York 3 PH Installation Instruction Download Page 5

035-15806-004 Rev. A (1000)

Unitary Products Group

5

RE-ASSEMBLING, BRAZING AND CLEANING OF 
JOINT CONNECTIONS

Remove the Schrader Valve cores from the service valves.
Remove the plugs from the service valve field tubing connec-
tions. Clean the joints to be brazed.

NOTE:  

Do not overheat the connection to be brazed as this

can cause improper flow of solder, resulting in a weak and
leaking joint. Never apply heat directly to face of fitting. Do
not heat solder by direct contact with flame of the torch.

When brazing copper tubing it is very important to preheat
the entire joint before applying the solder. This is done by
sweeping the flame steadily and evenly around the fitting, to
bring both fitting and tubing up to equal temperature before
applying the solder.

Reassemble groups of tubing and fittings, brazing several
joints instead of one joint at a time. This reduces the chance
for error in the alignment of the assembly. Replace schrader
valve cores. DO NOT OPEN SERVICE VALVES AT THIS
TIME.

NOTE:  

Do not heat solder by direct contact with flame of the

torch.

Clean joint connection immediately after brazing with wet rag.

REFRIGERANT LINE SUPPORT

Refrigerant lines should be supported in a way that no dips or
sags occur. We recommend four feet between supports. If
refrigerant lines are to be attached to the home structure,
care should be taken to eliminate the transmission of vibra-
tions. Attach the refrigerant lines to the indoor coil first.
Remove plugs from the indoor coil, then clean joints to be
brazed. Braze refrigerant lines to the indoor coil. Attach refrig-
erant lines to the outdoor unit.

CHARGING AND LEAK TESTING

On systems with or without service valves the refrigerant
should be recovered or recycled in accordance with EPA reg-
ulations. In some cases this may require putting piercing
valves on both the high and low sides of the system. 

When recovering refrigerant from a system, with a burnout,
follow a safe procedure due to possible contamination. 

Contaminated refrigerant must be recovered and returned to
the local refrigeration supply house for proper disposition.

TOTAL LINE LENGTH

Units should be installed only with approved system combina-
tion (indoor/outdoor) as specified in the Technical Guide.

For systems with total line length exceeding 50 feet, see
APPLICATION DATA, 690.01-AD1V(1296) and worksheet
690.01-AD1.1V(791) “General Piping Recommendations and
Refrigerant Line Length" for vapor and liquid line sizing, cali-
bration of liquid line pressure loss or gain, determination of
vapor line velocity, elevation limitations, orifice connections,
system charging, traps, etc.

System with liquid line pressure loss or gain grater than 11
psi must be provided with corrected orifice size as noted in
Form 690.01 - AD1V (1296).

ORIFICE SELECTION

NOTE:  

The proper orifice must be installed in the indoor coil

liquid line connection prior to the connection of the refrigerant
lines.

Each coil has an orifice installed in the fitting between the liq-
uid line connection and distributor. The orifice is identified on
a label next to the liquid line connection.

The orifice shipped with the outdoor unit is based on the most
sold combination, but it may be changed, depending on the
capacity and efficiency of the outdoor unit, elevation differ-
ences, and/or long total line lengths. An additional orifice(s) is
shipped with most outdoor units for the most commonly
required replacement combinations. Other sizes must be
ordered from Source 1 Parts if required.

See the appropriate Tabular Data Sheet for the correct orifice
size and charge adder. If the orifice size matches, nothing fur-
ther is required and the refrigerant lines may be connected
per the outdoor unit instruction. However, if another orifice
should be used, see the coil instruction for details to change
the orifice in the coil.

When using hard solder, an inert gas such as dry
nitrogen must be introduced and permitted to flow
through tubing during brazing to displace air and
prevent oxidation.

DO NOT vent refrigerant to the outdoors.

Avoid getting the refrigerant in the eyes or on the
skin.

The indoor coil is under 35 psig (inert gas) pressure.

Summary of Contents for 3 PH

Page 1: ...NIT 4 INDOOR UNITS 4 REFRIGERANT LINE 4 INSULATION OF VAPOR LINE 4 RE ASSEMBLING BRAZING AND CLEANING OF JOINT CONNECTIONS 5 REFRIGERANT LINE SUPPORT 5 CHARGING AND LEAK TESTING 5 TOTAL LINE LENGTH 5...

Page 2: ...any additional external static pressure The maximum and minimum conditions for operation must be observed to assure a system that will give maximum perfor mance with minimum service Check Electrical...

Page 3: ...ences standing off from the coil can reduce capacity loss due to wind chill effect Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches...

Page 4: ...istance and fewest number of bends Determine the path that the refrigerant lines will follow Starting at either the indoor coil or the outdoor unit refrigerant line connections carefully measure cut d...

Page 5: ...tamination Contaminated refrigerant must be recovered and returned to the local refrigeration supply house for proper disposition TOTAL LINE LENGTH Units should be installed only with approved system...

Page 6: ...t include a disconnect switch located within sight of the outdoor unit 2 Use the correct size fuse or circuit breaker as listed on the unit rating plate and data sheet See Tabular Data Sheet for minim...

Page 7: ...3 or 4 2 Using wire nuts connect the low voltage wiring as shown in Figure 5 6 or 7 3 A minimum of 18 AWG wire gauge for total lengths not exceeding 130 feet must be used in connecting the low voltage...

Page 8: ...TACTOR 1 TERMINALS GND LUG R B Y O W R Y G AIR HANDLER TERMINAL BLOCK 4TB TYPICAL THERMOSTAT ALL OUTDOOR WIRING MUST BE WEATHERPROOF USE COPPER CONDUCTORS ONLY X 53 G 60 66 JUNCTION BOX RED BRN YEL OR...

Page 9: ...see that nothing was over looked Have all braze joints on refrigerant lines been leaked checked Have base valves been opened Have all refrigerant lines been secured and iso lated properly Is the indo...

Page 10: ...035 15806 004 Rev A 1000 10 Unitary Products Group NOTES...

Page 11: ...035 15806 004 Rev A 1000 Unitary Products Group 11...

Page 12: ...without notice Printed in U S A 035 15806 004 Rev A 1000 Copyright by York International Corp 2000 All rights reserved Supersedes 035 15806 403 REV A 550 46 N2Y 499 Unitary 5005 Norman Product York OK...

Reviews: