GENERAL DESCRIPTION

Units shall be factory--assembled, single packaged Heat
Pumps, designed for outdoor mounted installation. Units shall
have minimum SEER ratings of 10.0. They shall have built in
field convertible duct connections for down discharge
supply/return or horizontal discharge supply/return, and be
available with factory installed options or field installed
accessories.

The units shall be factory wired, piped, charged with R--22
refrigerant and factory tested prior to shipment. All unit wiring
shall be both numbered and color coded. Enclosed in each unit
shall be a factory test log sheet consisting of the unit tested
pressures, temperatures and amps, as tested prior to
shipment.

All units shall be manufactured in a facility certified to ISO 9001
standards, and the cooling & heating performance shall be
rated in accordance with DOE and ARI test procedures. Units
shall be listed under UL 1995/CAN/CSA No. 236--M90
conditions.

UNIT CABINET

1. Unit cabinet shall be constructed of G90 galvanized

steel, with exterior surfaces coated with a non--chalking,
powered paint finish, certified at 750 hours salt spray test
per ASTM--B117 standards.

2. Indoor blower section shall be insulated with up to 1"

thick insulation, coated on the air side. Aluminum foil
faced insulation shall be used in the furnace compart-
ment and be fastened with ridged fasteners to prevent in-
sulation from entering the air stream.

3. Cabinet panels shall be “large” size, easily removable for

servicing and maintenance.

4. Full perimeter base rails shall be provided to assure reli-

able transit of equipment, overhead rigging, fork truck ac-
cess and proper sealing on roof curb applications.

5. Disposable 1" filters shall be furnished and be accessible

through a removable access door, sealed air tight. Units
filter track shall be designed to accommodate either 1" or
2" filters.

6. Fan performance measuring ports shall be provided on

the outside of the cabinet to allow accurate air measure-
ments of evaporator fan performance without removing
panels or creating air by--pass of the coils.

7. Units vertical discharge and return duct configuration

shall be designed to fit between standard 24" O.C.
beams without modification to building structure, duct
work and base unit.

8. Condensate pan shall be internally sloped and conform

to ASHARE 62--89 self--draining standards. Condensate
connection shall be a minimum of 3/4" I.D. female and be
a ridged mount connection.

INDOOR (SUPPLY) FAN ASSEMBLY

1. Fan shall be direct drive, multi--speed, or a factory in-

stalled belt drive, adjustable--pitch motor pulley option.
Job site selected (BHP) brake horse power shall not ex-
ceed the motors nameplate horse power rating, plus the
service factor. Units shall be designed not to operate
above service factor.

2. Fan wheel shall be double--inlet type with forward--

curved blades, dynamically balanced to operate
smoothly throughout the entire range of operation.
Airflow design shall be constant air volume.

3. Bearings shall be sealed and permanently lubricated for

longer life and no maintenance.

OUTDOOR FAN ASSEMBLY

1. The outdoor fan shall be of the direct--driven propeller

type, discharge air vertically, have aluminum blades
riveted to corrosion resistant steel spider bracket and
shall be dynamically balanced for smooth operation.

2. The outdoor fan motor shall be totally enclosed with

permanently lubricated bearings and internally protected
against overload conditions.

REFRIGERANT COMPONENTS

1. Compressors:

A. Shall be fully hermetic type, direct drive, internally pro-

tected with internal high--pressure relief and over tem-
perature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or --
10% of the unit nameplate voltage.

B. Shall have internal isolation and sound muffling to mini-

mize vibration and noise, and be externally isolated on
a dedicated, independent mounting.

2. Coils:

A. Evaporator and condenser coils shall have aluminum

plate fins mechanically bonded to seamless internally--
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.

B. Evaporator and Condenser coils shall be of the direct

expansion, draw--thru design.

3. Refrigerant Circuit and Refrigerant Safety Components

shall include:

A. Independent fixed--orifice expansion devices.

B. Filter drier/strainer to eliminate any moisture or foreign

matter.

C. Accessible service gage connections on both suction

and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.

D. The refrigeration system shall provide at least 15° F of

liquid sub--cooling at design conditions.

E. Unit shall have a suction line accumulator.

4. Unit Controls:

A. Unit shall be complete with self contained low--voltage

control circuit protected by a resetable circuit breaker
fuse on the 24 volt transformer side.

B. Unit shall incorporate a lock--out circuit which provides

reset capability at the space thermostat or base unit,
should any of the following standard safety devices trip
and shut off compressor:

036-21564-002-A-0404

20

Unitary Products Group

MECHANICAL SPECIFICATIONS

Summary of Contents for B3CH 036

Page 1: ...DESIGN Both the side and bottom duct openings are covered when they leave the factory If a side supply side return is desired you simply remove the two side duct covers from the outside of the unit an...

Page 2: ...ompressor compartment so the access cover can be removed for troubleshooting without affecting the normal system operating pressures AIR FILTERS Units come standard with 1 throwaway filters The unit f...

Page 3: ...eaters available as accessories all with single point power supply SEER Seasonal Energy Efficiency Ratio the total cooling output in BTU s during a normal annual usage period for cooling divided by th...

Page 4: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 1750 72 44 4 0 31 27 24 20 16 42 4 2 30 26 23 19 15 67 40...

Page 5: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2000 72 51 4 9 40 35 29 24 49 5 2 39 34 29 23 67 46 4 7 42...

Page 6: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2500 72 64 6 0 51 44 38 31 60 6 9 50 43 37 30 67 59 5 9 51...

Page 7: ...0 4 6 5 2 70 MBH 11 8 16 6 21 6 27 1 34 9 42 8 51 7 59 2 KW 3 5 3 6 3 8 3 8 4 0 4 2 4 8 5 4 80 MBH 10 9 15 3 19 9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 0 4 0 4 1 4 4 5 0 5 7 1600 55 MBH 12 1 17 0 22 0...

Page 8: ...NDOOR COIL AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MODEL BCH AIR FLOW CFM Available External Static...

Page 9: ...AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MOTOR AND DRIVE DATA Belt Drive Blower MODEL BLOWER RANGE R...

Page 10: ...PROTECTION REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH THE WIRING AND OVERCURRENT PROTECTION 2 3 4 TO REMOTE SENSOR 2TH04702224 IF USED 2 1 24 volt thermostat with subbase 2TH1170022...

Page 11: ...76 6 53 8 63 7 77 7 101 6 125 5 60 70 80 110 150 60 70 80 110 150 230 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 4 4 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 57...

Page 12: ...2 1 1 2 10 2 15 3 20 4 24 9 30 7 37 1 25 30 40 25 30 40 060 208 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 2CE04503006 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3 5...

Page 13: ...6 58 0 67 9 81 9 105 8 129 7 70 80 90 110 150 70 80 90 110 150 230 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 8 6 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 61 7 7...

Page 14: ...2 1 1 2 10 2 15 3 20 4 24 2 30 5 36 9 25 35 40 25 35 40 060 208 1 60 2CE04500525 2CE04500725 2CE04501025 2CE04501525 2CE04502025 2CE04503025 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3...

Page 15: ...made from wood or class A B or C roof covering material 2 Units must be installed oudoors Overhanging structures or shrubs should not obstruct outdoor air discharge outlet HOLE KNOCKOUT SIZE DIA USED...

Page 16: ...gain ac cess to the bottom supply air knockout panel 2 Remove and discard the bottom knockout panel 3 Replace the side duct cover 4 With filter section access panel removed from the unit remove and di...

Page 17: ...Y CORNER CORNER CORNER OPTIONS ACCESSORIES Electric Heat Nominal KW 5 7 KW 18 10 15 KW 23 20 30 KW 28 Economizer 50 Motorized Outdoor Air Damper 26 Barometric Relief Fixed Outdoor Air Intake Damper 10...

Page 18: ...ge conditions It contains a 12 5 OHM PTCR temperature resistor with a support clip and hardware for mounting ANTI RECYCLE TIMER A timer to prevent the unit compressor from short cycling It assures 5 m...

Page 19: ...PLICATIONS TYPICAL ROOF TOP INSTALLATION ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION FIELD SUPPLIED DISCONNECT SWITCH TO POWER SUPPLY CONTROL WIRING TO INDOOR THERMOSTAT...

Page 20: ...all be direct drive multi speed or a factory in stalled belt drive adjustable pitch motor pulley option Job site selected BHP brake horse power shall not ex ceed the motors nameplate horse power ratin...

Page 21: ...utdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi tioned space during normal operation During econo mizer operation a mixed a...

Page 22: ...me between compressor cycles 8 ELECTRIC HEAT Slide in design provides single point power and ranges from 5 to 30 KW OTHER FACTORY INSTALLED OPTIONS 1 HIGH PERFORMANCE BELT DRIVE MOTOR 2 TECHNICOAT PHE...

Page 23: ...036 21564 002 A 0404 Unitary Products Group 23...

Page 24: ...Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A 035 21564 002 A 0404 Copyright 2004 by York International Corporation All Rights Reserved Supersedes 036...

Reviews: