background image

CLEARANCES

All units require certain clearances for proper operation and
service. Refer to Figure 3 for the clearances required for com-
bustion, construction, servicing and proper unit operation.

WARNING: Do not permit overhanging structures or shrubs to

obstruct the condenser air discharge outlet.

DUCT WORK

These units are adaptable to downflow use as well as rear sup-
ply and return air duct openings. To convert to downflow, use
the following steps:

1. Remove the duct covers found in the bottom return and

supply air duct openings. There are four (4) screws secur-
ing each duct cover (save these screws to use later).

2. Install the duct covers, removed in step one, to the rear sup-

ply and return air duct openings. Secure with the four (4)
screws used in step one.

3. Seal the duct covers with silicone caulking.

Downflow units must have an L-shaped supply duct without
any outlets or registers located directly below the supply outlet
of the unit.

Duct work should be designed and sized according to the
methods of the Air Conditioning Contractors of America
(ACCA), as set forth in their Manual D.

A closed return duct system shall be used. This shall not pre-
clude use of economizers or ventilation air intake. Flexible
joints may be used in the supply and return duct work to mini-
mize the transmission of noise.

CAUTION: When fastening duct work to the side duct flanges on

the unit, insert the screws through the duct flanges only.
DO NOT insert the screws through the casing. Outdoor
duct work must be insulated and waterproofed.

NOTE: Be sure to note supply and return openings.

Refer to Figure 3 for information concerning rear and bottom
supply and return air duct openings.

FILTERS

Single phase units are shipped without a filter and is the responsi-
bility of the installer to secure a filter in the return air ductwork or
install a Filter/Frame Kit 
(1FF0114).

A filter rack and a filters are standard on three phase units.

Filters must always be used and must be kept clean. When fil-
ters become dirt laden, insufficient air will be delivered by the
blower, decreasing your units efficiency and increasing operat-
ing costs and wear-and-tear on the unit and controls.

Filters should be checked monthly especially since this unit
may be used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is required to be installed in the condensate
drain. The plumbing must conform to local codes. Use a seal-
ing compound on male pipe threads. Install the condensate
drain line (

3

4

“ NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the follow-
ing removable panels:

Blower service access

Electrical/filter access

Compressor service access

Refer to Figure 3 for location of these access panels and mini-
mum clearance.

THERMOSTAT

The room thermostat should be located on an inside wall ap-
proximately 56" above the floor where it will not be subject to
drafts, sun exposure or heat from electrical fixtures or appli-
ances. Follow manufacturer's instructions enclosed with the
thermostat for general installation procedure. Four or five color
coded insulated wires (minimum #18 AWG) should be used to
connect thermostat to unit. See Figure 2.

035-16703-001-A-0202

Unitary Products Group

3

MODELS

DEB

018

024

030

036

042

048

060

EVAPORATOR

BLOWER

CENTRIFUGAL BLOWER (Dia. x Wd. in.)

9 X 6

10 X 8

10 X 8

10 x 8

11 X 10

11 x 10

11 x 10

FAN MOTOR HP (Three Speed)

1

2

1

2

1

2

3

4

3

4

3

4

1

EVAPORATOR

COIL

ROWS DEEP

2

2

2

2

2

2

3

FINS PER INCH

13

15

15

15

15

13

16

FACE AREA (Sq. Ft.)

2.19

2.81

4.38

4.38

4.38

5.62

5.26

CONDENSER

FAN

PROPELLER DIA. (in.)

22

22

22

22

22

22

22

FAN MOTOR HP

1

4

1

4

1

4

1

4

1

4

1

4

1

4

NOM. CFM TOTAL

1,800

2,200

2,400

2,400

2,400

2,800

2,800

CONDENSER

COIL

ROWS DEEP

1

1

1

1

1

1

1

FINS PER INCH

18

16

20

18

16

13

20

FACE AREA (Sq. Ft.)

8.3

8.3

8.3

8.3

11.7

16.4

16.4

CHARGE

REFRIGERANT 22 (lbs./oz.)

3 / 4

3 / 5

3 / 13

3 / 10

4 / 7

5 / 15

5 / 15

FILTER

FACE AREA (Sq. Ft. / Qty. / Size)

2.14 / 2 / 14" x 22"

COMPRESSOR HERMETIC Type,  (Qty. = 1)

Recip

Recip

Recip

Recip

Recip

Scroll

Scroll

TABLE 3 -

PHYSICAL DATA

Get other manuals https://www.bkmanuals.com

Summary of Contents for CHAMPION D1EB018

Page 1: ...fer ence forms 55 70 N1 General Installation 55 70 N2 Pre start Post start Check List 511 26 N1 1V Electric Heater Accessory REPLACEMENT PARTS Refer to Replacement Parts Manual for complete listing of...

Page 2: ...he unit Spreader bars of suffi cient length should be used across the top of the unit BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY U...

Page 3: ...used and must be kept clean When fil ters become dirt laden insufficient air will be delivered by the blower decreasing your units efficiency and increasing operat ing costs and wear and tear on the...

Page 4: ...2 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information COMPRESSORS Units are shipped with compressor mountings factory adjusted for shi...

Page 5: ...08 230 3 60 187 253 14 1 110 0 1 1 3 5 22 2 30 30 96 75 048 208 230 3 60 187 253 14 1 105 0 0 7 4 0 22 3 30 30 96 75 060 208 230 3 60 187 253 16 0 125 0 1 3 7 0 28 3 40 40 96 75 036 460 3 60 414 504 5...

Page 6: ...0 1 1 3 5 2NH04501025 2NH04501525 1 1 7 5 10 0 11 3 15 0 20 8 24 1 31 3 36 1 30 4 34 4 43 5 49 5 35 35 45 50 35 35 45 50 048 208 230 3 60 14 1 105 0 0 7 4 0 2NH04501025 2NH04501525 2NH04502025 2NH0450...

Page 7: ...ure drop across a dry coil the actual CFM through the unit can be determined from the curve in Coil Delta P vs Supply Air CFM figure WARNING Failure to properly adjust the total system air quan tity c...

Page 8: ...6 1 18 7 21 3 105 5 3 6 6 7 8 10 9 14 0 17 1 20 3 110 8 3 11 9 15 5 19 2 115 5 7 9 8 14 0 18 1 TABLE 6 SUPERHEAT CHARGING TABLE FOR MODEL D1EB018 OUTDOOR TEMPERATURE F SUPERHEAT AT COMPRESSOR SUCTION...

Page 9: ...20 9 22 9 24 7 26 5 28 2 30 0 75 7 8 10 0 12 2 14 5 16 7 18 9 21 2 23 3 25 4 27 5 29 6 80 7 3 9 7 12 1 14 5 17 0 19 4 21 8 24 2 26 7 29 1 85 7 2 9 8 12 4 15 0 17 6 20 4 23 1 25 9 28 6 90 6 1 7 7 9 4...

Page 10: ...15 14 1 2 283 8 33 8 31 2 289 16 23 8 13 4 13 4 13 4 31 2 15 14 1 2 14 1 2 BOTTOM SUPPLY AIR OPENING 23 8 33 4 471 4 LOW VOLTAGE CONN 7 8 DIA KNOCKOUT HIGH VOLTAGE CONN 131 32 DIA KNOCKOUT FRONT ELECT...

Page 11: ...fan control board The 24 volts signal will ener gize relay K2 on the fan control board and the first stage of electric heat will be energized 3 When the heating demand is satisfied the electric heat w...

Page 12: ...PROVAL When the system is functioning properly secure the owner s approval Show him the location of all disconnect switches and the thermostat Teach him how to start and stop the unit and how to adjus...

Page 13: ...16 PR 713 PR 713 PR 710 PR 710 PR F6 F6 F4 F4 F2 F2 K6 K6 K4 K4 K5 K5 K3 K3 M1 M1 714 BK 714 BK 706 BK 706 BK 711 BK 711 BK 703 BK 703 BK 709 BK 709 BK F1 F1 F3 F3 F5 F5 DUAL POINT ELECTRIC HEAT SEE N...

Page 14: ...1 A 0202 FIG 5 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY M R C COMPR RELAY DFST STAT M1 DETAIL A 222 Y BLU BLU DS DEFROST CONTROL 031 01268 000B FOR DEFROST CONTROL 031 09104 000A SEE DETAIL A Get...

Page 15: ...B K 3 8 1 3 B R 8 1 4 Y L 2 L 2 L 2 1 2 3 H 1 L 1 L 1 L 1 K 1 2 0 9 R K 2 F A N C O N T R O L B O A R D T L H F L H 4 1 2 3 4 P 2 S 2 8 0 9 O 8 0 8 B R 2 0 4 B R S E E N O T E 8 1 1 D 1 4 D 1 5 D L S...

Page 16: ...ELEC HEAT PTCR START ASSIST OPTIONAL DEVICE 20 25 20 25 20 25 CB CIRCUIT BREAKER 24V 3 AMP F7 F8 F9 TB2 TERMINAL BLOCK ECM MOTOR SPEED CONNECTIONS M2 CONTACTOR ELECTRIC HEAT 230V COIL M3 CONTACTOR ELE...

Page 17: ...e Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2001 All Rights Reserved Supersedes 035 16703 000 A 0701 035 16703 001 A 0202 Get...

Reviews: