Air filters
All units have standard filters with metal frame and average filtering of 48 mm available in zig-zag. Gravi‐

metric efficiency is 90%, G4, complying with EN779 and fire resistance is F1 in accordance with DIN

53438.
Optionally, high opacimetric efficiency filters, classes F6 and F7 are available according to EN779. These

filters are easily installed behind the standard filters.

Cooling circuit
The Rooftop ACTIVA units have 1 cooling circuit equipped with 2 compressors placed in tandem. This

makes for better performance when the unit is not running at full capacity, which is usually the case. It

also improves unit operations at extreme temperatures, as it does not jam and continues operating at

partial capacity, using the entire surface of the exchangers.
Based on the accumulated operating hours of each compressor, a control circuit determines the order

of operation, thus lengthening their working life.

Compressors
Vertical hermetic scroll-type compressor, with internal motor protection and standard outside case re‐

sistance.
The compressors have dampers to reduce operating noise and vibrations.

Cooling circuit protection
All cooling circuits are supplied as standard with high and low-pressure switches, dehydrator filter on the

liquid line, discharge temperature cut-out switch, liquid sight glasses and temperature sensors for supply

air, suction liquid and outdoor air.

Service connections
In order to make the connections with a minimum amount of work, electrical and control cables can be

pulled into the unit at the side or through the base.

Electrical panel
The unit's electrical panel meets EN60204-1 and EN60439-1 standards. The main switch with a drive

lever is a standard component on all units. The electric motors are protected with specific thermal mag‐

netic switches and motor protection relays.
The unit is fitted with a sequence and phase fault sensor: where a non R-S-T phase sequence is detected

or where, once the unit is running, there is a phase fault, the sensor will disconnect the power supply to

the main board of the unit, preventing it from starting.

YKN2 Open Control Circuit
This is a 24 V control circuit. It can operate with the optional DPC-1 thermostat (communication) as well

as a 24 V thermostat with control signals (Y1, G, O/B, W).
The YKtool system analyser can be used to simplify commissioning and placement and to solve any

installation or operational faults.

Gas Burner (RAG/RAD Units)
All of the models that operate with gas have the same two capacity control stages. The burner group

consists of an aluminised steel pipe exchanger, adjustable gas valve, electronic starter control, mechan‐

ical ventilation and all the safety controls necessary to satisfy EC standards.
The gas supply pipe is directed to the heating compartment through the front panel of the unit. The unit

provided is complete and ready to be hooked up to a natural gas connection at 20 mbar (2ND-H, G20).

By making certain adjustments, it can also be easily converted to use with the 2ND-L G25 natural gas

family. In addition, it is possible to adapt it to operate with LPG (Liquefied Petroleum Gas propane G31)

using a specific conversion kit for the adaptation.

User manual

1

General description of the unit

1.1

3

Summary of Contents for Activa Series

Page 1: ...ACTIVA SERIES ROOF TOP Air Conditioners User manual Ref N 40318_EN 0709...

Page 2: ...Thermostat connections to the control board 7 1 5 2 Thermostat connections 8 1 6 Safety and equipment protection systems 8 1 7 Placing the unit out of service for a planned stoppage or breakdown 9 1...

Page 3: ...1 User manual...

Page 4: ...eel plate The outdoor parts are treated with an oven polymerised polyester paint RAL9002 guaranteeing a quality finish that lasts for many years 800 H N S in compliance with DIN 50021 There are option...

Page 5: ...ulled into the unit at the side or through the base Electrical panel The unit s electrical panel meets EN60204 1 and EN60439 1 standards The main switch with a drive lever is a standard component on a...

Page 6: ...Roof Top ACTIVA series of units is exclusively designed for the air conditioning of buildings and properties The unit uses a cooling system heat pump gas burners and or electrical heat for support dep...

Page 7: ...erty users must under no circumstances inspect or adjust the unit themselves All of inspections or adjustments that may be made by the user are performed using the DPC 1 thermo stat If the air conditi...

Page 8: ...oling heat pump gas burner heating The ARG ARD models join an additional heating and air supply system to their respective cooling circuits In this case the air inbound to the building or property cir...

Page 9: ...ramme determines when to automatically start the air con ditioning unit The performance of the different unit components is also determined by the operating programme Refer to the documentation for th...

Page 10: ...djust the unit themselves All of inspections or adjustments that may be made by the user are performed using the DPC 1 thermostat The air conditioning unit is fitted with electrical protection systems...

Page 11: ...netic switch on the unit power supply must be disconnected CAUTION Always keep the electrical power supply connected to the unit Only disconnect the unit if it is not to be used for a long period of t...

Page 12: ...45 Fault in economiser or hot water coil outdoor supply water return sensor 46 Smoke detector high temperature or supply temperature 80 C 91 Ambient sensor open or short circuited 92 Internal sensor...

Page 13: ...with the unit To make them easier maintenance tasks have been grouped by time intervals in a series of tables Maintenance responsibilities of the user see on page 11 1 8 2 Maintenance responsibilities...

Page 14: ...nt law as an electrical and electronic device and therefore this product cannot be dealt with at the end of its working life as domestic or urban waste The product must be taken to collection points f...

Reviews: