FIELD--INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER --
Includes a slide--in/plug--in damper assembly with fully
modulating spring return motor actuator capable of introducing
up to 100% outdoor air, one outdoor air electronic enthalpy
sensor and a rainhood with filters. The rainhood is painted to
match the basic unit and must be field--assembled before
installation. Economizer dampers are 2% low leakage type.

DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER --
Includes the same damper system and rainhood with filters as
described for a single enthalpy economizer above except this
accessory contains two enthalpy sensors. It uses a differential
enthalpy control that compares the outdoor air versus the
return air. The logic module then optimizes the economizer
operation for additional savings over the single input
economizer.

MOTORIZED AIR DAMPER -- Includes a slid--in/plug--in
damper assembly with a rainhood and filters. The outdoor air
dampers open when the indoor fan motor is energized. The
damper is capable of providing 0% through 100% of outdoor
return air opening.

MANUAL OUTDOOR DAMPER -- Provides 0% through 35%
or 0% through 100% of return air opening (field adjustable).
Designed for duct mounted side or bottom supply/return
applications. Includes rain hood assembly and filter.

ELECTRIC HEATERS -- Include nickel chromium elements, a
terminal block, fuses (where required by UL), all the necessary
connectors and hardware. All heaters utilize single point power
supply hookup. Capacities from 5 KW thru 30 KW heating are
available.

FUSE BLOCK KITS -- These kits have a fuse box with a fuse
block and fuses. They're available for all 460--3--60 volt
heaters and 208/230--3--60 volt heaters 7 KW and smaller.

ROOF CURB -- This 14" high full perimeter roof curb is
knocked down for field assembly and contains duct supports
that can easily be shifted for the desired unit duct arrangement.
No deck is required because the unit underside is insulated.

START ASSIST KIT (Standard on 4 ton units) -- Provides
increased starting torque for 3 and 5 ton single phase units in
areas with low voltage conditions. It contains a 12.5 OHM
PTCR temperature resistor with a support clip and hardware
for mounting.

ANTI--RECYCLE TIMER -- A timer to prevent the unit
compressor from short cycling. It assures 5 minutes off time
between compressor cycles.

OUTDOOR COIL GUARD -- Consists of grille--type sections
for assembling over the outdoor coil to protect it from damage.

WALL THERMOSTAT -- The units are designed to operate
with 24--volt electronic and electro--mechanical thermostats.
All units can operate with single stage heat/single stage cool
thermostats -- with or without the economizer. To obtain
maximum economizer operating savings, a two stage cooling
thermostat should be used. To obtain two stage cooling
operation, a jumper wire must be removed on the low voltage
relay board. (See unit wiring diagram.)

OUTDOOR THERMOSTAT -- A 24--volt thermostat providing
two stages of control for units equipped with supplemental
electric heaters.

036-21564-002-A-0404

18

Unitary Products Group

FACTORY INSTALLED OPTIONS

ECONOMIZERS - Units equipped with the factory-installed
economizer option have dampers that are positioned by a
spring return, fully modulating damper actuator capable of
introducing up to 100% outdoor air. As the outdoor air intake
dampers open, the return air dampers close. The changeover
from mechanical refrigeration to economizer operation is
determined by a single input electronic enthalpy control or by a
dual input electronic enthalpy control. Simultaneous
compressor and economizer operation is also possible.

The single enthalpy system contains a sensor that monitors the
outdoor air which automatically operates the damper actuator
allowing the dampers to open or close.

The dual enthalpy system contains a second sensor that
monitors the return air in addition to monitoring the outdoor air
described above for a single enthalpy system. The logic module
compares these two values and modulates the dampers
providing the maximum efficiency of the economizer system.

The economizer is completely installed and wired at the factory.
Only the outdoor air hood, including its filters, need be
assembled and installed in the field.

BELT-DRIVE BLOWERS - Adjustable belt-drive blowers,
providing maximum flexibility to handle many airflow
requirements, are available on all models.

Summary of Contents for B3CH 036

Page 1: ...DESIGN Both the side and bottom duct openings are covered when they leave the factory If a side supply side return is desired you simply remove the two side duct covers from the outside of the unit an...

Page 2: ...ompressor compartment so the access cover can be removed for troubleshooting without affecting the normal system operating pressures AIR FILTERS Units come standard with 1 throwaway filters The unit f...

Page 3: ...eaters available as accessories all with single point power supply SEER Seasonal Energy Efficiency Ratio the total cooling output in BTU s during a normal annual usage period for cooling divided by th...

Page 4: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 1750 72 44 4 0 31 27 24 20 16 42 4 2 30 26 23 19 15 67 40...

Page 5: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2000 72 51 4 9 40 35 29 24 49 5 2 39 34 29 23 67 46 4 7 42...

Page 6: ...l Cap 1 MBH Power Input2 KW Sensible Capacity1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 2500 72 64 6 0 51 44 38 31 60 6 9 50 43 37 30 67 59 5 9 51...

Page 7: ...0 4 6 5 2 70 MBH 11 8 16 6 21 6 27 1 34 9 42 8 51 7 59 2 KW 3 5 3 6 3 8 3 8 4 0 4 2 4 8 5 4 80 MBH 10 9 15 3 19 9 24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 0 4 0 4 1 4 4 5 0 5 7 1600 55 MBH 12 1 17 0 22 0...

Page 8: ...NDOOR COIL AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MODEL BCH AIR FLOW CFM Available External Static...

Page 9: ...AND 1 FILTERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS MOTOR AND DRIVE DATA Belt Drive Blower MODEL BLOWER RANGE R...

Page 10: ...PROTECTION REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH THE WIRING AND OVERCURRENT PROTECTION 2 3 4 TO REMOTE SENSOR 2TH04702224 IF USED 2 1 24 volt thermostat with subbase 2TH1170022...

Page 11: ...76 6 53 8 63 7 77 7 101 6 125 5 60 70 80 110 150 60 70 80 110 150 230 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 4 4 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 57...

Page 12: ...2 1 1 2 10 2 15 3 20 4 24 9 30 7 37 1 25 30 40 25 30 40 060 208 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 2CE04503006 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3 5...

Page 13: ...6 58 0 67 9 81 9 105 8 129 7 70 80 90 110 150 70 80 90 110 150 230 1 60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 8 6 5 3 7 5 10 6 15 9 21 2 1 1 1 2 2 22 1 31 2 44 2 66 2 88 3 61 7 7...

Page 14: ...2 1 1 2 10 2 15 3 20 4 24 2 30 5 36 9 25 35 40 25 35 40 060 208 1 60 2CE04500525 2CE04500725 2CE04501025 2CE04501525 2CE04502025 2CE04503025 8 6 4 0 5 6 8 0 11 9 15 9 22 2 1 1 1 2 2 2 19 1 27 1 38 3...

Page 15: ...made from wood or class A B or C roof covering material 2 Units must be installed oudoors Overhanging structures or shrubs should not obstruct outdoor air discharge outlet HOLE KNOCKOUT SIZE DIA USED...

Page 16: ...gain ac cess to the bottom supply air knockout panel 2 Remove and discard the bottom knockout panel 3 Replace the side duct cover 4 With filter section access panel removed from the unit remove and di...

Page 17: ...Y CORNER CORNER CORNER OPTIONS ACCESSORIES Electric Heat Nominal KW 5 7 KW 18 10 15 KW 23 20 30 KW 28 Economizer 50 Motorized Outdoor Air Damper 26 Barometric Relief Fixed Outdoor Air Intake Damper 10...

Page 18: ...ge conditions It contains a 12 5 OHM PTCR temperature resistor with a support clip and hardware for mounting ANTI RECYCLE TIMER A timer to prevent the unit compressor from short cycling It assures 5 m...

Page 19: ...PLICATIONS TYPICAL ROOF TOP INSTALLATION ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION FIELD SUPPLIED DISCONNECT SWITCH TO POWER SUPPLY CONTROL WIRING TO INDOOR THERMOSTAT...

Page 20: ...all be direct drive multi speed or a factory in stalled belt drive adjustable pitch motor pulley option Job site selected BHP brake horse power shall not ex ceed the motors nameplate horse power ratin...

Page 21: ...utdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi tioned space during normal operation During econo mizer operation a mixed a...

Page 22: ...me between compressor cycles 8 ELECTRIC HEAT Slide in design provides single point power and ranges from 5 to 30 KW OTHER FACTORY INSTALLED OPTIONS 1 HIGH PERFORMANCE BELT DRIVE MOTOR 2 TECHNICOAT PHE...

Page 23: ...036 21564 002 A 0404 Unitary Products Group 23...

Page 24: ...Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A 035 21564 002 A 0404 Copyright 2004 by York International Corporation All Rights Reserved Supersedes 036...

Reviews: