background image

035-15806-004 Rev. A (1000)

2

Unitary Products Group

GENERAL INFORMATION

These outdoor units are designed to be connected to a
matching UPG indoor coil with sweat connection lines. These
units are factory charged with refrigerant for a matching
indoor coil plus 15 feet of field supplied line. The outside unit
is designed to be placed alongside or at the back of the
home, remote from the indoor coil. The outdoor unit has been
factory run-tested and all components of the system are
ready for easy, immediate installation.

INSPECTION

Check the unit thoroughly for shipping damage, Unusually
rough handling during shipment may loosen fan motors, com-
pressors, or other components. Be sure that the unit is ready
to operate before installing it. If there is damage, file a claim
with the shipper.

REFERENCE

Use this instruction in conjunction with the instructions for the
appropriate indoor unit, air moving system and accessories.

Installer should pay particular attention to the words NOTE,
CAUTION and WARNING.

NOTES are intended to clarify or make the installation easier.

CAUTIONS identify procedures which, if not followed care-
fully, could result in personal injury, property damage or
equipment damage.

WARNINGS are given to alert the installer that severe per-
sonal injury, death or equipment damage may result if instal-
lation procedures are not followed properly.

LIMITATIONS

The unit should be installed in accordance with all national
and local codes and regulations which govern the installation
of this type of equipment. In lieu of local codes, the equip-
ment should be installed in accordance with National Electric
Code, and in accordance with the recommendations made by
the National Board of Fire Underwriters.

Limitations for the indoor unit, coil and appropriate accesso-
ries must also be observed.

The outdoor unit must not be installed with any duct work in
the air stream. The outdoor fan is the propeller type and is not
designed to operate against any additional external static
pressure.

The maximum and minimum conditions for operation must be
observed to assure a system that will give maximum perfor-

mance with minimum service. 

Check Electrical Power Supply

The electrical power should be checked to determined if ade-
quate power is available, and near constant voltage can be
maintained. If there is any question concerning the power
supply, contact the local power company for corrections; oth-
erwise, unsatisfactory performance may result. 

Selecting the Best Condensing Unit Location

Several important factors must be considered before select-
ing the best site for the air conditioning outside unit:

Distance to indoor coil

Proximity to the structure

Proximity to vents and exhaust systems

Ability to service

Sound transmission

Air circulation

Wind direction

Relationship between structure, sun, and unit

Distance from power source

Water drainage

Local codes

Locate the outside unit near enough to the indoor coil vicinity
to eliminate lengthy refrigerant line runs. Do not locate the
outside unit so it discharges air under eaves or gutters. Rain
or snow melt-off should not be able to run off a roof and down
upon the unit. Be sure vents are not located upwind from the
outside unit.

A minimum clearance of 18 inches is required for service at
the control panel and compressor compartments access. A
10 inch clearance is required for the air inlet to the outdoor
coil around the perimeter of the unit. The air discharge of the
unit requires a 60 inch clearance between the top of the unit
and any obstruction. See Figure 1.

The manufacturer is not responsible for the perfor-
mance of a mismatched system. The outdoor unit
must be installed with a compatible indoor unit as
designated in the specification data or in the Direc-
tory of Certified Unitary Air Conditioners published
by the Air Conditioning and Refrigeration Institute.
Using unmatched components may not only affect
the performance of the system, but may also void
the warranty of the equipment. 

Table 1: APPLICATION LIMITATIONS

Ambient Air Temperature 

on Outdoor Coil

Air Temperature on

Indoor Coil

Min. °DB

Max. °DB

Min. °WB

Max. °WB

50

125

57

72

Summary of Contents for 3 PH

Page 1: ...NIT 4 INDOOR UNITS 4 REFRIGERANT LINE 4 INSULATION OF VAPOR LINE 4 RE ASSEMBLING BRAZING AND CLEANING OF JOINT CONNECTIONS 5 REFRIGERANT LINE SUPPORT 5 CHARGING AND LEAK TESTING 5 TOTAL LINE LENGTH 5...

Page 2: ...any additional external static pressure The maximum and minimum conditions for operation must be observed to assure a system that will give maximum perfor mance with minimum service Check Electrical...

Page 3: ...ences standing off from the coil can reduce capacity loss due to wind chill effect Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches...

Page 4: ...istance and fewest number of bends Determine the path that the refrigerant lines will follow Starting at either the indoor coil or the outdoor unit refrigerant line connections carefully measure cut d...

Page 5: ...tamination Contaminated refrigerant must be recovered and returned to the local refrigeration supply house for proper disposition TOTAL LINE LENGTH Units should be installed only with approved system...

Page 6: ...t include a disconnect switch located within sight of the outdoor unit 2 Use the correct size fuse or circuit breaker as listed on the unit rating plate and data sheet See Tabular Data Sheet for minim...

Page 7: ...3 or 4 2 Using wire nuts connect the low voltage wiring as shown in Figure 5 6 or 7 3 A minimum of 18 AWG wire gauge for total lengths not exceeding 130 feet must be used in connecting the low voltage...

Page 8: ...TACTOR 1 TERMINALS GND LUG R B Y O W R Y G AIR HANDLER TERMINAL BLOCK 4TB TYPICAL THERMOSTAT ALL OUTDOOR WIRING MUST BE WEATHERPROOF USE COPPER CONDUCTORS ONLY X 53 G 60 66 JUNCTION BOX RED BRN YEL OR...

Page 9: ...see that nothing was over looked Have all braze joints on refrigerant lines been leaked checked Have base valves been opened Have all refrigerant lines been secured and iso lated properly Is the indo...

Page 10: ...035 15806 004 Rev A 1000 10 Unitary Products Group NOTES...

Page 11: ...035 15806 004 Rev A 1000 Unitary Products Group 11...

Page 12: ...without notice Printed in U S A 035 15806 004 Rev A 1000 Copyright by York International Corp 2000 All rights reserved Supersedes 035 15806 403 REV A 550 46 N2Y 499 Unitary 5005 Norman Product York OK...

Reviews: