FORM 160.52-O1
47
YORK INTERNA
TIONAL
TABLE 1 (Contd)
CAUSES OF NORMAL AND SAFETY SYSTEM SHUTDOWNS IN ACCORDANCE WITH THE MICROCOMPUTER
CONTROL, CENTER DISPLAY
SHUTDOWN CAUSE
GOVERNING CONTROL FUNCTION
CONTROL CENTER DISPLAY
OPERATING
PROGRAMMED
START-UP OF
PROBABLE CAUSE
DAY OF TIME OF
CAUSE OF
METHOD OF
DESCRIPTION
POINT
SETPOINTS
SYSTEM AFTER
AND SERVICE
WEEK
DAY
SHUTDOWN
RESTART
ON
ON
BY OPERATOR
SHUTDOWN
REQUIRED
RISE
FALL
MON.
10:00 AM
Oil Pressure
High Oil Press.
100PSID (689kPa)
59
Will start at 59
This Shutdown is provided
Transducer
Transducer
(During first 7 min.
PSID
PSID when compr.
to check on Oil Pressure
Error
of Compr. Oper.)
(406
switch is placed to
Transducers for failure in
60PSID (413kPa)
kPa)
STOP/RESET and
the high state. Replace
(After first 7 min.
then START
Oil Press. Transducer in
of Compr. Oper.)
oil sump or compressor
Vane Motor
Autostart
Vane Motor
Restart automatically Vanes are set improperly,
Switch Open
Switch
after Vane Motor arm reset vane linkage check
linkage is set pro-
vane positions using
perly. Press STOP/
the SERVICE key switch
RESET and then
and proper keys on the
START switch
MicroComputer Control
Center
MON.
10:00 AM
Starter
Motor Current >
Press compressor
Check motor starter
Malfunction
15% for 10 swc.
STOP/RESET
operation. Motor current
Detected
with Control Cen-
switch and then
value greater than 15%
ter not calling for
FLA
motor to run
MON.
10:00 AM
Program
Autostart
Micro Board
Watchdog timer circuit
Initiated
has reset software pro-
Reset
gram Chiller will
automatically restart.
Replace RTC
RTC-IC chip
Reprogram the Con- Weak battery
IC chip
trol Center Setponts
Replace RTC-IC chip
Reprogram
& proceed with
U16
Setpoints
Normal Start-up
MON.
10:00 AM
Low Oil
Autostart
Oil Temp.
71.0°F (21.6°C) 55°F
Press STOP/
Oil Temp. Thermistor
Temperature
Thermistor
(12.8
RESET switch &
disconnected from
(RT3)
°C)
then START
Analog Input Board.
switch
Reconnect or replace
open sensor.
MON.
10:00 AM
Faulty Dis-
Discharge Temp. 30.0°F (-1.1°C) 29.9°F
Press STOP/
Faulty Discharge Temp.
charge Temp.
Thermistor
(-1.2
START switch &
Thermistor (RT2) or dis-
Sensor
(RT2) discon-
°C)
then START
connected from Analog
nected or faulty
switch
Input Board. Connect or
operating temp.
replace open sensor.
= 32°F
MON.
10.00 AM
Low Line
SSS Logic
See legend on wiring
Chiller will automa-
Low AC Line Voltage
Voltage (SSS
Board
diagram
tically restart when
Units only)
all phases of line vol-
tage increase to the
minimum required
starting level.
MON.
10:00 AM
MTR Phase
SSS Logic
See Section 2
Press STOP/START
Motor Phase Current
Current
Board
switch then START
Unbalance
unbalance
switch
(SSS Units
only)