VAV, power exhaust is energized by means of a binary out-
put signal from the unit's VAV control board.

The exhaust fan, motor and controls are installed and 
wired at the factory. The rain hood must be assembled 
and installed in the field.

The power exhaust option can only be used on bot-
tom duct configurations.

MOTORIZED OUTDOOR AIR INTAKE DAMPER

 - 

Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a 
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit 
shuts down.

The rain hood is painted to match the basic unit and 
must be field assembled before installing.

BAROMETRIC RELIEF DAMPER -

 This damper option 

can be used to relieve internal building air pressure on 
units with an economizer without power exhaust. This 
accessory includes a rain hood, a bird screen and a fully 
assembled damper. With bottom duct connections, the 
damper should be mounted over the opening in the 
return air panel. With horizontal ductwork, the accessory 
should be mounted on the return air duct.

PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS

 - Special coating process that utilizes 

Technicoat 10-1" processes. Coating is applied by total 
immersion of the complete coil for maximum protection.

ELECTRIC HEATERS

 wired for single point power sup-

ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent 
operation at excessive temperatures.

VARIABLE AIR VOLUME (VAV)

 - A factory-installed 

variable frequency drive (VFD), mounted in the Blower 
Access compartment, is used to control the speed of the 
indoor blower motor in order to maintain a constant static 
pressure in the supply duct. A pressure transducer and 
VAV control board are mounted inside the control box. 
The drive comes completely wired and pre-programmed 
from the factory.

An optional, factory-installed manual bypass switch 
available with factory-installed VFD can be found in the 
Blower Motor Access compartment. The switch can be 
used to either route power to the VFD for modulating 
control of the blower motor, to bypass the drive and oper-
ate the motor at full speed, or to power the drive (and not 
the motor) for diagnostic purposes.

Due to space limitations, VAV is not available with any of 
the factory-installed BAS options described below, but is 
available with ‘BAS-ready’ models. Terminal blocks are 
provided in the control box for field wiring of the cus-
tomer-installed BAS.

A ‘VFD-ready’ option provides the provisions for a cus-
tomer-installed drive. The unit comes with a mounting 
bracket installed in the Blower Access compartment 
which may accommodate other vendor’s drives depend-
ing on their size. In order to utilize the unit’s mounting 

bracket, the maximum recommended drive dimensions 
are as follows:

For 5-hp motor applications ........................13” H x 6” W x 7” D

For 7.5 thru 15-hp motor applications .........13” H x 8” W x 8” D

If the drive will not fit in the allotted space, then it will 
have to be mounted elsewhere; either within the building 
on a perpendicular wall which is not subjected to exces-
sive temperature, vibration, humidity, dust, corrosive 
gas, explosive gas, etc., or within an appropriate enclo-
sure rated for outside installation to safeguard against 
moisture, dust and excessive heat.

A terminal block located in the control box is provided for 
field connection of the VFD controls.

HOT GAS BYPASS

 - To allow for low cooling load oper-

ation, a direct-acting pressure-modulating bypass control 
valve installed on the system #1 discharge line is used to 
divert high temperature, high pressure refrigerant around 
the TXV in order to maintain a desired minimum evapo-
rator pressure. HGBP is standard on all units with VAV 
and optional with CV units.

FILTER OPTIONS

 - Standard units are shipped with 2” 

throw-away filters installed. 2” pleated and 4” pleated fil-
ters are offered as a factory installed option.

CONVENIENCE OUTLET

 - This 110 volt outlet can be 

“powered” by the unit with a stepdown transformer or 
you may order the unit with a “non-powered” conve-
nience outlet that can be wired in the field.

DISCONNECT SWITCH

 - For gas heat units and cooling 

units with electric heat, a HACR breaker sized to the unit 
is provided. For cooling only units, a switch sized to the 
largest electric heat available for the particular unit is 
provided. Factory installed option only.

DOUBLE WALL CONSTRUCTION -

 Optional double 

wall construction is available to provide smooth inner 
surfaces for easy and effective cleaning to reduce risk of 
dirt and bacterial accumulation. Fiberglass insulation is 
sandwiched between heavy gauge steel sheets to form a 
durable, rigid casing to withstand higher working pres-
sures and impact forces. The heavy-duty construction 
provides excellent acoustic and thermal insulation and 
eliminates erosion of insulation material and contamina-
tion of the air stream.

BAS - Building Automation System Controls (avail-
able on two-system cooling product only).

Simplicity

®

 INTELLI-Comfort™ CONTROL - 

The York® 

Simplicity

® INTELLI-Comfort™ control is factory installed. 

It includes a supply air sensor, a return air sensor, and an 
outside air sensor. There are provisions for a field installed 
dirty filter indicator switch, an air-proving switch, an Out-
side Air Humidity sensor, a Return Air Humidity sensor, an 
Inside IAQ sensor, and an Outside Air IAQ sensor. Con-
struction mode operation, 365-day real time clock with 7 
day programming plus holiday scheduling is built-in. Two 
different modes of demand ventilation are achieved 
through the INTELLI-Comfort™ using CO

2

 sensors. It 

Summary of Contents for DJ 180

Page 1: ...low pressure loss of charge switches and freezestats Scroll compressors Two stage heating provided by dual independent heat exchangers with aluminized steel tubes redundant gas valves spark ignition with induced draft logic Permanently lubricated motors Bottom or side air discharge configuration capability field convertible Belt Drive Blower Motor with high static drive option Constant supply air ...

Page 2: ...DJ300 13 Tbl Pg 8 ALTITUDE CORRECTION FACTORS 14 9 SUPPLY AIR BLOWER PERFORMANCE 15 TON COOLING ONLY 180 MBH BOTTOM DUCT CONNECTIONS 16 10 SUPPLY AIR BLOWER PERFORMANCE 17 5 TON COOLING ONLY 210 MBH BOTTOM DUCT CONNECTIONS 17 11 SUPPLY AIR BLOWER PERFORMANCE 20 TON COOLING ONLY 240 MBH BOTTOM DUCT CONNECTIONS 18 12 SUPPLY AIR BLOWER PERFORMANCE 15 TON GAS HEAT 180 MBH BOTTOM DUCT CONNECTIONS 19 13...

Page 3: ...s BF Phase Monitor Dirty Filter Switch Hinged Filter Door Tool Free Access Panels BG Coil Guard Dirty Filter Switch Hinged Filter Door Tool Free Access Panels BH Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Tool Free Access Panels 15 25 Ton Magnum Model Number Nomenclature ZZ If desired option combination is not listed above ZZ will be assigned and configuration options will be ...

Page 4: ...essor discharge bypass valve is available for low cooling load applications Simplicity Controls Simplicity control boards have standardized a number of features previously available only as options or by utilizing additional controls Low Ambient An integrated low ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis tance Optionally th...

Page 5: ...m contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling The rainhood is painted to match the basic unit and must be field assembled before installing BAS READY ECONOMIZER Includes a slide in plug in damper assembly with fully modulating spring return motor actuator with zero to 95 degree rotation capable of introducing u...

Page 6: ...te other vendor s drives depend ing on their size In order to utilize the unit s mounting bracket the maximum recommended drive dimensions are as follows For 5 hp motor applications 13 H x 6 W x 7 D For 7 5 thru 15 hp motor applications 13 H x 8 W x 8 D If the drive will not fit in the allotted space then it will have to be mounted elsewhere either within the building on a perpendicular wall which...

Page 7: ...ESS STEEL HEAT EXCHANGER For applica tions in corrosive environments this option provides a full stainless steel heat exchanger assembly STAINLESS STEEL DRAIN PAN An optional rust proof stainless steel drain pan is available to provide years of trouble free operation in corrosive environ ments PHASE MONITORS Designed to prevent unit damage The phase monitor will shut the unit down in an out of pha...

Page 8: ...pressure on units with an economizer without power exhaust This accessory includes a rain hood a bird screen and a fully assembled damper With bottom duct connections the damper should be mounted over the opening in the return air panel With horizontal ductwork the accessory should be mounted on the return air duct HIGH STATIC DRIVE A smaller blower pulley and a shorter belt increase the speed of ...

Page 9: ...EER Energy Efficiency Ratio at full load the cooling capacity in Btu s per hour Btuh divided by the power input in watts expressed in Btuh per watt Btuh watt IPLV3 3 IPLV Integrated Part Load Value COOLING ONLY DJ180C E00 178 12 0 12 5 DJ210C E00 208 11 7 12 7 DJ240C E00 230 11 3 12 0 DJ300C E00 292 10 5 11 2 COOLING WITH GAS HEAT DJ180N S 178 12 0 12 5 DJ210N S 208 11 7 12 7 DJ240N S 230 11 3 12 ...

Page 10: ...105 4 92 6 79 8 5250 72 189 7 14 51 123 4 108 2 93 1 77 9 62 7 178 3 15 95 118 9 103 7 88 6 73 4 58 2 67 172 3 14 24 154 6 139 5 124 3 109 1 94 0 78 8 63 6 161 8 15 70 150 1 134 9 119 8 104 6 89 4 74 3 59 1 62 156 9 14 05 156 9 155 0 148 1 132 9 117 7 102 6 87 4 147 8 15 52 147 8 146 3 139 9 124 8 109 6 94 4 79 3 57 159 4 14 08 159 4 157 8 151 4 136 2 121 1 105 9 90 8 151 2 15 55 151 2 149 5 143 1...

Page 11: ...1 5 94 4 77 3 6500 72 218 3 17 77 143 8 125 0 106 3 87 5 68 7 204 8 19 63 137 9 119 1 100 3 81 6 62 8 67 202 6 17 33 183 9 165 1 146 4 127 6 108 8 90 1 71 3 189 9 19 18 178 3 159 5 140 8 122 0 103 3 84 5 65 8 62 194 1 17 12 194 1 186 0 168 5 149 8 131 0 112 2 93 5 182 8 19 06 182 8 174 8 157 4 138 6 119 9 101 1 82 4 57 181 1 16 92 181 1 180 1 170 4 151 7 132 9 114 1 95 4 168 8 18 69 168 8 168 8 16...

Page 12: ...7 7000 72 250 6 20 15 162 5 142 2 122 0 101 8 81 6 236 4 21 79 157 8 137 5 117 3 97 1 76 9 67 231 3 19 69 206 2 185 9 165 7 145 5 125 3 105 1 84 9 218 5 21 50 199 2 179 0 158 8 138 6 118 4 98 1 77 9 62 208 1 19 43 208 1 204 2 193 1 172 9 152 7 132 5 112 3 194 8 21 16 194 8 194 1 185 6 165 4 145 1 124 9 104 7 57 217 3 19 70 217 3 214 3 204 9 184 7 164 5 144 3 124 1 207 0 21 35 207 0 205 1 195 7 175...

Page 13: ... 7 8750 72 306 8 27 83 201 3 176 1 150 8 125 5 100 2 286 9 30 20 195 1 169 8 144 6 119 3 94 0 67 293 9 27 37 259 0 233 7 208 5 183 2 157 9 132 7 107 4 280 1 29 98 253 1 227 9 202 6 177 3 152 0 126 8 101 5 62 288 3 26 67 286 9 276 4 253 4 228 1 202 8 177 6 152 3 273 3 29 07 273 3 262 9 240 0 214 8 189 5 164 2 138 9 57 276 1 26 53 276 1 270 5 254 1 228 8 203 5 178 3 153 0 257 9 28 96 257 9 254 2 238...

Page 14: ...static pressure and BHP Since no temperature data is given we will assume an air temperature of 70 F Table 8 shows the correction factor to be 0 832 Corrected static pressure 1 5 x 0 832 1 248 IWC Corrected BHP 4 0 x 0 832 3 328 Example 2 A system located at 5 000 feet of elevation is to deliver 6 000 CFM at a static pressure of 1 5 Use the unit blower tables to select the blower speed and the BHP...

Page 15: ...261660 YTG C 0707 Unitary Products Group 15 FIGURE 2 ALTITUDE TEMPERATURE CONVERSION FACTOR ...

Page 16: ... 5 2 4 7 0 7 5 7 5 1 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 5 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1025 4 5 1 5 3 2 2 9 1 3 3 9 3 5 1 1 4 5 4 0 0 8 5 1 4 6 0 7 5 6 5 0 1065 3 5 1 6 3 4 3 0 1 4 4 0 3 6 1 2 4 7 4 2 1 0 5 5 4 9 1095 3 0 1 7 3 5 3 1 1 5 4 2 3 8 1 3 4 9 4 4 1 2 5 7 5 1 1130 2 0 1 9 3 7 3 3 1 7 4 5 ...

Page 17: ... 9 5 0 980 5 0 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9 5 8 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 1035 3 0 2 0 6 2 5 2 1 9 6 8 5 7 1 7 7 4 6 2 1 2 8 1 6 8 1050 2 5 2 1 6 4 5 4 2 0 7 0 5 9 1 8 7 6 6 4 1 3 8 3 7 0 1075 2 0 2 3 6 6 5 5 2 1 7 2 6 0 1 9 7 8 6 6 1 5 8 6 7 2 1100 1 0 2 4 6 7 5 6 2 2 7 3 6 1 2 1 7 9 6 7 230 460...

Page 18: ...2 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1010 4 0 1 8 5 8 4 9 1 7 6 3 5 3 1 5 6 9 5 8 1 0 7 5 6 3 0 5 7 9 6 7 1020 3 5 1 9 6 1 5 1 1 8 6 5 5 5 1 6 7 1 6 0 1 1 7 8 6 6 0 6 8 3 7 0 1035 3 0 2 0 6 2 5 2 1 9 6 8 5 7 1 7 7 4 6 2 1 2 8 1 6 8 0 7 8 6 7 3 1050 2 5 2 1 6 4 5 4 2 0 7 0 5 9 1 8 7 6 6 4 1 3 8 3 7 0 1075 2 0 2 3 6 6 5 5 2 1 7 2 6 0 1 9 7 8 6 6 1 5 8 6 7 2 1100 1 0 2 4 6 7 5 6 2 2 7 3 6 1 2 1 7 9 6 7 ...

Page 19: ... 1 0 4 4 3 9 0 8 5 0 4 5 0 6 5 6 5 0 208 VOLT AND HIGH STATIC DRIVE 965 6 0 1 2 2 7 2 5 0 9 3 2 2 9 0 6 3 7 3 3 0 4 4 4 3 9 0 2 5 0 4 5 980 5 5 1 3 2 9 2 6 1 0 3 4 3 0 0 7 3 8 3 4 0 5 4 5 4 0 0 3 5 1 4 6 1025 4 5 1 4 3 1 2 8 1 2 3 6 3 2 0 9 4 1 3 7 0 7 4 8 4 3 0 4 5 5 4 9 1065 3 5 1 6 3 4 3 0 1 4 3 9 3 5 1 1 4 5 4 0 0 9 5 1 4 6 1125 2 0 1 9 3 6 3 2 1 7 4 4 3 9 1 4 5 0 4 5 1 2 5 8 5 2 1170 1 0 2 1 ...

Page 20: ... 0 2 6 9 5 8 980 5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2 5 2 5 5 1 4 3 2 0 6 1 5 1 1 4 7 1 6 0 0 9 8 4 7 0 1065 2 0 2 6 5 3 4 4 2 1 6 3 5 3 1 5 7 3 6 2 1 0 8 6 7 2 1100 1 0 2 9 5 6 4 7 2 3 6 8 5 7 1 8 7 9 6 6 230 460 575 VOLT AND STANDARD DRIVE 870 6 0 1 3 3 6 3 0 0 7...

Page 21: ...5 0 1 9 4 5 3 8 1 5 5 4 4 5 1 0 6 3 5 3 0 4 7 2 6 1 0 1 8 5 7 1 995 4 5 2 1 4 5 3 9 1 6 5 5 4 7 1 1 6 4 5 4 0 5 7 5 6 3 0 2 8 6 7 3 1025 3 5 2 3 4 9 4 1 1 8 5 8 4 9 1 3 6 7 5 7 0 7 8 0 6 7 1050 2 5 2 5 5 1 4 3 2 0 6 1 5 1 1 4 7 1 6 0 0 9 8 4 7 0 1065 2 0 2 6 5 3 4 4 2 1 6 3 5 3 1 5 7 3 6 2 1 0 8 6 7 2 1100 1 0 2 9 5 6 4 7 2 3 6 8 5 7 1 8 7 9 6 6 230 460 575 VOLT AND STANDARD DRIVE 870 6 0 1 3 3 6 ...

Page 22: ...0 3 13 7 11 2 1215 4 0 2 7 8 6 7 0 2 1 10 4 8 5 1 4 12 3 10 1 0 6 14 3 11 7 1255 3 0 3 0 9 1 7 4 2 4 11 0 9 0 1 7 12 9 10 6 0 9 15 0 12 3 1290 2 0 3 2 9 5 7 8 2 7 11 5 9 4 2 0 13 5 11 1 1 2 15 6 12 8 1330 1 0 3 5 10 0 8 2 3 0 12 0 9 9 2 3 14 1 11 6 1 5 16 4 13 4 1365 0 0 3 7 10 5 8 6 3 2 12 6 10 3 2 6 14 7 12 1 1 8 17 0 13 9 230 460 575 VOLT AND STANDARD DRIVE 975 6 0 1 4 5 9 4 9 1 0 7 3 6 0 0 5 8...

Page 23: ...G CFM 15 TON 17 5 TON 20 TON 25 TON 4500 6000 7200 6000 7500 9000 6000 8000 9400 7500 10000 12500 WET INDOOR COIL 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 ELECTRIC HEAT OPTIONS 18 KW 0 3 0 4 0 4 0 4 0 4 0 5 0 4 0 4 0 5 0 4 0 5 0 6 36 KW 0 3 0 4 0 5 0 4 0 5 0 5 0 4 0 5 0 5 0 5 0 5 0 6 54 KW 0 4 0 5 0 5 0 5 0 5 0 6 0 5 0 5 0 6 0 5 0 6 0 7 72 KW 0 4 0 5 0 5 0 5 0 5 0 6 0 5 0 5 0 6 0 5 0 6 0 7 ...

Page 24: ...1 1 7 2 0 0 None 0 0 36 1 45 E18 18 0 1 21 7 36 1 45 E36 36 0 2 43 3 63 1 70 E54 54 0 2 65 0 74 0 90 E72 72 0 2 86 6 95 6 110 575 8 3 78 0 9 5 9 0 0 None 0 0 28 2 35 E18 18 0 1 17 3 29 0 35 E36 36 0 2 34 6 50 7 60 E54 54 0 2 52 0 59 3 70 E72 72 0 2 69 3 76 7 90 210 17 1 2 208 25 6 190 2 1 20 0 0 0 None 0 0 86 0 110 E18 13 5 1 37 5 86 0 110 E36 27 0 2 75 1 118 7 125 E54 40 6 2 112 6 165 9 175 E72 5...

Page 25: ... 114 1 9 10 0 0 0 None 0 0 56 5 70 E18 18 0 1 21 7 56 5 70 E36 36 0 2 43 3 66 6 70 E54 54 0 2 65 0 77 5 90 E72 72 0 2 86 6 99 1 110 575 13 5 80 1 5 8 2 0 0 None 0 0 44 6 50 E18 18 0 1 17 3 44 6 50 E36 36 0 2 34 6 53 6 60 E54 54 0 2 52 0 62 2 70 E72 72 0 2 69 3 79 5 90 300 25 208 47 1 245 3 7 38 6 0 0 None 0 0 159 4 200 E18 13 5 1 37 5 159 4 200 E36 27 0 2 75 1 159 4 200 E54 40 6 2 112 6 189 1 200 ...

Page 26: ...1 1 7 2 5 0 None 0 0 41 1 50 E18 18 0 1 21 7 42 3 50 E36 36 0 2 43 3 69 4 70 E54 54 0 2 65 0 80 2 90 E72 72 0 2 86 6 101 9 110 575 8 3 78 0 9 5 9 4 0 None 0 0 32 2 40 E18 18 0 1 17 3 34 0 40 E36 36 0 2 34 6 55 7 60 E54 54 0 2 52 0 64 3 70 E72 72 0 2 69 3 81 7 90 210 17 1 2 208 25 6 190 2 1 20 0 10 0 None 0 0 96 0 110 E18 13 5 1 37 5 96 0 110 E36 27 0 2 75 1 131 2 150 E54 40 6 2 112 6 178 4 200 E72...

Page 27: ...14 1 9 10 0 5 0 None 0 0 61 5 70 E18 18 0 1 21 7 61 5 70 E36 36 0 2 43 3 72 9 80 E54 54 0 2 65 0 83 7 90 E72 72 0 2 86 6 105 4 110 575 13 5 80 1 5 8 2 4 0 None 0 0 48 6 60 E18 18 0 1 17 3 48 6 60 E36 36 0 2 34 6 58 6 60 E54 54 0 2 52 0 67 2 70 E72 72 0 2 69 3 84 5 90 300 25 208 47 1 245 3 7 38 6 10 0 None 0 0 169 4 200 E18 13 5 1 37 5 169 4 200 E36 27 0 2 75 1 169 4 200 E54 40 6 2 112 6 201 6 225 ...

Page 28: ... 3 4 3 4 NOM CFM TOTAL Each 4 000 4 000 5 000 5 000 CONDENSER COIL ROWS DEEP 2 FINS PER INCH 20 FACE AREA Sq Ft 63 8 COMPRESSOR Qty Per Unit SCROLL 2 FILTERS QUANTITY PER UNIT 12 X 24 X 2 12 TOTAL FACE AREA Sq Ft 24 CHARGE REFRIGERANT 22 Lb Oz SYSTEM No 1 23 0 24 0 23 8 23 8 SYSTEM No 2 23 8 24 0 23 8 23 8 OPERATING WEIGHTS LBS BASIC UNIT COOLING ONLY 2260 2540 2560 2660 GAS ELECTRIC N24 2460 2740...

Page 29: ...t control box 3Second stage heating is not required on units with a single stage electric heater 4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set back position NOTE Fans switch must be in ON position for minimum ventilation during heater operation LINE VOLTAGE TERMINAL BLOCK 2TB IN CONTROL BOX GROUND LUG Refer to the ELECTR...

Page 30: ... 00 6 3 8 7 1 8 35 5 7 8 136 1 4 GAS OR ELECTRIC HEAT ACCESS DOT PLUG For pressure drop reading BLOWER COMPARTMENT ACCESS Auxiliary C GAS SUPPLY ENTRY CONTROL BOX ACCESS VENT AIR OUTLET HOODS BLOWER MOTOR ACCESS Location of Optional VFD Bypass BLOWER ACCESS Location of Optional VFD 52 5 8 180 19 32 COMPRESSOR ACCESS DISCONNECT SWITCH LOCATION ECONOMIZER MOTORIZED DAMPER FIXED OUTDOOR INTAKE AIR AN...

Page 31: ...haust option The covering consists of a heavy black paper composition 3 Replace the side supply and return air compartment panels For side duct applications 1 Replace the side panels on the supply and return air compartments with the side duct flange accessory kit panels 2 Connect ductwork to the flanges on those panels SUPPLY AIR RETURN AIR OUTDOOR AIR 5 1 8 18 5 8 27 3 4 39 5 8 40 1 2 OUTDOOR AI...

Page 32: ...RANCES LOCATION CLEARANCE Front 36 Rear 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 36 With Economizer 3 Right Side Cond Coil 36 Below Unit1 1 Units may be installed on combustible floors made from wood or class A B or C roof covering material 0 Above Unit2 2 Units must be installed outdoors Overhanging structures or shrubs should not obstruct condenser air dis...

Page 33: ...261660 YTG C 0707 Unitary Products Group 33 FIGURE 7 UNIT CENTER OF GRAVITY FIGURE 8 TYPICAL UNIT APPLICATIONS ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION ...

Page 34: ...99 481 300 Elec 2846 496 927 927 496 180 Gas 2660 302 316 453 590 565 434 210 Gas 2928 340 340 488 636 636 488 240 Gas 2960 344 344 493 643 643 493 300 Gas 3046 354 354 508 661 661 508 180 Elec 2460 280 292 419 546 523 401 210 Elec 2728 317 317 455 592 592 455 240 Elec 2760 321 321 460 599 599 460 300 Elec 2846 331 331 474 618 618 474 Unit Size Total Shipping Weight 4 Point Loads lbs A B C D 6 Poi...

Page 35: ...mension of the ducts allows duct work penetration between roof joists that are spaced on 72 centers Note Ducts can be installed into the curb from the roof All electrical and gas line connections can be made inside the curb FIGURE 10 UNIT ROOF CURB DIMENSIONS 25 1 4 FIGURE 11 ROOF CURB DUCT OPENINGS DIMENSION FIGURE 12 CUT AWAY OF ROOF CURB ...

Page 36: ...MINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage cooling units Jumper is required if there is no Smoke Detector circuit Jumper is required for any combination of R RC or RH 6 5 5 6 OCC is an output from the thermostat to indicate the Occupied condition X is an input to the the...

Page 37: ... They shall have built in field convertible duct connections for down discharge supply return or horizontal discharge supply return and be available with factory installed options or field installed accessories The units shall be factory wired piped charged with R 22 refrigerant and factory tested prior to ship ment All unit wiring shall be both numbered and color coded All units shall be manufact...

Page 38: ...table circuit breaker on the 24 volt transformer side b Unit shall incorporate a lockout circuit which pro vides reset capability at the space thermostat or base unit should any of the following standard safety devices trip and shut off compressor c Loss of charge Low pressure switch 1 High pressure switch 2 Freeze protection thermostat evaporator coil If any of the above safety devices trip a LED...

Page 39: ... Simultaneous economizer com pressor operation is also possible Dampers shall fully close on power loss BAS READY ECONOMIZER Outdoor and return air dampers that are interlocked and positioned by a fully modulating spring return damper actuator The maxi mum leakage rate for the outdoor air intake dampers shall not exceed 2 when dampers are fully closed and operating against a pressure differential ...

Page 40: ...r static pressure requirements WOOD SKID Allows unit to be handled with 90 forks ECONOMIZER MOTORIZED DAMPER RAIN HOOD DJN E C300 only Contains all hood panels and the hardware for assembling ANTI RECYCLE TIMER Assures 5 minute off time between compressor cycles LOW AMBIENT KIT Provides unit cooling operation down to 0 F COIL GUARD KIT Guard for cooling coil OTHER FACTORY INSTALLED OPTIONS POWER E...

Reviews: