background image

255029-YTG-C-0506

4

Unitary Products Group

ACCESSORIES

Refer to Price Manual for specific model numbers.

TXV Kits

 - TXV kits are available for “Flex-coil” applications

and  converting  R22  to  R410A  or  as  a  service  replacement.
All kits are bolt-on and require no brazing to install.

Non-Combustible Bases

 - A combustible floor base acces-

sory is available, if required by local codes, when the air han-
dler  is  installed,  in  the  downflow  position,  on  a  combustible
material.

Electric  Heaters -

 4HK  models shown under electrical data

include  sequential  operation  and  temperature  dual  limit
switches for safe, efficient operation. Circuit breakers are pro-
vided where shown.

External  Insulating  Wrap  Kit  -

  Provides  a  vinyl  covered

thermal  insulation  wrap,  providing  additional  thermal  insula-
tion  protection  to  prevent  sweating  in  applications  where
extreme high humidity is present. Air Handler cover (or wrap)
has Velcro edges for easy installation and access.

LIMITATIONS

These  units  must  be  wired  and  installed  in  accordance  with
all national and local safety codes.

Voltage limits are as follows: 

Airflow  must  be  within  the  minimum  and  maximum  limits
approved for electric heat, evaporator coils and outdoor units.

Air Handler Voltage

Voltage code

1

Normal  Operating 

Voltage Range

1. Rated in accordance with ARI Standard 110, utilization range “A”.

208/230-1-60

06

187-253

220/240-1-50

93

198-264

Entering Air Temperature Limits

Wet Bulb Temp.°F

Dry Bulb Temp. °F

Min.

Max.

Min.

Max.

57

72

65

95

Air Flow Data - 60 Hz Models

Models

Blower

Motor

Speed

208 Volt

CFM

@ External Static Pressure - IWC

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

AHP18B**(N,H)21

High

1142

1096

1053

997

925

828

721

210

N/A

N/A

Medium

677

652

634

615

572

486

295

120

N/A

N/A

Low

442

427

395

361

289

209

114

N/A

N/A

N/A

AHP24B**(N,H)21

High

1084

1038

985

935

856

762

665

602

484

333

Medium

840

807

767

693

610

550

485

387

323

221

Low

654

614

548

483

420

349

302

218

179

130

AHP30B**(N,H)21

High

1244

1184

1138

1079

1004

903

841

674

580

457

Medium

956

913

868

815

748

663

574

487

384

N/A

Low

941

904

862

806

731

643

566

480

361

226

AHP36C**(N,H)21

High

1719

1650

1572

1482

1386

1273

1108

925

785

644

Medium

1119

1097

1062

1019

935

827

743

637

479

337

Low

929

910

877

825

760

685

616

508

372

221

AHP42C**(N,H)21

High

1719

1650

1572

1482

1386

1273

1108

925

785

644

Medium

1119

1097

1062

1019

935

827

743

637

479

337

Low

929

910

877

825

760

685

616

508

372

221

AHP48D**(N,H)21

SHP48D**N21

High

1941

1818

1675

1532

1269

870

703

362

146

N/A

Medium

1594

1474

1409

1260

1021

802

524

215

144

N/A

Low

1241

1204

1128

1014

819

659

385

165

N/A

N/A

AHP60D**(N,H)21

SHP60D**N21

High / #5

2126

2093

2074

2048

1991

1941

1801

1569

1461

1366

Medium High / 

#4

1863

1842

1804

1800

1758

1730

1662

1503

1383

1306

Medium / #3

1642

1603

1593

1568

1523

1471

1410

1334

1307

1216

Medium Low / 

#2

1482

1468

1427

1370

1324

1274

1233

1196

1153

1099

Low / #1

1268

1220

1169

1118

1070

1037

982.5

949.1

891.9

831

1. Includes return air filter and coil.

Summary of Contents for AHP18 THRU 60

Page 1: ...ltimate refrigerant control required for today s high efficient product The UPG bolt on TXV provides the added flexibility to convert the air handler to the required refrigerant The UPG TXV is a true bolt on which does not require brazing to replace or install MicroBlueTM Coated Fins All air handler coils are treated with the MicroBlueTM hydrophilic coating to enhance the removal of condensate dur...

Page 2: ... 8 20 29 32 21 19 32 7 8 AHP60D N H 21 57 24 5 22 1 8 20 29 32 21 19 32 7 8 SHP60D N21 52 24 5 17 1 8 20 29 32 21 19 32 7 8 1 Actual size Conduit size COIL TECHNICAL DATA Model Application Refrig Conn Types Face Area Sq Ft Rows Deep Fin Per In Coil Size Tube Geometry Tube Dia Fin Type TXV AHP18B3X N H 21 Cooling Heat Pump Sweat 3 40 2 14 2 14 x 17 5 1 x 0 866 3 8 Enhanced None AHP18B2A N H 21 3 40...

Page 3: ... 16 5 13 8 10 8 AHP30B2A N H 21 1050 85 72 31 1 28 3 25 3 22 1 80 67 27 1 24 3 21 4 18 4 75 62 21 8 19 0 18 0 14 4 70 57 18 1 16 1 14 0 11 8 AHP36C2A N H 21 1200 85 72 41 6 37 8 33 8 29 8 80 67 33 3 29 4 25 8 21 9 75 62 26 0 21 9 23 9 17 8 70 57 22 3 20 6 19 0 17 8 AHP42C2C N H 21 1400 85 72 88 4 76 0 63 3 50 0 80 67 70 8 59 4 48 4 37 0 75 62 55 2 43 9 35 8 29 9 70 57 47 4 41 5 35 8 29 9 AHP48D2C ...

Page 4: ...64 Entering Air Temperature Limits Wet Bulb Temp F Dry Bulb Temp F Min Max Min Max 57 72 65 95 Air Flow Data 60 Hz Models Models Blower Motor Speed 208 Volt CFM1 External Static Pressure IWC 0 10 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 AHP18B N H 21 High 1142 1096 1053 997 925 828 721 210 N A N A Medium 677 652 634 615 572 486 295 120 N A N A Low 442 427 395 361 289 209 114 N A N A N A AHP24B...

Page 5: ...0 1284 1255 1207 1146 1075 988 846 729 572 Low 1146 1119 1090 1038 992 972 841 725 617 496 AHP42C N H 21 High 1883 1764 1657 1543 1435 1327 1210 902 714 527 Medium 1625 1510 1429 1339 1256 1172 1038 765 609 412 Low 1260 1225 1179 1110 1047 973 785 638 500 340 AHP48D N H 21 SHP48D N21 High 2029 1944 1837 1743 1643 1537 1435 1320 1064 789 Medium 1805 1730 1649 1566 1479 1385 1286 1147 851 683 Low 14...

Page 6: ... HP 1 HP Nominal RPM 1075 1075 1050 Voltage 230 Amps Full Load 230 3 8 3 8 7 6 Filter1 Type DISPOSABLE OR PERMANENT Size 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 Permanent Type Kit 1PF0602BK 1PF0603BK 1PF0603BK Shipping Operating Weight lbs AHP N1 and SHP N21 164 158 186 175 189 178 Shipping Operating Weight lbs AHP H1 167 161 190 179 193 182 1 Field Supplied Electrical Data Cooling Only 60 Hz Models T...

Page 7: ...Hi 13 2 17 6 45 1 60 1 3 3 4 4 6 6 8 8 13 2 17 6 AHP42C N H 21 4HK 6500506 0 5 Lo 3 6 4 8 12 3 16 4 3 6 4 8 3 6 4 8 3 6 4 8 4HK 6500806 0 5 Med 5 6 7 5 19 2 25 6 2 8 3 75 2 8 7 5 5 6 7 5 4HK 6501006 0 5 Med 7 2 9 6 24 6 32 8 3 6 4 8 7 2 9 6 7 2 9 6 4HK16501506 0 5 Med 10 8 14 4 36 9 49 1 3 6 4 8 7 2 9 6 10 8 14 4 4HK16501806 0 5 Hi 13 2 17 6 45 1 60 1 3 3 4 4 6 6 8 8 13 2 17 6 AHP48D N H 21 SHP48D...

Page 8: ...37 98 43 63 40 45 8 8 4HK 6501006 40 0 47 46 54 50 50 60 8 6 4HK16501506 60 0 69 13 79 50 70 90 4 3 4HK16501806 73 3 83 57 96 13 90 100 4 3 AHP42C N H 21 4HK 6500506 20 0 25 92 29 75 30 30 8 8 4HK 6500806 31 3 38 10 43 88 40 45 8 8 4HK 6501006 40 0 47 58 54 75 50 60 6 6 4HK16501506 60 0 69 25 79 75 70 90 4 3 4HK16501806 73 3 83 69 96 38 90 100 3 3 AHP48D N H 21 SHP48D N21 4HK 6500506 20 0 25 92 29...

Page 9: ...230 3 60 Models Heater Model Max Static Min CFM Total Heat1 kW Staging kW MBH W1 Only W2 Only W1 W2 Static Tap 208 240 208 240 208 240 208 240 208 240 AHP24B N H 21 4HK06501025 Data not available for this release Check for latest revision of this document or Air Handler Installation Instructions Documents available on line www upgnet com AHP30B N H 21 4HK06501025 AHP36C N H 21 4HK06501025 4HK06501...

Page 10: ...n humidity rise 3 Remove HUM STAT Jumper on AH Control Board 4 For heat pump applications set MODE jumper on air handler control board to the HP position 5 To change quantity of heat during HP defrost cycle Reverse connections at W1 and W2 on Air Handler Control Board AH SERIES Air Handler Control Wiring Typical A C Cooling only Applications THERMOSTAT AIR HANDLER BOARD 1 STAGE AIR CONDITIONING R ...

Page 11: ...255029 YTG C 0506 Unitary Products Group 11 TYPICAL APPLICATIONS UPFLOW DOWNFLOW HORIZONTAL RIGHT HORIZONTAL LEFT ...

Page 12: ...o change without notice Printed in U S A 255029 YTG C 0506 Copyright by York International Corp 2006 All rights reserved Supersedes 255029 YTG B 0506 Unitary 5005 Norman Products York OK Group Drive 73069 NOTES ...

Reviews: