350154-YTG-B-0408
2
Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change without
notice. Certified dimensions will be provided upon request.
Physical and Electrical Data
MODEL
CZH02411
CZH03611
CZH04811
CZH06011
Unit Supply Voltage
208-230V, 1
φ,
60Hz
Normal Voltage Range
1
187 to 252
Minimum
Circuit
Ampacity
15.6 23.6 29.2 34.8
Max. Overcurrent Device Amps
2
25 40 50 60
Min. Overcurrent Device Amps
3
20 25 30 35
Multi-stage
Compressor
Yes Yes Yes Yes
Compressor
Type
Scroll Scroll Scroll Scroll
Compressor Amps
Rated
Load
10.3 16.7 21.2 25.6
Locked
Rotor
52 82 96 118
Crankcase
Heater
No No No No
Fan Motor Amps
Rated Load
2.8
2.8
2.8
2.8
Fan
Diameter
Inches
24 24 24 24
Fan Motor
Rated
HP
1/3 1/3 1/3 1/3
Nominal
RPM
685 685 685 685
Nominal
CFM
2900 3200 3100 3150
Coil
Face Area Sq. Ft.
23.58
23.58
23.58
23.58
Rows
Deep
2 2 2 2
Fins
/
Inch
16 16 14 14
Liquid Line Set OD (Field Installed)
3/8
3/8
3/8
3/8
Vapor Line Set OD (Field Installed)
3/4
3/4
7/8
7/8
Unit Charge (Lbs. - Oz.)
4
15 - 1
13 - 7
12 - 9
13 - 5
Charge
Per
Foot,
Oz.
0.62 0.62 0.67 0.67
Operating
Weight
Lbs.
305 305 310 330
1
Rated in accordance with ARI Standard 110, utilization range “A”.
2
Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3
Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4
The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
VAPOR
LIQUID
2-3/8
3-1/8
6-1/2
C
A
B
Unit
Model
Dimensions
(Inches)
Refrigerant
Connection
Service Valve Size
A
B
C
Liquid
Vapor
24
39-1/2 42 34
3/8”
3/4”
36 39-1/2 42 34
48
39-1/2 42 34
7/8”
60 39-1/2 42 34