background image

GENERAL

This instruction covers the installation of the following outdoor
units: E1FD018A(S)06, E9FD018S06, E1FD024A(S)06,
E 9 F D0 24 S 06 ,  E 1F D0 30 A (S )06 ,  E 9F D 03 0S 06 ,
E 1F D 03 6A (S )06 , E9 FD0 36S 06, E 1FD 036 S(25 ,4 6),
E1FD042A(S)06, E1FD048A(S)06 E1FD048S(25, 46),
E1FD060A(S)06, E1FD060S06(25, 46).

The outdoor units are designed to be connected to a matching
indoor coil with either quick or sweat connect lines. Quick
connect units are factory charged with refrigerant for a match-
ing indoor coil and factory charged line sets are available in
various lengths. Sweat connect units are factory charged with
refrigerant for a matching indoor coil plus 15 feet of field
supplied lines.

Matching indoor coils are available with a thermal expansion
valve or an orifice liquid feed (YORKMATE flow control device)
sized for the most common usage. The orifice size and/or
refrigerant charge may need to be changed for some indoor-
outdoor unit combinations, elevation differences or total line
lengths. Refer to Application Data covering “General Piping
Recommendations and Refrigerant Line Length” (Form
690.01-AD1V).

THIS UNIT IS NOT EQUIPPED WITH A FILTER DRIER. A
SOLID CORE BI-FLOW DIRECTIONAL FILTER IS RE-
QUIRED FOR INSTALLATION AND ANY TIME THE REFRIG-
ERANT CIRCUIT IS OPENED.

INSPECTION

As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier’s delivery receipt. A
separate request for inspection by the carrier’s agent should
be made in writing. See Local Distributor for more information.

REFERENCE

Use this instruction in conjunction with the instructions for the
appropriate indoor unit, air moving system and accessories.

Installer should pay particular attention to the words: 

NOTE,

CAUTION and WARNING.

NOTES are intended to clarify or make the installation easier.

CAUTIONS identifies procedure which, if not followed carefully,
could result in personal injury, property damage or product
damage.

WARNINGS are given to alert the installer that severe personal
injury, death or equipment damage may result if installation
procedures are not handled properly.

NOMENCLATURE

LIMITATIONS

The unit should be installed in accordance with all national and
local safety codes.

Limitations for the indoor unit, coil and appropriate accessories
must also be observed.

The outdoor unit must not be installed with any ductwork in the
air stream. The outdoor fan is the propeller type and is not
designed to operate against any additional external static pres-
sure.

OUTDOOR

SPLIT-SYSTEM HEAT PUMPS

Supersedes: 

Supersedes: 515.26-N5Y (995)

MODELS E1(9)FD018, 024, 030 and 036

E1FD042, 048 and 060

(See Detail Listing Below)

515.26-N5Y (296)

035- 13682

AIR TEMPERATURE 

°

DB

ON OUTDOOR COIL

AIR TEMPERATURE

ON INDOOR COIL

Min.

Max.

Min.

Max.

Cool

Heat

Cool

Heat

°

WB

Cool

°

DB

Heat

°

WB

Cool

°

DB

Heat

50

-10*

115

75

57

50**

72

80

* If ambient will be below this, Accessory Kit 2LT06700224 must be installed to
cutoff heat pump.
** Operation below this temperature is permissible for a short period of time,
during morning warm-up.

TABLE 1 - APPLICATION LIMITATIONS

Voltage Code

Refrigerant Line Connections

Nominal Cooling Capacity

Product Category

Product  Generation

Product  Identifier

E = Outdoor Split System Heat Pump

1 = Design Level
9 = Canada

FDs = 10 SEER Heat Pump

018 = 1.5 Tons
024 = 2Tons
030 = 2.5Tons
036 = 3 Tons

042 = 3.5 Tons
048 = 4 Tons
060 = 5 Tons

A = Quick-Connect Fittings
S = Sweat Fittings

06 = 208/230-1-60
25 =208/230-3-60
46 = 460-3-60

E

1

FD 036

A

06

® 

INSTALLATION INSTRUCTION

Summary of Contents for E1FD018 Series

Page 1: ...priate indoor unit air moving system and accessories Installer should pay particular attention to the words NOTE CAUTION and WARNING NOTES are intended to clarify or make the installation easier CAUTI...

Page 2: ...cause personal injury Remember that condensate will drip from the unit coils during heat and defrost cycles and that this condensate will freezewhen thetemperature ofthe outdoor air is below 32 F Ele...

Page 3: ...SQ FT 14 2 15 1 15 1 17 0 20 20 24 ROWS DEEP 1 1 1 1 1 1 2 FIN INCH 13 18 18 20 13 16 13 LIQUID LINE OD 3 8 3 8 3 8 3 8 3 8 3 8 3 8 VAPOR LINE OD 5 8 5 8 3 4 3 4 7 8 7 8 7 8 OPERATING WEIGHT LBS 140 1...

Page 4: ...ressor where theheater isinstalled The heater should be energized for at least 8 hours before the thermostat is set to operate the compressor CAUTION An attempt to start the compressor without at leas...

Page 5: ...or C L or X T E FIELD INSTALLED JUMPER 1 2 2 BLK YEL ORG WHT BRN X FIGURE 4 TYPICAL 1 FIELD WIRING Air Handler Electric Heat Y O W1 or 66 W GRD LUG DEFROST CONTROL CONTACTOR GRD SCREW M R C 53 or W3 R...

Page 6: ...es with as few bends as possible Care must be taken not to damage the couplings or kink the tubing Care must also be used to isolate the refrigerant lines to minimize noise transmission from the equip...

Page 7: ...e coil instruction for details to change the orifice in the coil QUICK CONNECT SYSTEMS Indoor coils and outdoor units are to be connected with pre charged interconnecting tubing specified for the spli...

Page 8: ...it as shown in Figure 9 Also protect all painted surfaces and insulation during brazing After brazing cool joint with wet rag WARNING Thisis not a backseating valve The service access port has a valv...

Page 9: ...ovided Connect the control wiring see Figure 4 or 5 for Typical Field Wiring EVACUATION It will be necessary to evacuate the system if the unit has developed a leak during shipment or was for any othe...

Page 10: ...t through blower relay to provide blower operation 4 System will cycle with thermostat demand to provide cool ing as needed WITH POWER TO UNIT AND THERMOSTAT IN HEATING POSITION 1 Reversing valve is d...

Page 11: ...l illumi nate on the thermostat To reset the lockout turn the indoor thermostat s system switch to OFF then back to the selected mode within 5 second OR disconnect the power to the trans former for at...

Page 12: ...ting discharging warm air from the ducts 3 The vapor line at the outdoor unitwill feel warm to the touch 4 The liquid line at the outdoor unit will feel cool to the touch NOTICE TO OWNER If lockout oc...

Reviews: