1055361-BTG-B-0913
Johnson Controls Unitary Products
5
ELECTRICAL DATA - COOLING ONLY
Models
Motor FLA
1
Minimum Circuit
Ampacity
MOP
2
Minimum Wire Size (AWG)
3
AHR18B / AHR24B
1.4
1.8
15
14
AHR22B
2.2
2.8
15
14
AHR29C/AHR34C
2.3
2.9
15
14
AHR30B / AHR36B /
AHR42C / AHR48D /
AHR60D
3.0
3.8
15
14
1. FLA = Full Load Amps
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
3. 75
C, copper wire only. If wire other than non-plated, 75
C ambient, copper wire is used, consult applicable tables of the NEC and local codes.
ELECTRICAL HEAT: MINIMUM FAN SPEED
Heater Kit Models
1,2
Nom. kW
@240V
Air Handler Models
AHR18B
AHR22B
AHR24B
AHR29C
AHR30B
AHR34C
AHR36B
AHR42C
AHR48D
AHR60D
6HK(0,1)6500206
2.4kW
Low
Med
Low
Med
Low
Med
Low
Low
Low
Low
6HK(0,1)6500506
4.8kW
Med
Med
Low
Med
Low
Med
Low
Low
Low
Low
6HK(0,1)6500806
7.7kW
Med
High
Med
High
Med
Med
Med
Med
Low
Low
6HK(0,1)6501006
6HK06501025
9.6kW
Med
High
High
High
Med
High
High
Med
Med
Med
6HK(1,2)6501306
12.5kW
–
High
High
High
High
High
High
High
Med
Med
6HK(1,2)6501506
6HK06501525
14.4kW
–
High
High
High
High
High
High
High
Med
Med
6HK(1,2)6501806
6HK06501825
17.3kW
–
–
–
–
–
–
High
–
Med
Med
6HK(1,2)6502006
6HK16502025
19.2kW
–
–
–
–
–
–
High
–
High
High
6HK(1,2)6502506
6HK16502525
24kW
–
–
–
–
–
–
–
–
–
High
1. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.
2. (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper bar.
ELECTRIC HEAT PERFORMANCE DATA: 208/230-1-60 & 208/230-3-60
Heater
Models
1,2
Nominal kW
@240V
Total Heat
3
kW Staging
kW
MBH
W1 Only
W1 + W2
208V
230V
208V
230V
208V
230V
208V
230V
1PH
6HK(0,1)6500206
2.4
1.8
2.2
6.2
7.5
1.8
2.2
1.8
2.2
6HK(0,1)6500506
4.8
3.6
4.4
12.3
15.0
3.6
4.4
3.6
4.4
6HK(0,1)6500806
7.7
5.8
7.1
19.7
24.1
5.8
7.1
5.8
7.1
6HK(0,1)6501006
9.6
7.2
8.8
24.6
30.1
7.2
8.8
7.2
8.8
6HK(1,2)6501306
12.5
9.4
11.5
32.0
39.2
3.1
3.8
9.4
11.5
6HK(1,2)6501506
14.4
10.8
13.2
36.9
45.1
3.6
4.4
10.8
13.2
6HK(1,2)6501806
17.3
13.0
15.9
44.3
54.2
6.5
7.9
13.0
15.9
6HK(1,2)6502006
19.2
14.4
17.6
49.2
60.2
7.2
8.8
14.4
17.6
6HK(1,2)6502506
24.0
18.0
22.0
61.5
75.2
7.2
8.8
18.0
22.0
3PH
6HK06501025
9.6
7.2
8.8
24.6
30.1
7.2
8.8
7.2
8.8
6HK06501525
14.4
10.8
13.2
36.9
45.1
10.8
13.2
10.8
13.2
6HK06501825
17.3
13.0
15.9
44.3
54.2
13.0
15.9
13.0
15.9
6HK16502025
19.2
14.4
17.6
49.2
60.2
7.2
8.8
14.4
17.6
6HK16502525
24.0
18.0
22.0
61.5
75.2
9.0
11.0
18.0
22.0
1. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.
2. (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper bar.
3. For different power distributions, see conversion table on Page 4.