background image

DEFROST SEQUENCE OF OPERATION

These heat pumps have a unique “ambient modified” time-
temperature defrost control that automatically adjusts to
changes in the outdoor temperature. The defrost control
shortens the defrost initiation time periods above 2°C (35°F)
and extends the defrost initiation time periods below 2°C (35°F.
The control is factory set to defrost at 110 minutes (T3), but it
can be field adjusted to defrost at 80 minutes (T2) or 50 minutes
(T1) in areas with high humidity.

The curve in Figure 10 shows how defrost initiation times are
automatically compensated for changes in outdoor
temperature.

EXAMPLE: If the timer is factory set on pin T3 (110 minutes at
2°C (35°F) outdoor) and the outdoor temperature climbs to 7°C
(45°F), the time initiation cycle decreases to 100 minutes.

If the outdoor temperature drops to -12°C (10°F) where ice is
less likely to form, the 110 minute interval increses to 150
minutes.

Two requirements must be met before a defrost cycle can be
initiated.

1. The defrost time cycle must be complete.

2. The liquid line temperature must be less than -2°C (28°F).

Defrost terminates when the liquid line sensor reaches 13°C
(55°F) or after 10 minutes. If one or both circuits defrosts,
electric heat is energized.

The defrost time cycle restarts 10 minutes after the start of the
defrost cycle even though the liquid sensor terminated defrost
after three minutes.

During troubleshooting, the defrost time can be reduced to 20
seconds by shorting out the SW1 test pegs on the module. The
pegs are 13mm (

1

2

in.) long, 5mm (

3

16

in.) apart and are

mounted on a white base. See Figure 11.

LOCKOUT CONTROL

Any one of four conditions put the system into a lock-out
condition during the heating or cooling mode:

1. The discharge line temperature reaches 124°C (255°F)

(102°C reset [215°F]) or,

2. The discharge pressure reaches 2,786 kPa (398 psig)

(2,170 kPa reset [310 psig]) or,

3. The suction line freezestat equals -3°C (26°F) (3°C reset

[38°F]), or

4. The low-pressure cut-out equals 49 kPa (7 psig) (154 kPa

[22 psig]).

A lock-out energizes the emergency heat light on the
thermostat and the red LED light on the unit relay board.
Turning the thermostat switch to “off”, then back to “on” will
reset the system.

NOTICE TO OWNER:

If a lockout occurs, check for the following problems before
calling a serviceman:

1. Dirty filters.

2. Snow accumulation.

3. Leaf or debris blockage.

After eliminating the problem, attempt to restart the system as
follows:

turn the system switch on the thermostat to its “OFF”
position for 10 seconds.

turn it back to its original position.

If the unit doesn't start, call a service man.

NOTE: Models with an anti-cycle accessory have a five

minute delay before restarting.

035-18895-000-A-0902

14

Unitary Products Group

FIG. 10 - DEFROST INITIATION TIMES

-23

(-10)

-17

(0)

-12

(10)

-7

(20)

-1

(30)

5

(40)

10

(50)

16

(60)

°

C (

°

F)

Summary of Contents for B2CH180

Page 1: ...esign installation operation and service of this equipment is available in the following reference documents 55 70 N7 General Installation 55 70 N2 Pre start Post start Check List 44 320 10 Barometric...

Page 2: ...4 Supply Air Blower Performance 10 5 Static Resistances 11 6 Blower Motor and Drive Data 11 7 Electrical Data Basic Units 11 8 Electrical Data Units w Elec Heat 11 9 Heat Anticipator Setpoints 13 10 B...

Page 3: ...ST be used across the top of the unit Refer to Figure 1 Units may also be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used LENGTH OF FORKS MUST BE A...

Page 4: ...ccess panel per the instructions above to en sure moisture is not drawn into the unit during op eration The covering over the mounting holes only need be removed Do not remove the opening cover CONDEN...

Page 5: ...ired with a separate branch circuit fed directly from the meter panel and properly fused CAUTION When connecting electrical power and control wir ing to the unit waterproof type connectors MUST BE USE...

Page 6: ...ENTHALPY SETPOINT ADJUSTMENT Remove the economizer access panel from the unit to check the following adjustments Loosen but do not remove the two panel latches CAUTION Extreme care must be exercised...

Page 7: ...15 FAN MOTOR kW HP 3 0 4 INDOOR COIL ROWS DEEP 4 FINS PER INCH 13 FACE AREA m2 Ft 2 1 45 15 5 OUTDOOR FANS Two Per Unit PROPELLER DIA mm in 762 30 ea FAN MOTOR kW HP 0 7 1 ea NOMINAL AIRFLOW m3 s 2 8...

Page 8: ...0 0 Above Unit 1829 72 With 914 36 Maximum Horizontal Overhang For Outdoor Air Discharge NOTE Unit and ductwork are approved for zero clearance to combustible materials when equipped with electric hea...

Page 9: ...s 1 Remove and discard the side supply and return air duct covers 2 Connect ductwork to duct flanges on the rear of the unit For downflow duct applications 1 Remove the side supply and return air duct...

Page 10: ...N AIRFLOW 3750 CFM 4380 CFM 5000 CFM 5630 CFM 6250 CFM ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW ESP iwg Output bhp Input kW 845 6...

Page 11: ...FRAME SIZE EFF PITCH DIA mm in BORE mm in DESIG NATION PITCH DIA mm in BORE mm in DESIG NA TION PITCH LENGTH mm in DESIG NATION QTY 180 845 1040 3 0 4 0 184T 83 109 135 4 3 5 3 29 1 1 8 1VP56 188 7 4...

Page 12: ...nt supply air temperature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energizes compressor 1 outdoor fan motor 1 and outdoor fan motor 2 if the ambien...

Page 13: ...e the two dot plugs from the blower motor and the fil ter access panels shown in Figure 7 2 Insert at least 200mm 8 of tubing approximately 6mm 1 4 diameter into each of these holes for sufficient pen...

Page 14: ...defrost cycle even though the liquid sensor terminated defrost after three minutes During troubleshooting the defrost time can be reduced to 20 seconds by shorting out the SW1 test pegs on the module...

Page 15: ...ccur if the bearings are overlubri cated Use grease sparingly WARNING Perform all maintenance operations on the blower motor with power disconnected from the unit Do not attempt to lubricate bearings...

Page 16: ...035 18895 000 A 0902 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2002 All Rights Reserved...

Reviews: