background image

269425-UUM-A-0407

Unitary Products Group

7

TROUBLESHOOTING

The following visual checks should be made before troubleshooting:

1.

Check to see that the power to the furnace and the ignition control
module is ON.

2.

The manual shut-off valves in the gas line to the furnace must be
open.

3.

Make sure all wiring connections are secure.

4.

Review the sequence of operation. Start the system by setting the
thermostat above the room temperature. Observe the system’s
response. Then use the troubleshooting section in this manual to
check the system’s operation.

FURNACE CONTROL DIAGNOSTICS

The furnace has built-in, self-diagnostic capability. If a system problem
occurs, a blinking LED shows a fault code. The LED can flash red,
green or amber to indicate various conditions. It is located behind a
clear view port in the blower compartment door.

The control continuously monitors its own operation and the operation
of the system. If a failure occurs, the LED will indicate the failure code. If
the failure is internal to the control, the light will stay on continuously. In
this case, the entire control should be replaced, as the control is not
field repairable.

Flash sequence codes 1 through 11 are as follows: LED will turn “on”
for 1/4 second and “off” for 1/4 second. This pattern will be repeated the
number of times equal to the code. For example, six “on” flashes equals
a number 6 fault code. All flash code sequences are broken by a 2 sec-
ond “off” period.

SLOW GREEN FLASH: 

Normal operation.

SLOW AMBER FLASH:

 Normal operation with call for heat.

RAPID RED FLASH:

 Twinning error, incorrect 24V phasing. Check

twinning wiring.

RAPID AMBER FLASH:

 Flame sense current is below 1.5 microamps.

Check and clean flame sensor. Check for proper gas flow. Verify that
current is greater than 1.5 microamps at flame current test pad.

4

 

AMBER FLASHES: 

The control board is recieving a “Y” signal from

the thermostat without a “G” signal, indicating improper thermostat wir-
ing.

1 RED FLASH:

 This indicates that flame was sensed when there was

not a call for heat. With this fault code the control will turn on both the
inducer motor and supply air blower. A gas valve that leaks through or
is slow closing would typically cause this fault.

2 RED FLASHES:

 This indicates that the normally open pressure

switch contacts are stuck in the closed position. The control confirms
these contacts are open at the beginning of each heat cycle. This would
indicate a faulty pressure switch or miswiring.

3 RED FLASHES:

 This indicates the normally open pressure switch

contact did not close after the inducer was energized. This could be
caused by a number of problems: faulty inducer, blocked vent pipe, bro-
ken pressure switch hose or faulty pressure switch.

4 RED FLASHES:

 This indicates that a primary or auxiliary limit switch

has opened its normally closed contacts. With this fault code the control
will operate the supply air blower and inducer. This condition may be
caused by: dirty filter, improperly sized duct system, incorrect blower
speed setting, incorrect firing rate or faulty blower motor.

5 RED FLASHES:

 This fault is indicated if the normally closed contacts

in the rollout switch opens. The rollout control is manually reset. If it has
opened, check for proper combustion air, proper inducer operation, and
primary heat exchanger failure or burner problem. Be sure to reset the
switch and cycle power (24 VAC) to the control after correcting the fail-
ure condition.

6 RED FLASHES:

 This indicates that after the unit was operating, the

pressure switch opened 4 times during the call for heat. If the main
blower is in a “Delay on” mode, it will complete it, and any subsequent
delay off period. The furnace will lock out for one hour and then restart.

7 RED FLASHES:

 This fault code indicates that the flame could not be

established. This no-light condition occurred 3 times (2 retries) during
the call for heat before locking out. Low gas pressure, faulty gas valve,
dirty or faulty flame sensor, faulty hot surface ignitor or burner problem
may cause this. The furnace will lock out for one hour and then restart.

8 RED FLASHES:

 This fault is indicated if the flame is lost 5 times (4

recycles) during the heating cycle. This could be caused by low gas
pressure, dirty or faulty flame sensor or faulty gas valve. The furnace
will lock out for one hour and then restart.

9 RED FLASHES:

 Indicates reversed line voltage polarity or grounding

problem. Both heating and cooling operations will be affected. Check
polarity at furnace and branch. Check furnace grounding. Check that
flame probe is not shorted to chassis.

10 RED FLASHES:

 Gas flow with no call for heat. Check gas valve and

gas valve wiring.

11 RED FLASHES:

 This indicates that a primary or auxiliary limit switch

has opened its normally-closed contacts and has remained open for
more than five minutes. This condition is usually caused by a failed
blower motor or blower wheel. Cycle power (24 VAC) to the control to
reset the hard lockout condition after correcting the failure condition.

12 RED FLASHES:

 This code indicates an open igniter circuit, which

could be caused by a disconnected or loose wire or by a cracked or bro-
ken igniter.

STEADY ON RED: 

Control failure. Replace control board.

60-MINUTE AUTOMATIC RESET FROM LOCKOUT:

 This control

includes a “watchdog” type circuit that will reset from a lockout condition
after 60 minutes. Operational faults 6,7,8 will be reset. This provides
protection to an unoccupied structure if a temporary condition exists
causing a furnace malfunction. An example would be a low incoming
gas supply pressure preventing unit operation. When the gas pressure
is restored, at some point the “watchdog” would restart the unit and pro-
vide heat for the house.

NOTE: 

If a flame is detected the control flashes the LED for 1/8 of a

second and then enters a flame stabilization period.

Never bypass any safety control to allow furnace opera-
tion. To do so will allow furnace to operate under poten-
tially hazardous conditions.
Do not try to repair controls. Replace defective controls
with UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.

IGNITION CONTROL

Normal flame sense current is approximately

3.7 microamps DC (µa)

Low flame signal warning starts at 1.5 microamps.

Low flame signal control lockout point is

0.1 microamps DC (µa)

Summary of Contents for AHS8 UH Series

Page 1: ...ystem parts electrical parts that have been wet or the furnace if deemed necessary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or prop erty...

Page 2: ...nate outside the space containing the furnace 4 Examine the furnace casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physicall...

Page 3: ...TOP Read the safety information above 2 Set the thermostat to the lowest setting 3 Turn off all electric power to the appliance 4 Remove furnace door 5 Move gas control switch to the OFF position Do n...

Page 4: ...s with the same size new filter s Throw away filter s may be replaced with cleanable filter s at this time Cleanable filter s may be cleaned as described in the manufacturer instructions or as descri...

Page 5: ...g the burner assembly to the vestibule panel and remove this assembly Handle the assembly carefully since it contains the igniter which is fragile and easily broken The lower portion of the heat excha...

Page 6: ...y jumper located on the control board See Figure 8 The heating cycle is complete and ready for the start of the next heating cycle If the flame is not detected within 7 seconds of the gas valve openin...

Page 7: ...wer motor 5 RED FLASHES This fault is indicated if the normally closed contacts in the rollout switch opens The rollout control is manually reset If it has opened check for proper combustion air prope...

Page 8: ...retrieve the error codes push the LAST ERROR button The LED on the control will then flash the error codes that are in memory starting with the most recent There will be a two second pause between eac...

Page 9: ...MBH 1SR0302 SIDE RETURN FILTER KIT 1 FILTER ALL MODELS 1SR0200 SIDE RETURN FILTER KIT 1 4 FILTER ALL MODELS 1BR0114 BOTTOM RETURN FILTER KIT 1 FILTER 14 1 2 CABINETS 1BR0214 BOTTOM RETURN FILTER KIT 1...

Page 10: ...E BURNER Natural 45 38 PLATE RESTRICTOR 39 COLLAR FLUE 40 LO NOX SCREEN L Models Only MISCELLANEOUS 41 42 SIGHT GLASS OVAL 43 GASKET RESTRICTOR PLATE 44 TUBING SILICONE 45 SHIELD INDUCER 46 WIRING DIA...

Page 11: ...269425 UUM A 0407 Unitary Products Group 11 SECTION IV WIRING DIAGRAM FIGURE 9 Wiring Diagram...

Page 12: ...ts installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or servicing 3 Damage...

Reviews: