York 12 SEER Installation Manual Download Page 6

035-19946-001 Rev. B (0804)

6

Unitary Products Group

CFM SELECTION BOARD SETTINGS

For proper system operation the CFM Selection Board jumpers must be
set properly. 

Refer to the Tabular Data Sheet for the recommended air flow settings
for each size condensing unit.

Set the cooling speed per the instructions for the air handler or furnace
by selecting the correct COOL and ADJ taps. Verify the airflow using
the LED display on the CFM selection board.

The HUMIDISTAT jumper must also be removed if a dehumidistat is
installed.

 FIGURE 6:  

Typical Air Handler Thermostat Wiring

VARIABLE

SPEED

AIR HANDLER

AIR

CONDITIONER

C

Y

R

W

G

C

Y

R

O

CONTACTOR
COIL

CONTACTOR
COIL

Y1

W2

W1

G

HUM

Y2

X/L

X/L

1

2

1

HUMIDISTAT CONTACTS OPEN ON HUMIDITY RISE.
HUMIDISTAT JUMPER ON CFM SELECTION BOARD MUST BE REMOVED.

2

Y1, Y2, X/L, AND HUM LOCATED ON CFM SELECTION BOARD.

THERMOSTAT

 FIGURE 7:  

Typical Furnace Thermostat Wiring

1

VARIABLE

SPEED

FURNACE

C

Y

R

W

HUMIDISTAT CONTACTS OPEN ON HUMIDITY RISE.
HUMIDISTAT JUMPER ON CFM SELECTION BOARD
MUST BE REMOVED.

G

C

Y

R

O

Y1

W2

W1

G

HUM

Y2

X/L

1

THERMOSTAT

AIR

CONDITIONER

CONTACTOR
COIL

CONTACTOR
COIL

 FIGURE 8:  

Typical Field Wiring (Air Handler / Electrical Heat)

ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES

POWER WIRING

208/230-1-60

CONTACTOR
TERMINALS

COIL

GND.

LUG

C

Y

R

G

W

Y

R

G

W

POWER WIRING
CONTROL WIRING

FACTORY WIRING

24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)

FURNACE OR AIR HANDLER TERMINAL BLOCK

ROOM THERMOSTAT

CONDENSING UNIT

ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.

TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.

*

*

 FIGURE 9:  

CFM Selection Board

CFM SELECTION BOARD

TAP SELECTION

D
C
B
A

D
C
B
A

COOL

HEAT

ADJ

DELAY

REMOVE FOR

HEAT PUMP

HUMIDISTAT

Summary of Contents for 12 SEER

Page 1: ...ular attention to the signal words DANGER WARNING or CAUTION DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING indicates a potentia...

Page 2: ...ormed in order to insure proper sys tem operation and performance 1 Change out the indoor coil if required to an approved R 22 coil condensing unit combination with the appropriate metering device 2 I...

Page 3: ...periods of shutdown 6 Pack fiberglass insulation and a sealing material such as perma gum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility 7 See...

Page 4: ...just touches the chamfered retaining wall See Page 4 PRECAU TIONS DURING BRAZING SERVICE VALVE 13 Replace plunger cap finger tight then tighten an additional 1 12 turn 1 2 hex flat Cap must be replace...

Page 5: ...n the inside surface of the unit service access panel 3 Replace the corner cover and service access panel that were removed in Steps 2 and 4 of the Field Connections Power Wiring section 4 All field w...

Page 6: ...MUST BE REMOVED 2 Y1 Y2 X L AND HUM LOCATED ON CFM SELECTION BOARD THERMOSTAT FIGURE 7 Typical Furnace Thermostat Wiring 1 VARIABLE SPEED FURNACE C Y R W HUMIDISTAT CONTACTS OPEN ON HUMIDITY RISE HUMI...

Page 7: ...s avail able add refrigerant accordingly Check flare caps on service ports to be sure they are leak tight DO NOT OVERTIGHTEN between 40 and 60 inch lbs maximum Superheat Charging Method NOTE Use this...

Page 8: ...When applicable instruct the owner that the compressor is equipped with a crankcase heater to prevent the migration of refrigerant to the compressor during the OFF cycle The heater is energized only w...

Reviews: