Fault codes noted, but system allowed to run:

  31 - Throttle stepper failure

  32 - Cam sensor failure

  33 - Enrichment sol. failure

  34 - Ignition coil failure

  38 - Engine crank prevent

  41 - Indoor sensor failure

  42 - Supply air temperature over 130

°

F

  43 - Supply air temperature over 170

°

F

  52 - Outdoor temp sensor failure

  56 - S. A. interface fault

  62 - NVM access failure

Operation Below -5

°

 F\ -10

°

 F (Electric Heat Only)

If the engine is running and the outdoor temperature drops
below -10

°

F, the engine will shutdown. Once shutdown, it is not

allowed to run until the temp is above -5

°

F.

The electric heater or add-on hot water hydronic coil will be
energized and will cycle, based on first stage heat require-
ments.

The indoor blower will run at full speed.

Emergency Heat

When the switch on the thermostat is moved to EM HT, the
engine will shutdown and the electric heater, add-on hot water
hydronic coil or furnace will provide necessary heat, respond-
ing to first stage requirements. The indoor blower will run at full
speed.

USER’S INSTRUCTION

Assist owner with processing warranty cards. Review User’s
Information Manual and provide a copy for the owner on
guidance on proper operation. Instruct the owner how to start,
stop and adjust the temperature setting.

Also, review annual maintenance requirements, defrost operation,
exhaust gases at the outdoor unit, and the variable motor speed
which may be noticed at the indoor unit and outdoor unit engine.

When the system is functioning properly and the owner has
been fully instructed, secure the owner’s approval. 

INDOOR AIR FILTER

Indoor filters are recommended to keep the duct system clean
and to collect dust, lint and other debris from entering the air
handling/coil sections.

Filters are recommended to be replenished (replace throw-
aways) every three months. If electronic air filters are installed,
they should be cleaned on a regular basis to keep their effi-
ciency at peak levels.

ENGINE

The engine system requires maintenance on a regular interval.

A service maintenance kit is available and should be used when
performing engine maintenance. It includes:

Engine oil (11 liters - prepackaged for use)

Engine oil filter

Engine air filter

Engine spark plug

Engine spark plug wire

A regular operating interval of 12 months is the maximum time
interval for maintenance of engine to maintain engine warranty.

At the time of engine maintenance, the following is also recom-
mended:

Outdoor Unit

Cleaning of inlet engine air screen, outlet auxiliary heat
screen, lower openings in access panel and louver openings
in access panel

Washing of outdoor coil, if necessary

Checking and replenishing coolant level in overflow tank

Indoor Unit

Cleaning of system air filter

Clean refrigerant coil

Clean indoor blower housing and wheel.

WARNING: Engine maintenance can only be done by
trained YORK Triathlon dealers. Homeowners and oth-
ers not trained will void the warranty by doing this work
themselves.

515.35-N6Y

Unitary Products Group

13

Summary of Contents for E3GE036S01B

Page 1: ...sitioned with any obstructions in the air stream The outdoor fan is the propeller type and is not designedtooperateagainstanyadditionalexternalstaticpressure The maximum and minimum conditions for operation must be observed to assure a system that will give maximum perform ance with minimum service Refer to Table 1 LOCATION Before starting the installation select and check the suitability of the l...

Page 2: ...m for proper operation 10 Instruct owner on operation of unit Unit is charged with enough refrigerant for outdoor unit indoor unit and 15 ft of each line TABLE 2 PHYSICAL AND ELECTRICAL DATA MODEL E3GE036 UNIT SUPPLY VOLTAGE 115 1 60 NORMAL VOLTAGE RANGE1 108 to 126 MINIMUM CIRCUIT AMPACITY 28 8 MAX OVERCURRENT DEVICE AMPS 30 MIN FIELD WIRE SIZE AWG 2 10 MAX WIRE LENGTH Ft 3 VOLTAGE DROP 49 24 VOL...

Page 3: ...de the unit 7 Install unit on a surface at least as large as the minimum base dimension shown in Figure 3 If required isolation pads can be used to eliminate direct contact with the house structure Refer to Figure 3 for pad placement 8 Make a hole s in the structure wall large enough to accom modate the insulated vapor line liquid line natural gas line and electrical wiring 36 1 2 38 43 CONTROL WI...

Page 4: ...MOSTAT REFRIGERANT LINES TO INDOOR SECTION GAS LINE NEC CLASS 2 WIRING 18 AWG MIN ENGINE EXHAUST WEATHERPROOF DISCONNECT SWITCH SEAL OPENINGS WITH PERMAGUM OR EQUIVALENT 36 OVERHEAD CLEARANCE NOTE ALL OUTDOOR WIRING MUST BE WEATHERPROOF MIN 12 CLEARANCE TO BUILDING 36 SERVICE ACCESS CLEARANCE FOR REMAINING THREE SIDES WARNING If outdoor unit is less than 60 from building no windows or other openin...

Page 5: ...voided by taking adequate precautions to assure an internally clean and dry system Always use refrigeration grade copper tubing that is internally clean and dry for refrigerant lines Use clean hard drawn copper tubing where no appreciable amount of bending around an obstruction is necessary If soft copper is used care must be taken to avoid sharp bends which may cause a restriction The vapor lines...

Page 6: ...rom both the liquid and vapor fitting service ports at the outdoor unit Connect low pressure nitrogen to the liquid line service port 2 Braze the liquid line to the liquid fitting at the outdoor unit Be sure to wrap the fitting body with a wet rag Allow the nitrogen to continue flowing Do not braze the vapor fitting at this time 3 Remove pressure from indoor coil through the Schrader fitting on th...

Page 7: ...n in Fig 12 Refer to Step 2 below for connections FIGURE 11 OUTDOOR UNIT SHUT OFF VALVE Liquid Line OD Vapor Line OD R22 Charge oz ft 5 16 3 4 0 46 3 8 7 8 0 70 TABLE 4 ADDITIONAL REFRIGERANT LINE CHARGE CAUTION Do not connect manifold gauges unless trouble is suspected Approximately 3 4 ounce of refrig erant will be lost each time a standard manifold gauge is connected WARNING Never attempt to re...

Page 8: ...ol System ECS SYSTEM START UP AND ADJUSTMENTS The initial start up of the unit requires the following additional procedures 1 When the gas supply is initially connected to the unit the gas piping may be full of air In order to purge this air it is recommended that the plug on the gas line be loosened until the odor of gas is detected When gas is detected immediately retighten the plug and check fo...

Page 9: ...n clamp to minimize leakage connections are shown in Figure 14 Press the run button or operate the sampling procedure of the O2 analyzer Allow the analyzer to run until the pump stops or the reading stablizes Record and repeat the sampling proce dure Compare number to see if analyzer is reading properly If not take a couple more samples If this doesn t correct the problem inspect the analyzer to s...

Page 10: ...sent from thermostat The outdoor temperature is less than 43 F The refrigerant liquid temperature is less than 35 F If any of these conditions is present the heat pump system will shut down and the furnace will be engaged to provide all heat required The heat pump will not attempt a restart until a heating cycle has been completed and the following conditions are met There is no call for 3rd stage...

Page 11: ...operation until the call for heat is satisfied 5 When the call for heat is satisfied the thermostat circuit opens and the gas valve closes The inducer will continue to run for 15 seconds 6 The furnace blower will operate for the time chosen on the fan off setting 7 If flame is not detected the control module will re try ignition after a 60 second wait 8 After 60 seconds the ignition sequence is re...

Page 12: ...500 RPM 4 After 30 seconds the reversing valve will shift 5 The outdoor fan will cycle on and off 6 The engine speed will then increase to 3000 RPM for the duration of the defrost cycle 7 The electric heater or add on hot water hydronic system will operate during the defrost cycle to temper the indoor supply air The defrost will terminate when 1 The liquid temperature has reached 75 F or 2 The liq...

Page 13: ...ticed at the indoor unit and outdoor unit engine When the system is functioning properly and the owner has been fully instructed secure the owner s approval INDOOR AIR FILTER Indoor filters are recommended to keep the duct system clean and to collect dust lint and other debris from entering the air handling coil sections Filters are recommended to be replenished replace throw aways every three mon...

Page 14: ...ESSURE COOLING 3 TON 60 65 70 75 80 85 60 70 80 90 100 110 120 OD TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM TEMPERATURE PRESSURE CURVES 3 TON COOLING HEATING SUPPLY AIR TEMP DROP COOLING 3 TON 15 16 17 18 19 20 21 22 23 24 60 70 80 90 100 110 120 OD TEMP F T DB TEMP DROP F 3000 RPM 1800 RPM 1200 RPM 515 35 N6Y 14 Unitary Products Group ...

Page 15: ... 1800 RPM 3000 RPM 250 DISCHARGE PRESSURE HEATING 3 TON 150 160 170 180 190 200 210 220 230 0 10 20 30 40 50 TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM See Note SUCTION PRESSURE HEATING 3 TON 15 20 25 30 35 40 45 50 55 60 65 0 10 20 30 40 50 OD TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM See Note 515 35 N6Y Unitary Products Group 15 ...

Page 16: ...0 RPM 1800 RPM 1200 RPM See Note NOTE With furnace model the heat pump does not operate below 43 F Degrees F 0 150 100 50 OD TEMP F DISCHARGE TEMPERATURE SUCTION TEMPERATURE AT COMP 10 20 30 40 50 200 3000 1800 1200 1200 3000 1800 TEMPERATURES HEATING 3 TON 0 515 35 N6Y 16 Unitary Products Group ...

Page 17: ... 3 1 2 TON 0 50 100 150 200 250 300 350 400 60 70 80 90 100 110 120 OD TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM TEMPERATURE PRESSURE CURVES 3 1 2 TON COOLING HEATING SUPPLY AIR TEMP DROP COOLING 3 1 2 TON 15 16 17 18 19 20 21 22 23 24 60 70 80 90 100 110 120 OD TEMP F T DB TEMP DROP F 3000 RPM 1800 RPM 1200 RPM 515 35 N6Y Unitary Products Group 17 ...

Page 18: ... TON DISCHARGE PRESSURE HEATING 3 1 2 TON 150 160 170 180 190 200 210 220 0 10 20 30 40 50 OD TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM See Note NOTE With furnace model the heat pump does not operate below 43 F SUCTION PRESSURE HEATING 3 1 2 TON 15 20 25 30 35 40 45 50 55 60 65 70 0 10 20 30 40 50 OD TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM See Note 515 35 N6Y 18 Unitary Products Group ...

Page 19: ...TEMP RISE F 3000 RPM 1800 RPM 1200 RPM See Note 0 150 100 50 OD TEMP F DISCHARGE TEMPERATURE SUCTION TEMPERATURE AT COMP 10 20 30 40 50 200 3000 1800 1200 1200 3000 1800 TEMPERATURES HEATING 3 1 2 TON 0 NOTE With furnace model heat pump does not operate below 43 F 515 35 N6Y Unitary Products Group 19 ...

Page 20: ...WIRING DIAGRAMS 515 35 N6Y 20 Unitary Products Group ...

Page 21: ...515 35 N6Y Unitary Products Group 21 ...

Page 22: ...NOTES 515 35 N6Y 22 Unitary Products Group ...

Page 23: ...NOTES 515 35 N6Y Unitary Products Group 23 ...

Page 24: ...frigerant lines been routed and connected to the indoor and outdoor units Have refrigerant lines been checked for leaks Has the electrical control wiring been connected to the indoor and outdoor units in accordance with the wiring diagram enclosed Has the refrigerant system been properly evacuated and charged Have the engine exhaust pipe and vent hood been properly installed Have the engine shippi...

Reviews: