background image

157650-UIM-B-1105

2

Unitary Products Group

2.

The outdoor unit must not be installed with any duct work in the air
stream. The outdoor fan is the propeller type and is not designed
to operate against any additional external static pressure.

3.

The maximum and minimum conditions for operation must be
observed to assure a system that will give maximum performance
with minimum service.

4.

The maximum allowable line length for this product is 75 feet.

UNIT INSTALLATION

LOCATION

Before starting the installation, select and check the suitability of the
location for both the indoor and outdoor unit. Observe all limitations and
clearance requirements.

The outdoor unit must have sufficient clearance for air entrance to the
condenser coil, for air discharge, and for service access. See Figure 1.

NOTE: For multiple unit installations, units must be spaced a minimum
of 18 inches apart. (Coil face to coil face.)

If the unit is to be installed on a hot sun exposed roof or a black-topped
ground area, the unit should be raised sufficiently above the roof or
ground to avoid taking the accumulated layer of hot air into the outdoor
unit. 

Provide an adequate structural support.

GROUND INSTALLATION

The unit may be installed at ground level on a solid base that will not
shift or settle, causing strain on the refrigerant lines and possible leaks.
Maintain the clearances shown in Figure 1 and install the unit in a level
position.

Normal operating sound levels may be objectionable if the unit is placed
directly under windows of certain rooms (bedrooms, study, etc.).

Condensate will drain from beneath the coil of the outdoor unit during
the defrost cycle. Normally this condensate may be allowed to drain
directly on the ground.

Elevate the unit sufficiently to prevent any blockage of the air entrances
by snow in areas where there will be snow accumulation. Check the
local weather bureau for the expected snow accumulation in your area.

Isolate the unit from rain gutters to avoid any possible wash out of the
foundation.

UNIT PLACEMENT

1.

Provide a base in the pre-determined location.

2.

Remove the shipping carton and inspect for possible damage.

3.

Compressor tie-down bolts should remain tightened.

4.

Position the unit on the base provided.

NOTE: Heat pumps will defrost periodically resulting in water drainage.
The unit should not be located where water drainage may freeze and
create a hazardous condition - such as sidewalks and steps.

LIQUID LINE FILTER-DRIER

The heat pumps have a solid core bi-flow filter/drier located on the liquid
line.

NOTE: Replacements for the liquid line drier must be exactly the same
as marked on the original factory drier. See 
Source 1 for O.E.M.
replacement driers.

*As listed on the “Energy Guide yellow sticker on the unit.

AIR TEMPERATURE AT 

OUTDOOR COIL, °F

AIR TEMPERATURE AT

INDOOR COIL, °F

Min.

Max.

Min.

Max.

DB

Cool

DB 

Heat

DB

Cool

DB 

Heat

WB 

Cool

DB 

Heat

WB 

Cool

DB 

Heat

50

-10

115

75

57

50

1

1. Operation below this temperature is permissible for a short period of 

time, during morning warm-up.

72

80

 FIGURE 1:  Typical Installation with Required Clearances

MINIMUM 24” SERVICE ACCESS
CLEARANCE ON ONE SIDE

48” OVERHEAD
CLEARANCE

10” CLEARANCE
COIL AREA

WEATHERPROOF
DISCONNECT
SWITCH

THERMOSTAT

TO FURNACE OR
AIR HANDLER
TERMINAL BLOCK

NEC CLASS 1 WIRING

NEC CLASS 2 WIRING

TO INDOOR COIL

SEAL OPENING(S) WITH
PERMAGUM OR EQUIVALENT

CONTROL
ACCESS
PANEL

NOTE: ALL OUTDOOR WIRING

POSSIBLE OUTDOOR THERMOSTAT KIT LOCATIONS
(UNIT MOUNTING NOT AVAILABLE ON ALL MODELS)

The outdoor unit should not be installed in an area where mud or
ice could cause personal injury. Remember that condensate will
drip from the unit coil during heat and defrost cycles and that this
condensate will freeze when the temperature of the outdoor air is
below 32°F.

Failure to do so or using a substitute drier or a granular type may
result in damage to the equipment.

Filter-Drier

Source 1 Part No.

Apply with Models

13 SEER

19312 / 1458-001

024

20738 / 6536-334

030, 036, 042

Summary of Contents for ERHQ SERIES

Page 1: ...oderate injury It is also used to alert against unsafe practices and hazards involving only property dam age INSPECTION As soon as a unit is received it should be inspected for possible dam age during transit If damage is evident the extent of the damage should be noted on the carrier s delivery receipt A separate request for inspection by the carrier s agent should be made in writing See Local Di...

Page 2: ...or the expected snow accumulation in your area Isolate the unit from rain gutters to avoid any possible wash out of the foundation UNIT PLACEMENT 1 Provide a base in the pre determined location 2 Remove the shipping carton and inspect for possible damage 3 Compressor tie down bolts should remain tightened 4 Position the unit on the base provided NOTE Heat pumps will defrost periodically resulting ...

Page 3: ...s it is formed As the tubing becomes harder it is more susceptible to kinking and damage 3 Forming Copper a No attempt should be made to bend the suction line in a shorter radius than 12 See Figure 2 4 How to dispose of excess tubing a Tubing may be longer than required Coil excess tubing nearer the indoor coil rather than the outdoor unit b Excess tubing must be coiled horizontally so the flow of...

Page 4: ... using a wrench on the stationary fitting of the coupling while nut is being tightened Tighten the nut until the coupling bottoms out d Then tighten an additional 1 6 turn to complete the knife edge seal 10 Check for leaks a After the line set connections have been made they should be checked for leaks b If the valves were kept clean and lubricated per instruction no leaks should be found c Use le...

Page 5: ...drafts from outside doors or supply air grilles 6 Route the 24 volt control wiring NEC Class 2 from the outdoor unit to the indoor unit and thermostat NOTE To eliminate erratic operation seal the hole in the wall at the thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat NOTE A Start Assist Kit is available and recommended for long line set app...

Page 6: ...ON General The control maintains proper airflow through the outdoor coil during heating operation by melting frost and ice that may form on the coil Frost may accumulate unevenly in different sections of the coil because of the arrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal op...

Page 7: ...ost cycle is necessary The control will initiate a defrost cycle when the liquid line temperature is below the initiate point for the measured ambient temperature See Figure 10 continuously for 4 1 2 minutes This delay eliminates unnec essary defrost cycles caused by refrigeration surges such as those that occur at the start of a heating cycle The control will initiate a defrost cycle every 6 hour...

Page 8: ...conds the control will de energize the compressor but not cause a soft lockout condition If the control does not sense a second pressure switch opening before the six hour timer expires the timer and counter will be reset During the soft lockout mode the control will de energize the compres sor and energize the X L output with the appropriate flash code The control will reset the soft lockout cond...

Page 9: ... The outdoor fan motor is permanently lubricated and does not require periodic oiling 3 If the coil needs to be cleaned it should be washed with Calgon Coilclean mix one part Coilclean to seven parts water Allow solution to remain on coil for 30 minutes before rinsing with clean water Solution should not be permitted to come in contact with painted surfaces 4 Refer to the furnace or air handler in...

Page 10: ...157650 UIM B 1105 10 Unitary Products Group WIRING DIAGRAM FIGURE 12 Wiring Diagram ...

Page 11: ...157650 UIM B 1105 Unitary Products Group 11 NOTES ...

Page 12: ...ct to change without notice Printed in U S A 157650 UIM B 1105 Copyright by York International Corp 2005 All rights reserved Supersedes 157650 UIM A 0905 Unitary 5005 Norman Product York OK Group Drive 73069 ...

Reviews: