background image

INDICATIONS OF PROPER SYSTEM OPERATION

Cooling

Cooling operation is the same as any conventional air condi-
tioning unit.

1.  The outdoor fan should be running, with warm air being

discharged from the top of the unit.

2.  The indoor blower will be operating, discharging cool air

from the ducts.

3.  The vapor line at the outdoor unit will feel cool to the touch.

4.  The liquid line at the outdoor unit will feel warm to the touch.

Heating

Indications of proper heating operation is as follows:

1.  The outdoor fan should be running, with cool air being

discharged from the top of the unit.

2.  The indoor blower will be operating, discharging warm air

from the ducts.

3.  The vapor line at the outdoor unit will feel warm to the touch.

4.  The liquid line at the outdoor unit will feel cool to the touch.

The system can operate either as a heat pump with electric or
add-on hot water hydronic heat, or as a heat pump with furnace
back up heat.

HEAT / COOL TRIATHLON OPERATION

Basic System Operation

COOLING MODE:

The thermostat will initiate a demand for system operation.
Light on the thermostat will light indicating demand.

The reversing valve will be energized.

The outdoor fan will start, then the engine will start at 1,500
rpm.

The indoor fan will start after a delay.

Coolant will recirculate through the engine until tempera-
tures are adequate to open the coolant thermostat and send
coolant to the outdoor coil.

HEATING MODE:

The system will operate as a heat pump or as a furnace in
heating.

The operation of the heat pump and the furnace will be covered
separately. The flowchart (see Figure 15) shows the control
sequence.

Heat Pump

The thermostat will call for system operation. The light on
the thermostat will light, indicating demand.

The outdoor fan will start, then the engine will start at 1,500
rpm.

The indoor fan will start after a delay.

Coolant will recirculate through the engine until tempera-
tures are adequate to open the coolant thermostat and send
coolant to the outdoor coil.

Engine speed will adjust after initial startup based on the
demand from the thermostat.

It is possible for the indoor blower to be operating if the
thermostat fan switch is set for continuous fan.

Furnace

Furnace operation is the normal heating mode when one of the
following is present:

There is a call for 3rd stage heat or emergency heat ("W"
signal sent from thermostat)

The outdoor temperature is less than 43

°

 F.

The refrigerant liquid temperature is less than 35

°

 F.

If any of these conditions is present the heat pump system will
shut down and the furnace will be engaged to provide all heat
required. The heat pump will not attempt a restart until a heating
cycle has been completed and the following conditions are met:

There is no call for 3rd stage heat or emergency heat (no
"W" signal being sent by the thermostat).

The outdoor temperature is greater than 46

°

 F.

The refrigerant liquid temperature is greater then 38

°

 F.

The thermostat will call for system operation. The light on
the thermostat will light, indicating demand.There is a six
minute off-time between cooling or heating cycles. If the
system has cycled off it will be a minimum of six minutes
before it will be allowed to restart.

The gas valve is energized after a pre-purge by the inducer
motor and after the ignitor has warmed has warmed up.

Ignition occurs in the furnace and the heat exchanger begins
heating

The indoor (furnace blower) fan will start after a delay.

It is possible for the indoor blower to be operating if the
thermostat fan switch is set for continuous fan.

TECHNICAL OPERATION

Cooling Mode

1. The thermostat calls for cooling. There is a six minute

off-time between cooling or heating cycles. If the system
has cycled off it will be a minimum of six minutes before it
will be allowed to restart.

2.  The reversing valve toggles to relieve pressure differential

and then energizes.

3.  The unit control will self-test, then perform a system check

to determine if sensors are correctly opened / closed.

4. An engine start is attempted. If start is successful, the

engine comes up to 1500 rpm. If the start is unsuccessful,
another start will be attempted. The engine will attempt 5
starts before a fault requiring a shut-down occurs. A fault
will be posted and a six minute delay will occur until another
five attempt cycle can be made. After three sets of failed
start attempts (15 actual start attempts) the system will
shut down, post a fault and lock out.

5.  After a successful start, the indoor unit blower will start at

minimum speed. It is possible for the indoor blower to
already be operating if the thermostat fan switch is set to
continuous fan.

6.  After the engine speed reaches adequate operating tem-

perature, the system will respond to thermostat commands
and speed up or slow down as required. Maximum cooling
is achieved when the engine speed reaches 3000 rpm.

515.35-N6Y

10

Unitary Products Group

Summary of Contents for E3GE036S01B

Page 1: ...sitioned with any obstructions in the air stream The outdoor fan is the propeller type and is not designedtooperateagainstanyadditionalexternalstaticpressure The maximum and minimum conditions for operation must be observed to assure a system that will give maximum perform ance with minimum service Refer to Table 1 LOCATION Before starting the installation select and check the suitability of the l...

Page 2: ...m for proper operation 10 Instruct owner on operation of unit Unit is charged with enough refrigerant for outdoor unit indoor unit and 15 ft of each line TABLE 2 PHYSICAL AND ELECTRICAL DATA MODEL E3GE036 UNIT SUPPLY VOLTAGE 115 1 60 NORMAL VOLTAGE RANGE1 108 to 126 MINIMUM CIRCUIT AMPACITY 28 8 MAX OVERCURRENT DEVICE AMPS 30 MIN FIELD WIRE SIZE AWG 2 10 MAX WIRE LENGTH Ft 3 VOLTAGE DROP 49 24 VOL...

Page 3: ...de the unit 7 Install unit on a surface at least as large as the minimum base dimension shown in Figure 3 If required isolation pads can be used to eliminate direct contact with the house structure Refer to Figure 3 for pad placement 8 Make a hole s in the structure wall large enough to accom modate the insulated vapor line liquid line natural gas line and electrical wiring 36 1 2 38 43 CONTROL WI...

Page 4: ...MOSTAT REFRIGERANT LINES TO INDOOR SECTION GAS LINE NEC CLASS 2 WIRING 18 AWG MIN ENGINE EXHAUST WEATHERPROOF DISCONNECT SWITCH SEAL OPENINGS WITH PERMAGUM OR EQUIVALENT 36 OVERHEAD CLEARANCE NOTE ALL OUTDOOR WIRING MUST BE WEATHERPROOF MIN 12 CLEARANCE TO BUILDING 36 SERVICE ACCESS CLEARANCE FOR REMAINING THREE SIDES WARNING If outdoor unit is less than 60 from building no windows or other openin...

Page 5: ...voided by taking adequate precautions to assure an internally clean and dry system Always use refrigeration grade copper tubing that is internally clean and dry for refrigerant lines Use clean hard drawn copper tubing where no appreciable amount of bending around an obstruction is necessary If soft copper is used care must be taken to avoid sharp bends which may cause a restriction The vapor lines...

Page 6: ...rom both the liquid and vapor fitting service ports at the outdoor unit Connect low pressure nitrogen to the liquid line service port 2 Braze the liquid line to the liquid fitting at the outdoor unit Be sure to wrap the fitting body with a wet rag Allow the nitrogen to continue flowing Do not braze the vapor fitting at this time 3 Remove pressure from indoor coil through the Schrader fitting on th...

Page 7: ...n in Fig 12 Refer to Step 2 below for connections FIGURE 11 OUTDOOR UNIT SHUT OFF VALVE Liquid Line OD Vapor Line OD R22 Charge oz ft 5 16 3 4 0 46 3 8 7 8 0 70 TABLE 4 ADDITIONAL REFRIGERANT LINE CHARGE CAUTION Do not connect manifold gauges unless trouble is suspected Approximately 3 4 ounce of refrig erant will be lost each time a standard manifold gauge is connected WARNING Never attempt to re...

Page 8: ...ol System ECS SYSTEM START UP AND ADJUSTMENTS The initial start up of the unit requires the following additional procedures 1 When the gas supply is initially connected to the unit the gas piping may be full of air In order to purge this air it is recommended that the plug on the gas line be loosened until the odor of gas is detected When gas is detected immediately retighten the plug and check fo...

Page 9: ...n clamp to minimize leakage connections are shown in Figure 14 Press the run button or operate the sampling procedure of the O2 analyzer Allow the analyzer to run until the pump stops or the reading stablizes Record and repeat the sampling proce dure Compare number to see if analyzer is reading properly If not take a couple more samples If this doesn t correct the problem inspect the analyzer to s...

Page 10: ...sent from thermostat The outdoor temperature is less than 43 F The refrigerant liquid temperature is less than 35 F If any of these conditions is present the heat pump system will shut down and the furnace will be engaged to provide all heat required The heat pump will not attempt a restart until a heating cycle has been completed and the following conditions are met There is no call for 3rd stage...

Page 11: ...operation until the call for heat is satisfied 5 When the call for heat is satisfied the thermostat circuit opens and the gas valve closes The inducer will continue to run for 15 seconds 6 The furnace blower will operate for the time chosen on the fan off setting 7 If flame is not detected the control module will re try ignition after a 60 second wait 8 After 60 seconds the ignition sequence is re...

Page 12: ...500 RPM 4 After 30 seconds the reversing valve will shift 5 The outdoor fan will cycle on and off 6 The engine speed will then increase to 3000 RPM for the duration of the defrost cycle 7 The electric heater or add on hot water hydronic system will operate during the defrost cycle to temper the indoor supply air The defrost will terminate when 1 The liquid temperature has reached 75 F or 2 The liq...

Page 13: ...ticed at the indoor unit and outdoor unit engine When the system is functioning properly and the owner has been fully instructed secure the owner s approval INDOOR AIR FILTER Indoor filters are recommended to keep the duct system clean and to collect dust lint and other debris from entering the air handling coil sections Filters are recommended to be replenished replace throw aways every three mon...

Page 14: ...ESSURE COOLING 3 TON 60 65 70 75 80 85 60 70 80 90 100 110 120 OD TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM TEMPERATURE PRESSURE CURVES 3 TON COOLING HEATING SUPPLY AIR TEMP DROP COOLING 3 TON 15 16 17 18 19 20 21 22 23 24 60 70 80 90 100 110 120 OD TEMP F T DB TEMP DROP F 3000 RPM 1800 RPM 1200 RPM 515 35 N6Y 14 Unitary Products Group ...

Page 15: ... 1800 RPM 3000 RPM 250 DISCHARGE PRESSURE HEATING 3 TON 150 160 170 180 190 200 210 220 230 0 10 20 30 40 50 TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM See Note SUCTION PRESSURE HEATING 3 TON 15 20 25 30 35 40 45 50 55 60 65 0 10 20 30 40 50 OD TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM See Note 515 35 N6Y Unitary Products Group 15 ...

Page 16: ...0 RPM 1800 RPM 1200 RPM See Note NOTE With furnace model the heat pump does not operate below 43 F Degrees F 0 150 100 50 OD TEMP F DISCHARGE TEMPERATURE SUCTION TEMPERATURE AT COMP 10 20 30 40 50 200 3000 1800 1200 1200 3000 1800 TEMPERATURES HEATING 3 TON 0 515 35 N6Y 16 Unitary Products Group ...

Page 17: ... 3 1 2 TON 0 50 100 150 200 250 300 350 400 60 70 80 90 100 110 120 OD TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM TEMPERATURE PRESSURE CURVES 3 1 2 TON COOLING HEATING SUPPLY AIR TEMP DROP COOLING 3 1 2 TON 15 16 17 18 19 20 21 22 23 24 60 70 80 90 100 110 120 OD TEMP F T DB TEMP DROP F 3000 RPM 1800 RPM 1200 RPM 515 35 N6Y Unitary Products Group 17 ...

Page 18: ... TON DISCHARGE PRESSURE HEATING 3 1 2 TON 150 160 170 180 190 200 210 220 0 10 20 30 40 50 OD TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM See Note NOTE With furnace model the heat pump does not operate below 43 F SUCTION PRESSURE HEATING 3 1 2 TON 15 20 25 30 35 40 45 50 55 60 65 70 0 10 20 30 40 50 OD TEMP F PSIG 3000 RPM 1800 RPM 1200 RPM See Note 515 35 N6Y 18 Unitary Products Group ...

Page 19: ...TEMP RISE F 3000 RPM 1800 RPM 1200 RPM See Note 0 150 100 50 OD TEMP F DISCHARGE TEMPERATURE SUCTION TEMPERATURE AT COMP 10 20 30 40 50 200 3000 1800 1200 1200 3000 1800 TEMPERATURES HEATING 3 1 2 TON 0 NOTE With furnace model heat pump does not operate below 43 F 515 35 N6Y Unitary Products Group 19 ...

Page 20: ...WIRING DIAGRAMS 515 35 N6Y 20 Unitary Products Group ...

Page 21: ...515 35 N6Y Unitary Products Group 21 ...

Page 22: ...NOTES 515 35 N6Y 22 Unitary Products Group ...

Page 23: ...NOTES 515 35 N6Y Unitary Products Group 23 ...

Page 24: ...frigerant lines been routed and connected to the indoor and outdoor units Have refrigerant lines been checked for leaks Has the electrical control wiring been connected to the indoor and outdoor units in accordance with the wiring diagram enclosed Has the refrigerant system been properly evacuated and charged Have the engine exhaust pipe and vent hood been properly installed Have the engine shippi...

Reviews: