background image

Stub kits are available to field fabricate quick connect line sets
or to connect mix-matched units and coils.

Unit should be installed only with approved system combina-
tions (indoor coil/outdoor unit) specified in Technical Guide.

See Application Data,"General Piping Recommendations and
Refrigerant Line Length," for vapor and liquid line sizing, cal-
culation of liquid line pressure loss or gain, determination of
vapor line velocity, elevation limitations, orifice corrections,
system charging, traps, etc.

Total line lengths are limited to 75 feet due to the storage
capacity of the accumulator. Systems with total line lengths
over 50 feet must be provided with a low voltage start kit.

Elevation differences are limited to:

Indoor Above Outdoor........50 ft.
Outdoor Above Indoor........50 ft.

Systems with liquid line pressure loss or gain greater than 11
psi must be provided with corrected orifice size.

Inter-connecting refrigerant lines should be sized to match the
factory supplied fittings. Liquid lines must NEVER be increased
or decreased. Vapor lines may be increased one size to mini-

mize pressure drop as long as a velocity of at least 1000 feet
per minute is maintained.

Additional charge is required for inter-connecting piping greater
than 15 feet for sweat units and some indoor coil matches.

The lines should be installed so that they will not obstruct
service access to the coil, air handling system or filter. Install
the lines with as few bends as possible. Care must be taken
not to damage the couplings or kink the tubing. Care must also
be used to isolate the refrigerant lines to minimize noise
transmission from the equipment to the structure.

Tape and suspend the refrigerant lines as shown. DO NOT
allow metal-to-metal contact.

OUTDOOR UNIT      E1FD / E9FD

018

024

030 036

042

048

060

UNIT ORIFICE(S)

1

55, 57

59, 61

67, 69

75

81

84, 87

99

FACTORY   R-22
CHARGE, LBS. OZ.

SWEAT

4 - 11

5 - 15

6 - 6

6 - 9

7 - 6

7 - 9

15 - 5

QUICK

4 - 1

5 - 6

5 - 11

5 - 15

6 - 12

6 - 15

14 - 10

INDOOR COIL

COIL

ORIFICE2

SYSTEM O ADDITIONAL CHARGE, OZ.

G3HC / G1FC018

55

55 + 2

59 + 0

-

-

-

-

-

G3HC / G1FC024

61

57 + 14

59 + 0

-

-

-

-

-

G3HC / G1FC030

69

61 + 16

69 + 0

-

-

-

-

G3HC / G1FC036

81

-

-

69 + 4

75 + 0

-

-

-

G3HC / G1FC042

78

-

-

-

75 + 13

81 + 3

-

-

G3HC / G1FC048

90

-

-

-

-

81  +  11

84  +  0

-

G3HC / G1FC060

96

-

-

-

-

-

87  +  19

99  +  0

G3US018

55

55 + 2

59 + 0

-

-

-

-

-

G3UA024

59

55 + 14

59 + 0

-

-

-

-

-

G3UA030

65

-

61 + 16

-

-

-

-

-

G3UA036

69

-

61 + 16

69 + 4

75 + 0

-

-

-

G3UA037

69

-

61 + 16

69 + 4

75 + 0

-

-

-

G3UA048

87

-

-

-

-

81  +  11

84  +  0

-

G3UA060

96

-

-

-

-

-

87  +  19

99  +  0

G3UA061

96

-

-

-

-

-

87  +  19

99  +  0

G2UT024

-

-

+ 0

-

-

-

-

-

G2UT030

-

-

+16

-

-

-

-

-

G2UT036

-

-

+16

+4

+0

-

-

-

G2UT037

-

-

+16

+4

+0

-

-

-

G2UT048

-

-

-

-

-

+  11

+  0

-

G2UT060

-

-

-

-

-

-

+  19

-

G2UT061

-

-

-

-

-

-

+  19

+  0

G3CN030

65

57 + 14

61 + 16

69 + 0

-

-

-

-

G3CN042

73

-

-

-

75 + 13

81 + 3

-

-

G3CN060

87

-

-

-

-

-

87  +  19

99  +  0

F1RP / F1FP018

53

55 + 0

-

-

-

-

-

-

F1RP / F1FP024

61

57 + 6

61 + 0

-

-

-

-

-

F1RP / F1FP030

65

-

61 + 0

67 + 2

-

-

-

-

F1RP / F1FP036

75

-

-

-

75 + 0

-

-

-

F1RP / F1FP042

78

-

-

-

75 + 2

78 + 0

-

-

1

These orfices are packed in the instruction/warranty packet of each outdoor unit.

2

These orifices are factory-mounted in the flow control device of each indoor coil.

NOTE:  Orifices in (   ) must be ordered from the Parts Department.

TABLE 4- ADDITIONAL R-22 CHARGE/ORIFICE SIZE

LIQUID

LINE

TAPE

SHEET
METAL
HANGER

INSULATED
VAPOR LINE

FIGURE 6 - TUBING HANGER

515.26-N5Y

6

Unitary Products Group

Summary of Contents for E1FD018 Series

Page 1: ...priate indoor unit air moving system and accessories Installer should pay particular attention to the words NOTE CAUTION and WARNING NOTES are intended to clarify or make the installation easier CAUTI...

Page 2: ...cause personal injury Remember that condensate will drip from the unit coils during heat and defrost cycles and that this condensate will freezewhen thetemperature ofthe outdoor air is below 32 F Ele...

Page 3: ...SQ FT 14 2 15 1 15 1 17 0 20 20 24 ROWS DEEP 1 1 1 1 1 1 2 FIN INCH 13 18 18 20 13 16 13 LIQUID LINE OD 3 8 3 8 3 8 3 8 3 8 3 8 3 8 VAPOR LINE OD 5 8 5 8 3 4 3 4 7 8 7 8 7 8 OPERATING WEIGHT LBS 140 1...

Page 4: ...ressor where theheater isinstalled The heater should be energized for at least 8 hours before the thermostat is set to operate the compressor CAUTION An attempt to start the compressor without at leas...

Page 5: ...or C L or X T E FIELD INSTALLED JUMPER 1 2 2 BLK YEL ORG WHT BRN X FIGURE 4 TYPICAL 1 FIELD WIRING Air Handler Electric Heat Y O W1 or 66 W GRD LUG DEFROST CONTROL CONTACTOR GRD SCREW M R C 53 or W3 R...

Page 6: ...es with as few bends as possible Care must be taken not to damage the couplings or kink the tubing Care must also be used to isolate the refrigerant lines to minimize noise transmission from the equip...

Page 7: ...e coil instruction for details to change the orifice in the coil QUICK CONNECT SYSTEMS Indoor coils and outdoor units are to be connected with pre charged interconnecting tubing specified for the spli...

Page 8: ...it as shown in Figure 9 Also protect all painted surfaces and insulation during brazing After brazing cool joint with wet rag WARNING Thisis not a backseating valve The service access port has a valv...

Page 9: ...ovided Connect the control wiring see Figure 4 or 5 for Typical Field Wiring EVACUATION It will be necessary to evacuate the system if the unit has developed a leak during shipment or was for any othe...

Page 10: ...t through blower relay to provide blower operation 4 System will cycle with thermostat demand to provide cool ing as needed WITH POWER TO UNIT AND THERMOSTAT IN HEATING POSITION 1 Reversing valve is d...

Page 11: ...l illumi nate on the thermostat To reset the lockout turn the indoor thermostat s system switch to OFF then back to the selected mode within 5 second OR disconnect the power to the trans former for at...

Page 12: ...ting discharging warm air from the ducts 3 The vapor line at the outdoor unitwill feel warm to the touch 4 The liquid line at the outdoor unit will feel cool to the touch NOTICE TO OWNER If lockout oc...

Reviews: