York International N Series Installation Manual Download Page 5

103904-UIM-B-0505

Unitary Products Group

5

INDOOR UNIT PREPARATION

Prepare Air Handler for installation as follows:

1.

Attach coil casing to blower section in a way appropriate to indoor
unit application. See appropriate “BLOWER / COIL ASSEMBLY”
instructions for G2FD Coils.

2.

Confirm the metering device.

NOTE: If a humidistat accessory is installed with the system, a thermal

expansion valve kit must be installed on the indoor side.

NOTE: Instructions for installing accessories are included with the

accessories.

3.

Attach Filter Rack Accessory if applicable. The filter rack is
designed for use with G2FD coil or blower section in a downflow
configuration.

4.

For upflow and horizontal applications, insert filter in the filter com-
partment below the coil.

BLOWER / COIL ASSEMBLY UPFLOW AND 

HORIZONTAL INSTALLATIONS

NOTE: See coil instructions prior to assembly for drain pan installation

or baffle adjustment.

1.

Apply neoprene gasket to top of coil.

2.

Position blower casing over coil opening.

NOTE: Tie plate and screws are provided with all full-cased coils.

3.

Align the six holes provided and attach tie plate to back of casings
using screws provided. 

4.

Remove blower access panel.

5.

Fasten duct flanges of coil to duct flanges of air handler with
screws. See Figure 6.

6.

Secure toe plate of blower to top panel of coil using 2 screws pro-
vided. 

7.

See sections on electrical and blower speed connections.

8.

Re-position and replace access panel.

BLOWER / COIL ASSEMBLY DOWNFLOW 

INSTALLATION

1.

Position blower casing over duct connection and secure such that
the supply air end of the blower is down. 

2.

Apply neoprene gasket to return-air side of air handler. 

3.

Place coil casing over blower return opening.

4.

Align the six holes provided and attach tie plate to back of casings
using screws provided. 

NOTE: Tie plate and screws are included with all full cased coils.

5.

Remove blower access panel and coil filter door.

6.

Secure the two toe plates of the blower section and coil using pro-
vided holes and 2 screws. 

7.

See sections on electrical and blower speed connections.

8.

Re-position and replace access panel and filter door. 

ELECTRIC HEATERS & OPERATING CONTROLS

The low voltage transformer and the CFM board fan / heater control are
standard on all models. The air handlers are shipped pre-wired to oper-
ate as cooling only applications. To complete the installation for cooling
only, install a 6-pin jumper plug to the control board to bypass the
heater limit controls. This jumper plug is secured to the duct cover near
the 4-pin power plug harness. Failure to install the plug will cause the
blower to run continuously. See Figure 10.

Mark the unit nameplate with the appropriate heater selection on the
space provided or NONE to indicate cooling only. To operate these units
with electric heat, it is necessary to field install an electric heater kit
(2HK). See Electric Heater Accessory Installation instructions for proper
installation procedure. Prior to installing electric heat, it is necessary to
perform the following procedure:

1.

Remove the 4-pin power plug from the control board (See Figure
10).

NOTE: This pin must not be used when electric heaters are installed.

2.

Remove the four (4) screws from the duct cover and remove the
duct cover from the air handler.

Right-hand Airflow Application Only - Models with Circuit 
Breakers

If unit is to be installed for right hand air flow, the circuit breakers in the
heat kit will need to be removed and rotated 180°, so the OFF position
will be down when the cabinet is positioned on the right side. This is an
NEC requirement. Do One Set Of Breakers At A Time - to make sure
wires are reconnected properly
. Loosen terminal screws on the wires
and gently pull the wires back from the breaker.   Remove screws
securing the breaker plate and rotate 180°, then secure the breaker
plate and reconnect the wires to the breaker. Proper torque for terminal
screws is 35 in/lbs.

LOW VOLTAGE CONTROL CONNECTIONS

The 24 volt power supply is provided by an internally wired low voltage
transformer which is standard on all models. However, if the unit is con-
nected to a 208 volt power supply the low voltage transformer must be
rewired to the 208 volt tap. See the unit wiring label.

Field supplied low voltage wiring can exit the unit on the top right hand
corner or the right hand side panel (see Figure 4, item K).

Install the 7/8" plastic bushing supplied with the unit in the selected hole
and keep low voltage wiring as short as possible inside the control box.

The field wiring is to be connected at the screw terminals of the control
board (Refer to Figures 12, 13, 14, 15, 16, 17, 18, 19, and 20). 

Equipment should never be operated without filters.

 FIGURE 6:  Tie Plate & Fastening Tabs

TIE PLATE

COIL

AIR HANDLER

COIL

TOP PLATE

AIR HANDLER

DOWNFLOW

APPLICATION

UPFLOW & HORIZONTAL

APPLICATIONS

Blowers installed in a downflow application with an electric heater
kit must include a non-combustible floor base if installing on a com-
bustible floor. See instructions for 1FB0617, 1FB0621 and
1FB0624.

 FIGURE 7:  Electric Heaters in Horizontal Configuration

HEAT KIT
ASSEMBLY

REMOVE 3 SCREWS TO
REMOVE THE CIRCUIT
BREAKER BRACKET
FROM HEAT KIT
ASSEMBLY

JUMPER BAR

JUMPER BAR
COVER

FIELD SUPPLY WIRING
WILL BE ATTACHED TO
THIS SIDE OF THE
CIRCUIT BREAKER(S)

CIRCUIT BREAKER(S) -
THERE MAY BE ONE,
TWO OR THREE

CIRCUIT BREAKER
BRACKET

HEAT KIT WIRING WILL BE
ATTACHED TO THIS SIDE OF
THE CIRCUIT BREAKER(S)

AIR

FLOW

Summary of Contents for N Series

Page 1: ...ANCES 2 LOCATION 2 DUCT CONNECTIONS 4 SUSPENSION KITS 4 INDOOR UNIT PREPARATION 5 BLOWER COIL ASSEMBLY UPFLOW AND HORIZONTAL INSTALLATIONS 5 BLOWER COIL ASSEMBLY DOWNFLOW INSTALLATION 5 ELECTRIC HEATERS OPERATING CONTROLS 5 LOW VOLTAGE CONTROL CONNECTIONS 5 LINE POWER CONNECTIONS 6 BLOWER SPEED COMFORT SELECTION 6 WIRING DIAGRAMS 11 DRAIN CONNECTIONS 14 MAINTENANCE 14 COIL CLEANING 14 LUBRICATION ...

Page 2: ...ructions are required as a minimum for a safe installation GENERAL INFORMATION This Modular Air Handler provides the flexibility for installation in any upflow downflow or horizontal application These versatile models may be used with or without electric heat The variable speed ECM motors provide a selection of air volume to match any application The unit can be positioned for bottom return air in...

Page 3: ...en into consideration and provided for as follows a Refrigerant piping and connections are located in the front b Maintenance and servicing through the front or access side of unit with both sides and rear of unit having zero inch clear ance c Condensate drain lines are connected in the front clear of fil ter d Filter removal e When no electric heat is used the unit as well as all duct work and pl...

Page 4: ...charge opening sizes shown in Figure 4 Duct work should be fabricated and installed in accordance with local and or national codes This includes the standards of the National Fire Protection Association for Installation of Air Conditioning and Ventilat ing Systems NFPA No 90B SUSPENSION KITS A suspension kit is available Models 1BH0601 is designed specifically for the units contained in this instr...

Page 5: ...sly See Figure 10 Mark the unit nameplate with the appropriate heater selection on the space provided or NONE to indicate cooling only To operate these units with electric heat it is necessary to field install an electric heater kit 2HK See Electric Heater Accessory Installation instructions for proper installation procedure Prior to installing electric heat it is necessary to perform the followin...

Page 6: ...umpers on the CFM selection board as indicated in Table 2 To Set Heat Pump CFM The heat pump CFM setting is the same as the cooling CFM No addi tional CFM setting is required however you must remove the jumper at the bottom of the connector board labeled Remove for Heat Pump for heat pump operation See Figure 8 To Set Electric Heat CFM The blower speed required for the Electric Heat is different t...

Page 7: ...SINGLE SOURCE 2 5 25 KW 25 KW SHOWN 1 PHASE ELECTRIC HEAT WITH CIRCUIT BREAKER BREAKER BAR REMOVED MULTI SOURCE 15 25 KW 25 KW SHOWN TYPICAL WIRING WITHOUT ELECTRIC HEAT GND LUG POWER SUPPLY GND LUG GND LUG POWER SUPPLY GND LUG GND LUG POWER SUPPLY 1 GND LUG GND LUG POWER SUPPLY GND LUG POWER SUPPLY 2 POWER SUPPLY 3 GND LUG POWER SUPPLY GND LUG POWER WIRING 208 230 1 60 NOTE USE ONLY COPPER CONDUC...

Page 8: ...K 6500806B 0 5 1335 7 0 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0 11 3 15 0 2HK16502006B 15 0 20 0 51 2 68 3 3 8 5 0 7 5 10 0 15 0 20 0 2HK16502506B 18 8 25 0 64 2 85 3 3 8 5 0 11 3 15 0 18 8 25 0 2HK16503006A 22 5 30 0 76 8 102 4 7 5 10 0 15 0 20 0 22 5 30 0 1 Heat KW shown at 240V represen...

Page 9: ...55 2 60 8 60 70 6 4 2HK16501506B 62 5 78 0 86 9 80 90 4 3 2HK16502006B 83 3 100 3 112 9 110 125 2 1 2HK16502506B 104 2 123 1 139 0 125 150 1 1 0 2HK16503006A 125 0 145 3 165 0 150 175 1 0 2 0 1 Heat amps shown at 240V represents maximum heater rating 2 OCP Over current protection HACR type circuit breaker or time delay fuse TABLE 8 Electrical Data for Single Source Power Supply Copper Wire 208 230...

Page 10: ... 52 1 35 35 50 60 8 8 8 6 2HK16502006B 55 2 60 8 45 1 52 1 60 70 50 60 6 4 8 6 2HK16502506B 33 0 34 8 45 1 52 1 45 1 52 1 35 35 50 60 50 60 8 8 8 6 8 6 2HK16503006A 55 2 60 8 45 1 52 1 45 1 52 1 60 70 50 60 50 60 6 4 8 6 8 6 1 Heat amps shown at 240V represents maximum heater rating 2 OCP Over current protection HACR type circuit breaker or time delay fuse TABLE 10 Electrical Data for Multi source...

Page 11: ...y for SEER enhancement 1 Optional Dehumidification Humidistat contacts open on rise Remove Humidistat Jumper on CFM selection board Refer to CFM Selection Board Graphic Indicates convenience terminal Not functional in this application For Heat Pump Applications Remove Heat Pump Jumper on CFM selection board Refer to CFM Selection Board Graphic To change quantity of heat during HP defrost cycle Rev...

Page 12: ...t Jumper on CFM selection board Refer to CFM Selection Board Graphic Indicates convenience terminal Not functional in this application Y Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 Second Blower Off Delay for SEER enhancement 1 Optional Dehumidification Humidistat contacts open on rise Remove Humidistat Jumper on CFM selection board Refer to C...

Page 13: ...Humidistat Jumper on CFM selection board Refer to CFM Selection Board Graphic Indicates convenience terminal Not functional in this application For Heat Pump Applications Remove Heat Pump Jumper on CFM selection board Refer to CFM Selection Board Graphic To change quantity of heat during HP defrost cycle Reverse connections at W1 W2 on Air Handler Control Board FIGURE 20 Control Wiring N1VS New UP...

Page 14: ...to be cleaned or replaced it should be washed with Calgon coilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted sur faces LUBRICATION The bearings of the blower motor are permanently lubricated CONDENSATE DRAINS During the cooling season check the condens...

Page 15: ...103904 UIM B 0505 Unitary Products Group 15 NOTES ...

Page 16: ...to change without notice Printed in U S A 103904 UIM B 0505 Copyright by York International Corp 2005 All rights reserved Supersedes 103904 UIM A 1204 Unitary 5005 Norman Product York OK Group Drive 73069 NOTES ...

Reviews: