background image

SEQUENCE OF OPERATION

COOLING:

On call for cooling, the thermostat makes 24V circuits: R to O,
R to Y, and R to G. Circuit R to O energizes the reversing valve,
switching it to cooling position. Circuit R to Y energizes the
contactor, starting outdoor fan motor and compressor circuit.
R to G energizes the indoor unit blower relay, starting the indoor
blower motor.

HEATING:

On call for heating, thermostat makes circuits R to Y and R to
G. Circuit R to Y energizes contactor, starting outdoor fan motor
and compressor. Circuit R to G energizes the indoor blower
relay, starting the blower motor.

Should the temperature continue to fall, R to W is made through
the second stage of the thermostat. Circuit R to W energizes
the supplemental electric heat. The field-installed option out-
door thermostat can be used to turn on only the first stage of
electric heat if the temperature is above the setting tempera-
ture.  If gas/propane furnace is used as the supplemental heat,
add-on control kit (2AC02700701) must be used.  See the
add-on control installation instruction for the system operation.

EMERGENCY HEAT:

When switch on thermostat is placed in emergency heat position:

1. Emergency light is energized.

2. Compressor circuit is locked out.

3. Supplemental and standby heaters (if installed) will be

controlled by first stage of heating thermostat.

4. Indoor blower will operate on demand for heat and cycle off

with the last heater element when in “AUTO” position.

SAFETY LOCKOUT MODE:

The lock out control opens the circuits to the compressor
contactor, stopping the compressor in response to (400 #) High

Pressure limit switch opening for more than one second. The
compressor will remain off, even though the limits close and
will start up only when the lockout is reset. Since there is no “X”
output on this control, no malfunction indication light will illumi-
nate on the thermostat. To reset the lockout, turn the indoor
thermostat’s system switch to “OFF” then, back to the selected
mode within 5 second OR disconnect the power to the trans-
former for at least two seconds. Please note that thermostats
with anti-short cycle timers will only be able to reset by discon-
necting the power to the transformer for at least two seconds.

DEFROST:

The defrost control is a time/temp control which includes a
field-selectable (white tap located at board edge) time period
between defrost cycle (30, 60, and 90 minutes). Factory set at
60 minutes.

The electronic timer and the defrost cycle will start only when
the contactor is energized and the defrost thermostat is closed.
The defrost thermostat is closed when the liquid temperature
falls below approximately 31

°

F.

The defrost mode is identical to the cooling mode except that
the outdoor fan motor stops and the first stage of heat (5KW if
electric heat) is turned on through W1 / 66  to continue
warming the conditioned space.

The defrost cycle will be terminated when the defrost thermo-
stat is opened at 60

°

F or 10 minutes of compressor accumu-

lated run time, whichever comes first. Note: The defrost
thermostat delay will make the coil temperature about 75 - 80

°

F.

Please note that the timer will stop the circuit  when R to Y is
disconnected.

TEST PIN:

The “TEST” terminals are designed for defrost test. When the
“TEST” terminals are shorted together, the control will allow the
unit to go into a defrost cycle if the compressor is operating.
When the short is removed, the heat pump will remain in defrost
until the defrost thermostat is open or 10 minutes expires. If the
thermostat is open when the short is removed, the heat pump
will exit defrost.

FIGURE 12 - TIME / TEMPERATURE DEFROST BOARD

TEST

W

W1/66

Y

O

90

C

RUN TIME

90
60
30

60
30

SEL MIN

U1

COND   FAN

K2

K3

R2

K1

HIGH VOLTAGE

PRESSURE
SWITCH

REVERSING
VALVE

DEFROST
STAT

C

C

COMPRESSOR
RELAY

C

R

R

TIME
SELECTION
TAP

DEFROST
TEST 
PIN

M

THERMOSTAT

515.26-N5Y

Unitary Products Group

11

Summary of Contents for E1FD018 Series

Page 1: ...priate indoor unit air moving system and accessories Installer should pay particular attention to the words NOTE CAUTION and WARNING NOTES are intended to clarify or make the installation easier CAUTI...

Page 2: ...cause personal injury Remember that condensate will drip from the unit coils during heat and defrost cycles and that this condensate will freezewhen thetemperature ofthe outdoor air is below 32 F Ele...

Page 3: ...SQ FT 14 2 15 1 15 1 17 0 20 20 24 ROWS DEEP 1 1 1 1 1 1 2 FIN INCH 13 18 18 20 13 16 13 LIQUID LINE OD 3 8 3 8 3 8 3 8 3 8 3 8 3 8 VAPOR LINE OD 5 8 5 8 3 4 3 4 7 8 7 8 7 8 OPERATING WEIGHT LBS 140 1...

Page 4: ...ressor where theheater isinstalled The heater should be energized for at least 8 hours before the thermostat is set to operate the compressor CAUTION An attempt to start the compressor without at leas...

Page 5: ...or C L or X T E FIELD INSTALLED JUMPER 1 2 2 BLK YEL ORG WHT BRN X FIGURE 4 TYPICAL 1 FIELD WIRING Air Handler Electric Heat Y O W1 or 66 W GRD LUG DEFROST CONTROL CONTACTOR GRD SCREW M R C 53 or W3 R...

Page 6: ...es with as few bends as possible Care must be taken not to damage the couplings or kink the tubing Care must also be used to isolate the refrigerant lines to minimize noise transmission from the equip...

Page 7: ...e coil instruction for details to change the orifice in the coil QUICK CONNECT SYSTEMS Indoor coils and outdoor units are to be connected with pre charged interconnecting tubing specified for the spli...

Page 8: ...it as shown in Figure 9 Also protect all painted surfaces and insulation during brazing After brazing cool joint with wet rag WARNING Thisis not a backseating valve The service access port has a valv...

Page 9: ...ovided Connect the control wiring see Figure 4 or 5 for Typical Field Wiring EVACUATION It will be necessary to evacuate the system if the unit has developed a leak during shipment or was for any othe...

Page 10: ...t through blower relay to provide blower operation 4 System will cycle with thermostat demand to provide cool ing as needed WITH POWER TO UNIT AND THERMOSTAT IN HEATING POSITION 1 Reversing valve is d...

Page 11: ...l illumi nate on the thermostat To reset the lockout turn the indoor thermostat s system switch to OFF then back to the selected mode within 5 second OR disconnect the power to the trans former for at...

Page 12: ...ting discharging warm air from the ducts 3 The vapor line at the outdoor unitwill feel warm to the touch 4 The liquid line at the outdoor unit will feel cool to the touch NOTICE TO OWNER If lockout oc...

Reviews: