BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
2.80 m
3
/s
3.30 m
3
/s
3.80 m
3
/s
4.10 m
3
/s
4.40 m
3
/s
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
ESP
(Pa)
Output
(kW)
Input
(kW)
HIGH STATIC DRIVE (m
3
/s)
895
6.0
312
3.5
4.0
268
3.7
4.3
198
4.2
4.8
143
4.6
5.2
79
5.1
5.8
930
5.0
362
3.7
4.3
318
4.0
4.5
248
4.5
5.1
193
4.9
5.6
129
5.4
6.2
970
4.0
421
4.0
4.5
377
4.2
4.9
306
4.8
5.5
252
5.2
6.0
187
5.8
6.6
1005
3.0
473
4.2
4.8
429
4.5
5.1
359
5.1
5.8
304
5.6
6.4
240
6.1
7.0
1045
2.0
535
4.4
5.0
491
4.8
5.5
420
5.4
6.2
365
5.9
6.8
-
-
-
1080
1.0
590
4.6
5.3
546
5.0
5.8
475
5.7
6.5
420
6.2
7.1
-
-
-
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)*
AIRFLOW
5930 CFM
6990 CFM
8050 CFM
8685 CFM
9320 CFM
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
ESP
(iwg)
Output
(bhp)
Input
(kW)
HIGH STATIC DRIVE (CFM)
895
6.0
1.3
4.7
4.0
1.1
5.0
4.3
0.8
5.6
4.8
0.6
6.1
5.2
0.3
6.8
5.8
930
5.0
1.5
5.0
4.3
1.3
5.3
4.5
1.0
6.0
5.1
0.8
6.6
5.6
0.5
7.2
6.2
970
4.0
1.7
5.3
4.5
1.5
5.7
4.9
1.2
6.4
5.5
1.0
7.0
6.0
0.8
7.8
6.6
1005
3.0
1.9
5.6
4.8
1.7
6.0
5.1
1.4
6.8
5.8
1.2
7.4
6.4
1.0
8.2
7.0
1045
2.0
2.1
5.9
5.0
2.0
6.4
5.5
1.7
7.3
6.2
1.5
7.9
6.8
-
-
-
1080
1.0
2.4
6.2
5.3
2.2
6.8
5.8
1.9
7.7
6.5
1.7
8.4
7.1
-
-
-
5120416-XIM-C-0216
32
Johnson Controls Unitary Products
NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 16 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static
pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
Supply Air Blower Performance (20 Ton) - Cooling Only 240 Mbh - Bottom Duct Connections