268723-BIM-C-0908

12

Johnson Controls Unitary Products

Compressors

The scroll compressor used in this product is specifically 
designed to operate with R-410A Refrigerant and cannot be 
interchanged.

The compressor also uses a polyolester (POE oil), Mobil 3MA 
POE. This oil is extremely hydroscopic, meaning it absorbs 
water readily. POE oil can absorb 15 times as much water as 
other oils designed for HCFC and CFC refrigerants. Take all 
necessary precautions to avoid exposure of the oil to the 
atmosphere.

POE (polyolester) compressor lubricants are known to cause 
long term damage to some synthetic roofing materials.

Procedures which risk oil leakage include, but are not limited to, 
compressor replacement, repairing refrigerant leaks, replacing 
refrigerant components such as filter drier, pressure switch, 
metering device or coil.

Units are shipped with compressor mountings which are 
factory-adjusted and ready for operation.

Phasing

Three-phase, scroll compressors operate in only one direction. 
If the scroll is drawing low amperage, has similar suction and 
discharge pressures, or is producing a high noise level, the 
scroll is misphased. Change the incoming line connection 
phasing to obtain the proper rotation.

CONDENSER FAN DATA

Fan diameter (Inch)

22

22

22

22

22

22

Type

Prop

Prop

Prop

Prop

Prop

Prop

Drive type

Direct

Direct

Direct

Direct

Direct

Direct

No. speeds

1

1

1

1

1

1

Number of motors

1

1

1

1

1

1

Motor HP each

 1/4

 1/4

 1/4

 1/4

 1/4

 1/2

RPM

850

850

850

850

850

1100

Nominal total CFM

1800

1800

2400

2400

3000

3000

DIRECT DRIVE EVAP FAN DATA

Quantity

1

1

1

1

1

1

Fan Size (Inch)

10 x 8

10 x 8

11 x 10

11 x 10

11 x 10

11 x 10

Type

Centrifugal

Centrifugal

Centrifugal

Centrifugal

Centrifugal

Centrifugal

No. speeds

5

5

5

5

5

5

Motor HP each

 1/2

 1/2

 3/4

 3/4

 3/4

1

RPM

Variable

Variable

Variable

Variable

Variable

Variable

Frame size

48

48

48

48

48

48

FILTERS

Quantity - Size

2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1

Table 6:

Physical Data  (Continued)

Component

Models

BUZ024

BUZ030

BUZ036

BUZ042

BUZ048

BUZ060

Nominal Tonnage

2.0

2.5

3.0

3.5

4.0

5.0

This system uses R-410A Refrigerant which operates at 
higher pressures than R-22. No other refrigerant may be 
used in this system.

Do not leave the system open to the atmosphere. Unit 
damage could occur due to moisture being absorbed by 
the 

POE oil

 in the system. This type of oil is highly 

susceptible to moisture absorption

Exposure, even if immediately cleaned up, may cause 
embrittlement (leading to cracking) to occur in one year 
or more. When performing any service that may risk 
exposure of compressor oil to the roof, take precautions 
to protect roofing.

Do not loosen compressor mounting bolts.

Scroll compressors require proper rotation to operate 
properly. Failure to check and correct rotation may result 
in property damage.

Summary of Contents for BUZ024

Page 1: ...heat pumps designed for outdoor installation on a roof top or a slab Field installed electric heater accessories are available to provide supplemental electric heat combined with electric cooling and...

Page 2: ...mited to building electrical and mechanical codes Before performing service or maintenance operations on unit turn off main power switch to unit Electrical shock could cause personal injury Improper i...

Page 3: ...denser Fan Motor Highly Efficient Enhanced Copper Tube Aluminum Fin Indoor Coil Highly Efficient Enhanced Copper Tube Aluminum Fin Outdoor Coil Decorative Protective Coil Guard 5 Speed Direct Drive Bl...

Page 4: ...the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreader bars whose length exceeds the largest dimension across the unit MUST...

Page 5: ...SIDE RETURN AIR OPENING SIDE SUPPLY AIR OPENING LOW VOLTAGE CONN 7 8 DIA KNOCKOUT HIGH VOLTAGE CONN 1 31 32 DIA KNOCKOUT HIGH VOLTAGE CONN 7 8 DIA KNOCKOUT A 3 3 4 1 1 2 2 1 2 2 3 8 4 1 2 49 1 8 28 1...

Page 6: ...T 26 3 4 CONDENSATE DRAIN 3 4 NPTF LOW VOLTAGE CONN 7 8 DIA KNOCKOUT HIGH VOLTAGE CONN 1 31 32 x 7 8 KNOCKOUT 22 1 2 43 1 2 40 1 2 4 14 1 2 28 3 8 14 1 2 BACK 3 3 8 SIDE RETURN AIR OPENING 14 1 2 3 1...

Page 7: ...bottom supply and return air duct openings Roof Curb On applications when a roof curb is used the unit must be positioned on the curb so the front of the unit is tight against the curb Filters Single...

Page 8: ...and or local ordinances The unit must be electrically grounded in accordance with local codes or in their absence with the N E C C E C Voltage tolerances which must be maintained at the compressor te...

Page 9: ...led 24 volt wire Only required on units with supplemental electric heat PROGRAMMABLE THERMOSTAT ONLY THERMOSTAT UNIT CONTROL BOARD TERMINAL STRIP 24 VOLT TRANSFORMER NOTE HEAT ANTICIPATOR SHOULD BE SE...

Page 10: ...5 2 54 2 62 5 94 2 104 6 100 110 208 230 3 60 11 5 77 18 1 2 6 0 None 21 6 30 2NH04501025 7 5 10 1 20 8 24 1 47 6 51 6 50 60 2NH04501525 11 3 15 1 31 3 36 1 60 7 66 7 70 70 460 3 60 5 1 35 8 0 8 3 0 N...

Page 11: ...R410a R410a R410a R410a R410a R410a Refrigerant charge lb oz 6 0 7 4 9 6 12 0 10 10 11 8 ARI HEATING PERFORMANCE 47 F Capacity Rating Mbh 22 2 27 8 32 8 40 0 45 5 56 0 System Power Kw COP 3 4 3 3 3 0...

Page 12: ...Direct Direct Direct Direct Direct Direct No speeds 1 1 1 1 1 1 Number of motors 1 1 1 1 1 1 Motor HP each 1 4 1 4 1 4 1 4 1 4 1 2 RPM 850 850 850 850 850 1100 Nominal total CFM 1800 1800 2400 2400 30...

Page 13: ...030 1922 746 1069 1829 746 1104 1712 728 1134 1528 659 1146 High 5 2214 968 1104 2089 918 1121 1949 859 1136 1785 787 1148 1576 689 1154 Table 8 Bottom Duct Application Size Tons Blower Speed Setting...

Page 14: ...0 700 0 01 0 00 0 02 0 03 800 0 01 0 01 0 02 0 03 900 0 01 0 01 0 02 0 04 1000 0 02 0 01 0 02 0 04 1100 0 03 0 01 0 03 0 05 1200 0 04 0 02 0 03 0 06 1300 0 04 0 03 0 03 0 07 1400 0 04 0 04 0 03 0 08...

Page 15: ...or cooling has been satisfied the 24 volt Y signal is removed and the M1 contactor is de energized When the fan switch on the thermostat is in the ON position the indoor blower motor continues to run...

Page 16: ...bit feature prohibits defrost if the coil temperature is above 40 F A forced defrost feature puts the system into a defrost period every 6 hours and 4 minutes to recirculate lubricants unless the coil...

Page 17: ...VALVE ENERGIZED SYSTEM OPERATES IN COOLING COMPRESSOR AND OUTDOOR FAN INSTANT OFF FAN 60 SEC DELAY OFF FAN INSTANT ON OFF COMPRESSOR AND OUTDOOR FAN INSTANT ON AFTER ANTI SHORT CYCLE DELAY SYSTEM OPE...

Page 18: ...OPERATES IN HEATING HEATER BANK 1 2 3 ELEC HEAT INSTANT ON HEATER BANK 4 5 6 ELEC HEAT 10 SEC DELAY ON OFF COMPRESSOR AND OUTDOOR FAN INSTANT OFF HEATER BANK 4 5 6 ELEC HEAT INSTANT OFF HEATER BANK 1...

Page 19: ...268723 BIM C 0908 Johnson Controls Unitary Products 19 Typical Wiring Diagrams Typical BUZ024 060 Heat Pump 208 230 1 60 volt Wiring Diagram...

Page 20: ...268723 BIM C 0908 20 Johnson Controls Unitary Products Typical BUZ030 060 Heat Pump 230 3 60 volt Wiring Diagram...

Page 21: ...268723 BIM C 0908 Johnson Controls Unitary Products 21 Typical BUZ030 060 Heat Pump 460 3 60 volt Wiring Diagram...