background image

12

HIGH WALL

Vertical Discharge Condensing Unit
(H*DA, H*DB, H*RA)

The indoor unit and interconnecting wiring voltage is
220 volts. Where the outdoor unit requires a different
operating voltage such as 24 volts one of the following
solutions can be applied.
1. The coil of the relay switching the compressor and

reversing valves should be changed to a 220V coil.

2. A transformer should be installed to supply 24 volts

and a relay installed with a 220 volt coil to switch the
24 volts required by the outdoor units. The transformer
should be energised at all times and not switched by
the start signal from the indoor unit. Switching the
transformer directly will cause electronic noise which
may cause malfunction of the electronics.

Wiring

L   N    1    2

For further detail on wiring of these units, see the diagrams pasted
inside each unit.

Cautions

• Never modify the unit by removing any of the safety

guards or by bypassing any of the safety interlock
swithces.

• Connect the connecting cable correctly and connect

the connecting cable to terminal as identified with their
respective marks.

• Do not scratch the conductive core & inner insulator of

power supply cables and do not deform or smash on
the surface of cables.

Electrical Connections

All electrical wiring and connections must comply with
local codes and standards. Power supply cord and
interconnection cord used must not be lighter than
Polychloroprene sheated cord (245 IEC 57 or H05RN-F).
Disconnecting device must have a contact separation
of at least 3 mm.

MHC 07-25 -Cooling Only

  

2

1

3

1

N

L

2

N

4

3

4

MHC 07-25 -Heat Pump

  

2

1

3

1

N

L

2

N

4

3

4

For correct installation, a proper ground connection must be
made for unit.

Wiring sizes

Or as required to meet national and local codes.

Notes

• Terminals N and 1 (see diagrams above) correspond

to power supply to the indoor unit coming from the
outdoor unit.

• Compressor power supply is established by teminal 2.
• Power supply to the 4-way valve is established by

terminal 3.

• For further details on wiring of these units, see the

diagrams pasted inside each unit.

Indoor
Unit

Outdoor
Unit

Indoor
Unit

Outdoor
Unit

Power

220-240V/1Ph/50Hz

Supply 208-230V/1Ph/60Hz

Unit size

7

9

12

18

25

Power supply

mm

2

3x2.5

3x4

Interconnection Cooling mm

2

3x2.5 + Ground

(Indoor/Outdoor) Heating mm

2

4x2.5 + Ground

Fuse (slow-Blow)

A

10

16

20

Indoor
Unit

Cooling Only Units

24 V FROM OUTDOOR UNIT

Power Supply

Power

220-240V/1Ph/50Hz

Supply 208-230V/1Ph/60Hz

03_MHC/BOH 07-25.p65

18/3/02, 16:31

12

Summary of Contents for BOC-07

Page 1: ...035T80000 000 MODELS MHC MHH BOC BOH 07 MHC MHH BOC BOH 09 MHC MHH BOC BOH 12 MHC MHH BOC BOH 18 MHC MHH BOC BOH 25 Installation Manual MINISPLIT HIGH WALL AIR CONDITIONER Installation Manual...

Page 2: ...tion Quality POLICY We will continuously strive to satisfy our customers with consistent reliability in product service and support CONTENTS Safety Precautions 4 Part List 5 Preparation Before Install...

Page 3: ...ifold Guage 10 Gas leak detector 11 Vaccum pump 12 Pipe clamp 13 Pipe Cutter 14 Flare Tool Set 15 Electrical Circuit tester EXTENDED PARTS 1 Refrigerant Pipe Models MHC MHH BOC BOH 07 09 12 18 25 Liqu...

Page 4: ...y for possible damage Before undertaking any work on the unit make sure that the power supply has been disconnected CAUTIONS FOR INSTALLATION Do not install in a place where flammable gas may leak It...

Page 5: ...Included with indoor unit 3 Central mounting bracket 4 Not supplied Screws and Anchor Set 5 Remote Control and Battaries Set 6 Installation and Owner s manual 7 Quantity X1 X1 X1 X1 X4 X1 X1 T E M P M...

Page 6: ...cables are needed use the terminal block SELECTION OF THE LOCATION Select a place which provides the space around the units as shown in the diagram below Models MHC MHH BOC BOH 07 09 12 18 25 A 60cm 6...

Page 7: ...re is an obstacle near the air inlet or outlet Installation of the indoor unit at too low a position Installation of outdoor units too close or blowing discharged air into each other Installation of t...

Page 8: ...Gas side piping Liquid side piping Additional drain hose Connecting cable Vinyl tape Apply after carrying out a drainage test To carry out the drainage test remove the air filters and pour water into...

Page 9: ...ing the sharp edge of the mounting plate Wiring This indoor unit is ready for connection to the outdoor unit Cautions Never modify the unit by removing any of the safety guards or by bypassing any of...

Page 10: ...ting plate Make sure that the unit is correctly hung in place by sliding it to the left then to the right Press the bottom left and bottom right hand corners of the unit against the mounting plate unt...

Page 11: ...Notes Connect the pipe correctly Do not apply the excessive torque Use an appropriate bending tool to form curves and avoid over tightening the refrigerant tubes To prevent heat loss the two lines mus...

Page 12: ...re inner insulator of power supply cables and do not deform or smash on the surface of cables Electrical Connections All electrical wiring and connections must comply with local codes and standards Po...

Page 13: ...e of the protection modes are listed below Mode Operation Protection Controlled conditions from remedy Cooling Low outdoor Indoor coil Stop outdoor fan and and Dry temperature freezing up Compressor w...

Page 14: ...the compressor will not start C There is insufficient heating or cooling D The compressor run continuously E The compressor starts but shuts down quickly F Clicking sound is heard from the air condit...

Page 15: ...3 8 3 8 H mm 290 290 290 315 356 Indoor W mm 799 799 799 1 019 1 019 Dimensions D mm 181 181 181 180 180 H mm 492 492 492 590 696 Outdoor W mm 764 764 764 820 850 D mm 230 230 230 280 287 Weights Ind...

Page 16: ...460 3 60 1 1 1 1 1 3 1 1 3 1 3 3 Reciprocating Scroll Recip R 22 Models Power Supply Compressor Refrigerant Type Outdoor Unit V Ph Hz Ph H DB H DA 012 018 024 030 036 048 060 076 220 240 1 50 380 3 5...

Page 17: ...26 5 Rotary Recip R 22 208 230 1 60 1 1 1 1 1 2x0 85 0 85x1 20 2x1 20 2x1 73 2x2 26 2x4 5 4 5x5 7 2x5 7 16 9 26 5 Rotary Recip R 22 Models Power Supply Power Consumption Running Current Compressor Re...

Page 18: ...18 HIGH WALL...

Page 19: ...HIGH WALL 19...

Page 20: ...each system of the unit into a suitable container using a refrigerant reclaim or recovery unit This refrigerant may then be re used if appropriate or returned to the manufacturer for disposal Under N...

Reviews: