any landscaping. This
allows compact location on multi-unit  applications.
LOW OPERATING SOUND LEVEL - The upward air flow car-
ries the normal operating noise up away from the living area.
The rigid top panel effectively isolates any motor sound. Isola-
tor mounted compressor and the rippled fins of the condenser
coil muffle the normal fan motor and compressor operating
sounds.
LOW MAINTENANCE - Long life permanently lubricated
motor- bearings need no annual servicing.
EASY SERVICE ACCESS - Fully exposed refrigerant connec-
tions and a single panel covering the electrical controls make
servicing easy. Easy access for coil clearing is also provided.
RE-USABLE SERVICE VALVES - Provided on both the liquid
and vapor sweat connections for ease of evacuating and
charging.

Summary of Contents for E4TS030

Page 1: ...been tested to provide 1 3 greater protection than conven tional units PROTECTED COMPRESSORS The Twin Single compres sor is protected against high pressure Hard start components are included to ensure...

Page 2: ...hermostat calls for second stage cooling Y2 on two consecutive cooling cycles the next call for cooling for either first or second stage will energize the unit in second stage mode The above mode will...

Page 3: ...2650 3200 3200 COIL FACE AREA SQ FT 20 0 20 0 20 0 20 0 ROWS DEEP 1 1 2 2 FIN INCH 16 16 13 13 LIQUID LINE OD 3 8 3 8 3 8 3 8 VAPOR LINE OD 7 8 7 8 7 8 7 8 UNIT CHARGE LBS OZ 3 3 The Unit Charge is c...

Page 4: ...TIONAL CHARGE OZ G1FA G1UA048S17 21 78 701 0 702 0 G1FA G1UA060S21 24 84 702 10 703 0 703 0 G1FA060S21 24T 84 703 0 703 0 G2FD046 S H 17 78 701 0 702 0 G2FD042 S H 21 78 701 0 G2FD048 S H 21 24 84 701...

Page 5: ...040 27400 22200 15 2 13 8 2 1605 49000 36400 11 6 E4TS060 F 2 3 FV060 10 15 20 25 24 1 1220 27800 23400 14 5 13 2 2 1875 55500 40500 10 4 N1VSD20 7 5 10 15 20 25 30 G2FD060S24 1 1200 27800 23400 14 5...

Page 6: ...1 1 640 20200 15200 14 1 12 5 2 1200 35800 25800 11 2 G2FD048S21 1 640 20400 15400 14 3 12 8 2 1200 36000 26000 11 3 G1UA060S21 1 640 21000 15800 14 6 13 1 2 1200 37000 26600 11 4 G1FA060S21 1 640 210...

Page 7: ...20V 24 G2FD060S24 1 1000 27000 20400 13 7 12 6 2 1800 55000 39600 10 0 G2FD061H24 1 1000 28000 20800 14 0 12 8 2 1800 56000 40000 10 2 P1XUD20V 24 G1UA060S24 1 990 27000 20400 13 8 12 5 2 1800 55500 4...

Page 8: ...1065 27000 16000 9 2 3 64 E4TS036 N1VSC16 5 7 5 10 15 20 21 G2FD048S21 1 770 19600 3 78 2 770 31600 19000 8 7 3 52 2 1185 35000 20800 9 2 3 54 N1VSD20 7 5 10 15 20 25 30 24 G2FD048S24 1 780 20000 3 8...

Page 9: ...540 12400 3 54 2 540 24200 14200 8 3 3 39 2 1050 26400 15400 8 6 3 58 G1FA048S17 1 540 12400 3 54 2 540 24200 14200 8 3 3 39 2 1050 26400 15400 8 6 3 58 P1XUC16V075 21 G2FD042S21 1 600 13000 3 70 2 60...

Page 10: ...2400 19000 8 1 3 44 2 1220 36000 21200 8 5 3 70 G1FA048S21 1 650 17200 3 52 2 650 32400 19000 8 1 3 44 2 1220 36000 21200 8 5 3 70 G2FD048S21 1 650 17400 3 54 2 650 32600 19400 8 2 3 48 2 1220 36200 2...

Page 11: ...0 3 64 2 715 33400 20200 8 7 3 64 2 1260 37000 22400 9 0 3 90 G1FA060S24 1 715 18800 3 64 2 715 33400 20200 8 7 3 64 2 1260 37000 22400 9 0 3 90 E4TS048 P1XUC16V075 21 G1UA060S21 1 880 20800 3 24 2 88...

Page 12: ...4 G2FD061H24 1 915 22600 3 40 2 915 45000 25600 8 0 3 44 2 1620 48500 27600 8 3 3 62 E4TS060 P1XDD20V112 G2FD060S24 1 1000 23400 3 38 2 1000 49500 26000 7 5 3 28 2 1800 54000 28400 7 9 3 46 G2FD061H24...

Page 13: ...90 23 26 17 97 23 41 K W 3 06 2 90 2 79 2 79 2 77 3 09 2 94 2 86 2 86 2 85 3 12 2 97 2 93 2 93 2 92 E4TS030S06A WITH N1VSC1606 G2FD048S21 LOW CFM 1 CYLINDER OPERATION CONDENSER ENTERING AIR TEMPERATU...

Page 14: ...5 3 54 3 42 3 33 3 33 3 24 115 T C 33 74 30 98 28 42 28 42 27 19 34 01 31 83 29 53 29 53 29 18 34 29 32 67 30 65 30 65 31 18 S C 16 85 22 69 26 44 21 15 26 79 18 07 24 40 27 91 22 31 28 98 19 30 26 12...

Page 15: ...27 17 56 14 12 18 17 11 73 15 40 17 40 13 89 18 84 12 54 16 87 17 24 13 66 19 51 K W 1 62 1 58 1 56 1 56 1 56 1 64 1 61 1 59 1 59 1 58 1 66 1 63 1 61 1 61 1 60 Air Handler Coil T C S C KW N1VSD20 G2FD...

Page 16: ...4 57 4 57 4 48 5 27 5 03 4 75 4 75 4 64 5 47 5 20 4 93 4 93 4 80 E4TS048S06A WITH N1VSD2006 G2FD060S24 LOW CFM 1 CYLINDER OPERATION CONDENSER ENTERING AIR TEMPERATURE ID CFM 850 1040 1140 ID DB F 80 8...

Page 17: ...81 125 T C 49 61 47 33 43 91 43 91 42 66 50 19 47 59 45 10 45 10 44 17 50 77 47 86 46 28 46 28 45 69 S C 26 29 36 41 43 93 35 07 40 19 27 46 38 64 45 25 35 77 42 94 28 63 40 87 46 58 36 46 45 69 K W...

Page 18: ...36 1 08 20 52 1 09 20 67 1 09 70 18 50 1 16 18 66 1 17 18 81 1 17 80 16 64 1 24 16 79 1 25 16 95 1 25 47 60 16 02 1 05 16 15 1 06 16 28 1 08 70 14 90 1 12 15 00 1 13 15 10 1 14 80 13 77 1 19 13 85 1 2...

Page 19: ...KW MBTUH KW N1VSB12 G2FD046S17 0 98 1 04 0 89 0 94 Variable Speed Furnace Coil MBTUH KW MBTUH KW P1XDB12V G2FD046S17 0 97 1 03 0 87 0 96 P1XUB12V G2FD046S17 0 97 1 02 0 87 0 95 P1XUB12V G1UA048S17 0...

Page 20: ...12 G2FD046S17 0 98 1 00 Variable Speed Furnace Coil MBTUH KW P1XDB12V G2FD046S17 0 87 0 94 P1XUB12V G2FD046S17 0 86 0 94 P1XUB12V G1UA048S17 0 87 0 94 P1XUB12V G1FA048S17 0 87 0 94 P1DUB16V G2FD046S17...

Page 21: ...1 1 87 70 27 16 2 00 28 00 2 00 28 83 2 00 80 24 88 2 12 25 62 2 12 26 36 2 13 47 60 25 88 1 80 26 28 1 81 26 68 1 81 70 23 31 1 90 23 80 1 91 24 29 1 91 80 20 73 1 99 21 32 2 00 21 90 2 01 35 60 22 7...

Page 22: ...12 53 2 72 12 80 2 81 E4TS060S06A WITH N1VSD2006 G2FD061S21 LOW CFM 1 CYLINDER OPERATION ID CFM 1000 1200 1350 OD DB ID DB F MBTUH1 2 KW MBTUH1 2 KW MBTUH1 2 KW 60 60 36 04 2 14 36 57 2 14 37 10 2 13...

Page 23: ...3 MATCHING INDOOR COMPONENTS G1UA UPFLOW G2FD MULTI POSITION UPFLOW HORIZONTAL AND DOWNFLOW G1FA FULL CASED AIR HANDLERS FOR NON FURNACE APPLICATIONS N1VS MODULAR BLOWER UPFLOW HORIZONTAL AND DOWNFLOW...

Page 24: ...e without notice Printed in U S A 036 21342 002 Rev E 0505 Copyright by York International Corp 2005 All rights reserved Supersedes 036 21342 002 Rev D 1104 Unitary 5005 Norman Product York OK Group D...

Reviews: