Johnson Controls Unitary Products
7
697887-YTG-H-0514
AHE60D
6HK(0,1)6500206
10.0
18.3
20.0
20
20
12
12
6HK(0,1)6500506
20.0
29.2
32.5
30
35
10
8
6HK(0,1)6500806
32.0
42.2
47.5
45
50
8
8
6HK(0,1)6501006
40.0
50.8
57.5
60
60
6
6
6HK(1,2)6501306
52.0
63.8
72.5
70
80
6
4
6HK(1,2)6501506
60.0
72.5
82.5
80
90
4
4
6HK(1,2)6501806
72.0
85.5
97.5
90
100
3
3
6HK(1,2)6502006
80.0
94.2
107.5
100
110
3
2
6HK(1,2)6502506
100.0
115.8
132.5
125
150
1
1/0
1. (0,1) - maybe 0 (no circuit breaker) or 1 (with circuit breaker).
2. (1,2) maybe 1 (with circuit breaker, no breaker jumper bar) or 2 (with circuit breaker & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
4. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60 (Continued)
Air Handler Models
Heater
Models
1,2
Heater
Amps
@240V
Field Wiring
Min. Circuit Ampacity
MOP.
3
Min Wire Size (AWG)
4
208V
230V
208V
230V
208V
230V
ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60
Air
Handlers
Models
Heater
Models
Total
Heater
Amps
@240V
Min. Circuit Ampacity
MOP
1
Min. Wire Size (AWG)
2
208V
230V
208V
230V
208V
230V
Circuit
Circuit
Circuit
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
1st
3
2nd
3rd
AHE22B
AHE24B
AHE30B
6HK16501306
52.0
22.2 37.6
–
24.6 43.3
–
25
40
–
25
45
–
10
8
–
10
8
–
6HK16501506
60.0
25.1 43.3
–
27.9 50.0
–
30
45
–
30
50
–
10
8
–
10
8
–
AHE34C
AHE36C
AHE42D
6HK16501306
52.0
23.3 37.6
–
25.7 43.3
–
25
40
–
30
45
–
10
8
–
10
8
–
6HK16501506
60.0
26.2 43.3
–
29.0 50.0
–
30
45
–
30
50
–
10
8
–
10
8
–
6HK16501806
72.0
43.5 39.0
–
49.0 45.0
–
45
40
–
50
45
–
8
8
–
8
8
–
6HK16502006
80.0
47.8 43.3
–
54.0 50.0
–
50
45
–
60
50
–
8
8
–
6
8
–
AHE48D
6HK16501306
52.0
25.4 37.6
–
27.8 43.3
–
30
40
–
30
45
–
10
8
–
10
8
–
6HK16501506
60.0
28.3 43.3
–
31.1 50.0
–
30
45
–
35
50
–
10
8
–
8
8
–
6HK16501806
72.0
45.6 39.0
–
51.1 45.0
–
50
40
–
60
45
–
8
8
–
6
8
–
6HK16502006
80.0
49.9 43.3
–
56.1 50.0
–
50
45
–
60
50
–
8
8
–
6
8
–
AHE60D
6HK16501306
52.0
25.4 37.6
–
27.8 43.3
–
30
40
–
30
45
–
10
8
–
10
8
–
6HK16501506
60.0
28.3 43.3
–
31.1 50.0
–
30
45
–
35
50
–
10
8
–
8
8
–
6HK16501806
72.0
45.6 39.0
–
51.1 45.0
–
50
40
–
60
45
–
8
8
–
6
8
–
6HK16502006
80.0
49.9 43.3
–
56.1 50.0
–
50
45
–
60
50
–
8
8
–
6
8
–
6HK16502506
100.0
49.9 43.3 21.7 56.1 50.0 25.0
50
45
25
60
50
25
8
8
10
6
8
10
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
2. Stated sizes are for 75°C, copper wire only. If wire other than non-plated, 75°C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
3. 1st Circuit includes the blower motor amps.