035-16703-001-A-0202
6
Unitary Products Group
DEB
POWER
SUPPLY
COMPRESSOR
COND.
FAN
MOTOR
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
ELECTRIC HEAT ACCESSORY
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
1
AMPS
MAX.
HACR
2
BREAKER
SIZE
MODEL
RLA
LRA
MODEL NO.
ST
AGE
KW
TOTAL
AMPS
018 208/230-1-60
9.0
48.0
1.1
2.6
2NH04500506
2NH04500706
1
2
3.8/5.0 *
5.6/7.5 *
18.1/20.8
27.1/31.3
25.8/29.3
37.1/42.3
30/30
40/45
30/30
40/45
024 208/230-1-60
11.2
60.0
1.1
2.6
2NH04500506
2NH04500706
2NH04501006
1
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
18.1/20.8
27.1/31.3
36.1/41.7
25.8/29.3
37.1/42.3
48.4/55.3
30/30
40/45
50/60
30/30
40/45
50/60
030 208/230-1-60
12.0
73.0
1.1
2.6
2NH04500506
2NH04500706
2NH04501006
2NH04501506
1
2
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
18.1/20.8
27.3/31.3
36.1/41.7
54.2/62.5
25.8/29.3
37.1/42.3
48.4/55.3
71.0/81.4
30/30
40/45
50/60
80/90
30/30
40/45
50/60
80/90
036 208/230-1-60
17.3
94.0
1.1
3.5
2NH04501006
2NH04501506
2
2
7.5/10.0 *
11.3/15.0 *
36.1/41.7
54.2/62.5
49.5/56.5
72.1/82.5
50/60
80/90
50/60
80/90
042 208/230-1-60
20.5
120.0
1.1
3.5
2NH04500506
2NH04500706
2NH04501006
2NH04501506
1
2
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
18.1/20.8
27.1/31.3
36.1/41.7
54.2/62.5
30.2/30.4
38.2/43.4
49.5/56.5
72.1/82.5
40/40
50/50
50/60
80/90
40/40
50/50
50/60
80/90
048 208/230-1-60
24.4
140.0
1.3
4.0
2NH04501006
2NH04501506
2NH04502006
2NH04502506
2
2
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
36.1/41.7
54.2/62.5
72.2/83.3
90.3/104.2
50.1/57.1
72.1/83.1
95.3/109.2
117.8/135.2
60/60
80/90
100/110
125/150
60/60
80/90
100/110
125/150
060 208/230-1-60
28.9
165.0
1.3
7.0
2NH04501006
2NH04501506
2NH04502006
2NH04502506
2
2
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
36.1/41.7
54.2/62.5
72.2/83.3
90.3/104.2
53.9/60.8
76.5/86.9
99.0/112.9
121.6/139.0
70/70
80/90
100/125
125/150
70/70
80/90
100/125
125/150
036 208/230-3-60
10.9
78.0
1.1
3.5
2NH04501025
2NH04501525
1
1
7.5/10.0 *
11.3/15.0 *
20.8/24.1
31.3/36.1
30.4/34.4
43.5/49.5
35/35
45/50
35/35
45/50
042 208/230-3-60
14.1
110.0
1.1
3.5
2NH04501025
2NH04501525
1
1
7.5/10.0 *
11.3/15.0 *
20.8/24.1
31.3/36.1
30.4/34.4
43.5/49.5
35/35
45/50
35/35
45/50
048 208/230-3-60
14.1
105.0
0.7
4.0
2NH04501025
2NH04501525
2NH04502025
2NH04502525
1
1
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
20.8/24.1
31.3/36.1
41.7/48.1
52.1/60.1
31.1/35.1
44.1/50.1
57.1/65.1
70.2/80.2
35/40
45/60
60/70
80/90
35/40
45/60
60/70
80/90
060 208/230-3-60
16.0
125.0
1.3
7.0
2NH04501025
2NH04501525
2NH04502025
2NH04502525
1
1
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
20.8/24.1
31.3/36.1
41.7/48.1
52.1/60.1
34.8/38.8
47.8/53.9
60.9/68.9
73.9/83.9
40/40
50/60
70/70
80/90
40/40
50/60
70/70
80/90
036
460-3-60
5.8
40.0
0.6
1.8
2NH04501046
2NH04501546
1
1
10.0 **
15.0 **
12.0
18.0
17.3
24.8
20
25
20
25
042
460-3-60
7.1
54.0
0.6
1.8
2NH04501046
2NH04501546
1
1
10.0 **
15.0 **
12.0
18.0
17.3
24.8
20
25
20
25
048
460-3-60
7.1
55.0
0.6
2.0
2NH04501046
2NH04501546
2NH04502046
2NH04502546
1
1
2
2
10.0 **
15.0 **
20.0 **
25.0 **
12.0
18.0
24.1
30.1
17.5
25.1
32.6
40.1
20
30
35
45
20
30
35
45
060
460-3-60
8.0
67.0
0.7
3.5
2NH04501046
2NH04501546
2NH04502046
2NH04502546
1
1
2
2
10.0 **
15.0 **
20.0 **
25.0 **
12.0
18.0
24.1
30.1
19.4
26.9
34.4
42.0
20
30
35
45
20
30
35
45
036
575-3-60
4.5
32.0
0.4
1.5
2NH04501058
2NH04501558
1
1
10.0 ***
15.0 ***
9.6
14.4
13.9
19.9
15
20
15
20
042
575-3-60
5.8
44.0
0.4
1.5
2NH04501058
2NH04501558
1
1
10.0 ***
15.0 ***
9.6
14.4
13.9
19.9
15
20
15
20
048
575-3-60
5.6
44.0
0.6
1.6
2NH04501058
2NH04501558
2NH04502058
2NH04502558
1
1
2
2
10.0 ***
15.0 ***
20.0 ***
25.0 ***
9.6
14.4
19.2
24.1
14.0
20.0
26.1
32.1
15
25
30
35
15
25
30
35
060
575-3-60
6.4
50.0
0.6
2.8
2NH04501058
2NH04501558
2NH04502058
2NH04502558
1
1
2
2
10.0 ***
15.0 ***
20.0 ***
25.0 ***
9.6
14.4
19.2
24.1
15.5
21.5
27.6
33.6
20
25
30
35
20
25
30
35
1
= Dual element, time delay type.
* = KW listed is for 240 volts, use table on previous page for 208 or 230 volts.
2
= Standard circuit breakers may be used in Canada and on applications ** = KW listed is for 480 volts, use table on previous page for 460 volts.
over 60 amps where the heaters are separately fused. *** = KW listed is for 600 volts, use table on previous page for 575 volts.
TABLE 5 -
ELECTRICAL DATA (COOLING / ELECTRIC HEAT)