0
14 - Pulley adjustment and belt tensing
1.- Adjusting pulley
- Loosen the belts. Loosen tensing screw "A".
- Loosen studs "B" to release mobile rims "C".
- Turn both rims, on the thread of the fixed core of the pulley,
in the adequate direction to increase or decrease pulley
aperture.
Attention:
Both channels must have the same clearance
(the same number of opening turns).
- Tighten studs to a maximum, coinciding with their seat in
the fixed hub core of the pulley.
2.- Belt tensing
- Tense with tensing screw "A".
- If no belt strain gauge is available, use the following practi-
cal method:
- Apply a pressure of 5 kg on the midpoint of the belt, and
perpendicular to same.
- With this pressure, the belt should move from 12 to
14 mm.
.- It is recommendable to check belt tension twice during
the first 24 operating hours.
Caution:
Disconnect all power supply to the unit before
carrying out any of these operations.
F=5 Kg
12 - 1
4 mm
B
STUDS
A
TENSING
SCREW
D
.P
.
FULLY CLOSED POSITION
(OR TURNS), MAX. Ø D.P.
D
.P
.
THE MORE OPENING TURNS,
THE LESS Ø D.P.
FIXED CORE
C
B
(X4)
B
(X4)
C
MOBILE RIM
Summary of Contents for B4IH-360
Page 2: ......
Page 43: ...43 20 Wiring diagrams 20 1 Cool only models D4IC 360 D4IC 360G50 400 3 50 1 of 3...
Page 44: ...44 D4IC 360G50 400 3 50 2 of 3...
Page 45: ...45 D4IC 360G50 400 3 50 3 of 3...
Page 46: ...46 20 2 Cool only models D4IC 480 D4IC 480G50 400 3 50 1 of 3...
Page 47: ...47 D4IC 480G50 400 3 50 2 of 3...
Page 48: ...48 D4IC 480G50 400 3 50 3 of 3...
Page 49: ...49 20 3 Heat pump models B4IH 360 400 3 50 1 of 3...
Page 50: ...50 B4IH 360 400 3 50 2 of 3...
Page 51: ...51 B4IH 360 400 3 50 3 of 3...
Page 52: ...52 20 4 Heat pump models B4IH 480 400 3 50 1 of 3...
Page 53: ...53 B4IH 480 400 3 50 2 of 3...
Page 54: ...54 B4IH 480 400 3 50 3 of 3...
Page 55: ...55 20 5 Cool only gas heating models D4IG 360 400 3 50 1 of 4...
Page 56: ...56 D4IG 360 400 3 50 2 of 4...
Page 57: ...57 D4IG 360 400 3 50 3 of 4...
Page 58: ...58 D4IG 360 400 3 50 4 of 4...
Page 59: ...59 20 5 Cool only gas heating models D4IG 480 400 3 50 1 of 4...
Page 60: ...60 D4IG 480 400 3 50 2 of 4...
Page 61: ...61 D4IG 480 400 3 50 3 of 4...
Page 62: ...62 D4IG 480 400 3 50 4 of 4...
Page 63: ...63 Configuration of switches Data and dimensions are subject to change without prior notice...
Page 64: ...www johnsoncontrols com...