background image

 

10

Unitary Products Group

Superheat Charging Method

NOTE: Use this method only during system maintenance and

repair.

1.

Operate system until temperatures and pressures stabi-
lize (minimum of 10 minutes).

2.

Measure and record indoor wet bulb (WB) temperature
using a sling psychrometer and the outdoor dry bulb
(DB) temperature using a thermometer.

3.

Measure and record the suction pressure at the suction
service valve port.

4.

Using Table 3, note the superheat value corresponding
to the intersection of the indoor wet bulb and the outdoor
dry bulb.

5.

With the superheat value obtained in step 4 and the suc-
tion pressure value from step 3, find the intersection of
the values in Table 4. This is the required suction tube
tempera-ture at the suction service valve.

6.

To bring the tube temperature in line with the required
value from Table 4, add refrigerant to the service port to
cause the tube temperature to fall and reclaim refrigerant
to cause the temperature to rise.

Check flare caps on Schrader fittings to be sure they are 
tight. DO NOT OVERTIGHTEN (40-60 inch-lbs. maximum).

SYSTEM START-UP

ENERGIZE CRANKCASE HEATER

This unit is equipped with a crankcase heater for the com-
pressor.

A warning label with an adhesive back is supplied in the unit 
installation instruction packet. This label should be attached 
to the field supplied disconnect switch where it will be easily 
seen. See below.

In order to energize the crankcase heater:- Set indoor two 
stage cooling thermostat to "OFF" position.- Close the line 
power disconnect to the unit.

SYSTEM OPERATION

See Figure 9 to trace the flow of refrigerant through the sys-
tem. 

WITH POWER TO UNIT AND THERMOSTAT IN COOLING 
POSITION.

1.

Reversing valve is energized through thermostat system
switch to position refrigerant circuit for cooling operation.
In the cooling cycle, discharge gas is pumped to the out-

door coil which is the condenser. The indoor coil is the
evaporator.

2.

If fan switch is in “ON” position, a circuit is made through
blower relay to provide continuous blower operation.

3.

When thermostat cooling contact closes, a circuit is
made to energize contactor and start the system, if the
compres-sor has been off for 5 minutes. There is an anti-
short cycle timer built into the defrost control requiring
the compressor to be off at least 5 minutes. With fan
switch in “AUTO” position, a circuit is made from thermo-
stat cooling contact through blower relay to provide
blower operation.

4.

System will cycle with thermostat demand to provide
cool-ing as needed.

WITH POWER TO UNIT AND THERMOSTAT IN HEATING 
POSITION

1.

Reversing valve is de-energized to position refrigerant
cir-cuit for heating operation. In the heating cycle, dis-
charge gas is pumped to the indoor coil which is the con-
denser. The outdoor coil is the evaporator.

2.

If fan switch is in “ON” position, a circuit is made through
blower relay to provide continuous blower operation.

3.

When first stage of thermostat heating contact closes, a
circuit is made through the control to energize contactor
and start the system, if the compressor has been off 5
minutes. There is an anti-short cycle timer built into the
defrost control requiring the compressor to be off at least
5 min-utes. With fan switch in “AUTO” position, a circuit
is made from thermostat heating contact through blower
relay to provide blower operation.

4.

The system will cycle in response to thermostat signal to
provide heating as needed.

5.

Supplemental electric heaters are energized by second
stage of heating thermostat.

SEQUENCE OF OPERATION COOLING:

On call for cooling, the thermostat makes 24V circuits: R to 
O, R to Y, and R to G. Circuit R to O energizes the reversing 
valve, switching it to cooling position. Circuit R to Y energizes 
the contactor, starting outdoor fan motor and compressor 
(after the anti-short cycle period). Circuit R to G energizes the 
indoor unit blower relay, starting the indoor blower motor.

HEATING:

On call for heating, thermostat makes circuits R to Y and R to 
G. Circuit R to Y energizes contactor, starting outdoor fan 
motor and compressor (after the anti-short cycle period). Cir-
cuit R to G energizes the indoor blower relay, starting the 
blower motor. 

Should the temperature continue to fall, R to W is made 
through the second stage of the thermostat. Circuit R to W 
energizes the supplemental electric heat. The field-installed 

IMPORTANT

 An attempt to start the compressor without at least 8
hours of crankcase heat will damage the compressor.

Summary of Contents for E4FD018-60

Page 1: ...ERAL INFORMATION GROUNDING 7 POWER WIRING 7 ACCESSORY WIRING 7 THERMOSTAT MOUNTING WIRING 7 EVACUATION 9 SYSTEM CHARGE 9 REFRIGERANT LINE CHARGES 9 MEASUREMENT METHOD 9 SUPERHEAT CHARGING METHOD 10 SY...

Page 2: ...that personal injury and or equipment damage may result if installation pro cedures are not handled properly INSPECTION As soon as a unit is received it should be inspected for possi ble damage during...

Page 3: ...ndensate will drain from beneath the coil of the outdoor unit during the defrost cycle Normally this condensate may be allowed to drain directly on the ground Elevate the unit sufficiently to prevent...

Page 4: ...an specified line size could result in oil return problems Using too small a line will result in loss of capacity and other problems caused by insufficient refrigerant flow Slope horizontal vapor line...

Page 5: ...n in Fig ure 5 Also protect all painted surfaces and insulation during brazing After brazing cool joint with wet rag Valve can be opened by removing the plunger cap and fully inserting a hex wrench in...

Page 6: ...hes retaining ring Release the refrigerant charge into the system See Precautions Dur ing Brazing Angle Valves on page 6 11 If the refrigerant tubing indoor evaporator coil or outdoor condensing unit...

Page 7: ...chematic wiring label is located on the inside surface of the unit electrical box cover and this instruction POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and within s...

Page 8: ...l block on the indoor unit for the actual arrangement of the terminals BREAKER ALL WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE AND OR LOCAL CODES Connect power wiring to terminal block 3TB...

Page 9: ...should be installed only with the tubing sizes for approved system com binations as specified in Tabular Data Sheet The charge given is applicable for total tubing lengths up to 15 feet See Applicati...

Page 10: ...he system if the compres sor has been off for 5 minutes There is an anti short cycle timer built into the defrost control requiring the compressor to be off at least 5 minutes With fan switch in AUTO...

Page 11: ...d an output to turn on a fault indicator light at the ther mostart through X L terminal Code flashed will be either 2 flashes if the pressure switch opens during cooling or heating mode or 3 flashes i...

Page 12: ...art the unit then the test terminals must be held for at least 10 seconds When the short is removed the heat pump will remain in defrost until the defrost thermostat opens or 10 minutes expires If the...

Page 13: ...for snow accumulation 3 Outdoor section for leaf or debris blockage Eliminate problem turn off the thermostat for 10 seconds and attempt start Wait 5 minutes If system does not start call serviceman...

Page 14: ...27 26 25 23 Evaporator Entering Air F Table 4 Temperature and Pressure SUCTION PRES SURE PSIG Service Port SUCTION SERVICE VALVE SUPERHEAT 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 61 5 35 37...

Page 15: ...93 176 35 108 220 02 49 82 389 64 109 26 79 141 30 94 179 06 109 223 17 50 84 03 65 111 23 80 143 63 95 181 80 110 226 35 51 85 69 66 113 22 81 145 99 96 184 56 111 229 56 52 87 38 67 115 24 82 148 37...

Page 16: ...n d i t i o n i n g Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A 035 17421 000 RevB Copyright by Unitary Products Group 1999 All right...

Reviews: