036-21216-003-A-0204
Unitary Products Group
5
WALL THERMOSTAT - The units are designed to operate
with 24-volt electronic and electro-mechanical thermostats.
All units can operate with single stage heat / single stage cool
thermostats - with or without the economizer.
.
FIGURE 1 - SUNLINE ULTRA CUTAWAY (Model DHG gas heating)
L O W V O L T A G E R E L A Y B O A R D
A N D T E R M I N A L S T R I P
B E L T D R I V E
B L O W E R M O T O R
2 0 G A U G E A L U M I N I Z E D
S T E E L T U B U L A R H E A T
E X C H A N G E R
L O N G L A S T I N G
P O W D E R P A I N T F I N I S H
E L E C T R I C H E A T
A C C E S S O R Y
L O C A T I O N
( E l e c / E l e c U n i t s )
P O W E R V E N T E R M O T O R
W I T H P O S T P U R G E C Y C L E
H I G H E F F I C I E N C Y
C O M P R E S S O R S
F U L L P E R I M E T E R B A S E
R A I L S W I T H F O R K L I F T
S L O T S A N D L I F T I N G H O L E S
C O P P E R T U B E /
A L U M I N U M F I N
C O N D E N S I N G C O I L
K N O C K O U T F O R S I D E
G A S S U P P L Y E N T R Y
K N O C K O U T F O R B O T T O M
P O W E R E N T R Y
K N O C K O U T F O R B O T T O M
G A S S U P P L Y E N T R Y
T E R M I N A L B L O C K
( F o r S i n g l e P o i n t P o w e r
S u p p l y o n E l e c / E l e c U n i t s )
K N O C K O U T S F O R
S I D E P O W E R A N D
C O N T R O L E N T R Y
3 / 4 " P V C F E M A L E
C O N D E N S A T E D R A I N
B O T T O M R E T U R N A I R
D U C T O P E N I N G
S I D E R E T U R N A I R
D U C T O P E N I N G
O U T D O O R A I R O P E N I N G
F O R S L I D E - I N / P L U G - I N
I N T N E R A L E C O N O M I Z E R
E C O N O M I Z E R H O O D
E L E C T R I C A L D I S C O N N E C T
M O U N T I N G L O C A T I O N
( F i e l d I n s t a l l e d )
TABLE 1: CAPACITY RATING - COOLING / ELECTRIC HEAT
MODEL
ARI RATINGS
1
NOMINAL ELECTRIC HEAT CAPACITY
2
(kW)
COOLING CAPACITY
80 / 67-95
°
F
SOUND
RATING
3
(dBels)
MBH
SEER
4
EER
5
240V
480V
DHE036
42.5
12.25
11.10
86
5, 7, 10,
15 & 20
7, 10,
15 & 20
DHE048
46.5
13.20
11.40
87
DHE060
57.0
12.20
10.60
86
5, 7, 10,
15, 20 & 30
7, 10, 15,
20 & 30
1.
Certified in accordance with the Unitary Small Equipment certification program, which is
based on ARI Standard 210/240.
2.
Heaters are available as accessories - all with single point power supply.
3.
Rated in accordance with ARI Standard 270.
4.
SEER = Seasonal Energy Efficiency Ration - the total cooling output in BTU’s during a nor-
mal annual usage period for cooling divided by the total electric power input in watt-hours
during the same period.
5.
EER = Energy Efficiency Ration - the cooling capacity in Btu’s per hour (Btuh) divided by
the power input in watts at any given set of rating conditions, expressed in BTUH per watt
(BTUH/watt).