background image

1055361-BTG-B-0913

10

Johnson Controls Unitary Products

AIR FLOW DATA (CFM)

1

Models

Blower 

Motor Speed

External Static Pressure (in. wc.)

0.10

0.20

0.30

0.40

0.50

0.60

0.70

208 Volt

AHR18B

High

1024

1000

970

930

860

810

NA

Medium

756

731

700

670

620

550

NA

Low

557

531

495

445

375

315

195

AHR22B

High

1214

1177

1136

1071

1019

951

828

Medium

705

684

661

592

548

404

266

Low

534

512

460

394

261

167

125

AHR24B

High

995

970

935

900

925

795

645

Medium

820

810

780

745

695

545

485

Low

715

695

640

405

370

375

220

AHR29C

High

1605

1548

1486

1420

1356

1159

913

Medium

981

960

921

815

756

697

614

Low

769

717

654

561

510

451

389

AHR30B

High

1380

1315

1245

1160

1075

990

885

Medium

1060

1040

1005

955

890

860

820

Low

1035

980

910

825

770

685

485

AHR34C

High

1496

1423

1328

1217

1105

1041

942

Medium

976

907

843

815

742

686

582

Low

729

687

647

602

498

447

366

AHR36B

High

1410

1335

1270

1190

1110

990

820

Medium

1215

1170

1115

1050

935

850

740

Low

950

935

895

855

NA

NA

NA

AHR42C

High

1800

1725

1645

1545

1360

1200

1050

Medium

1535

1480

1415

1280

1155

1010

870

Low

1225

1195

1095

1025

925

825

680

AHR48D

High

1890

1830

1755

1650

1565

1450

1285

Medium

1515

1480

1450

1380

1295

1115

985

Low

1170

1165

1140

1100

965

860

745

AHR60D

High

1911

1841

1757

1668

1564

1439

1233

Medium

1556

1507

1450

1388

1266

1246

989

Low

1211

1181

1151

1062

992

911

827

230 Volt

AHR18B

High

1145

1100

1055

1005

930

845

725

Medium

755

750

725

665

605

485

435

Low

680

655

625

585

540

395

300

AHR22B

High

1294

1254

1189

1133

1064

996

907

Medium

803

785

763

729

645

585

422

Low

615

600

566

492

447

284

183

AHR24B

High

1305

1285

1225

1175

920

915

835

Medium

930

920

890

845

705

760

505

Low

735

730

700

670

545

470

NA

AHR29C

High

1711

1665

1598

1513

1435

1309

1088

Medium

1134

1111

1068

998

909

813

735

Low

887

861

792

695

649

576

486

AHR30B

High

1450

1380

1300

1215

1130

1030

910

Medium

1330

1280

1205

1135

1050

975

780

Low

1160

1120

1065

1005

930

825

635

AHR34C

High

1579

1511

1399

1273

1145

1068

978

Medium

1108

1057

987

924

849

770

703

Low

849

802

756

712

630

527

170

AHR36B

High

1470

1390

1325

1245

1155

1045

880

Medium

1325

1265

1205

1125

1025

965

840

Low

1115

1075

1025

950

NA

NA

NA

(For notes see page 11.)

Summary of Contents for AHR18B3XH21

Page 1: ... ing device For added flexibility an R 22 or R 410A TXV or orifice can be field installed to meet your refrigerant choice FEATURES Thermal Expansion Valve Provides the ultimate refrigerant con trol required for today s high efficient product The UPG bolt on TXV provides the added flexibility to convert the air handler to the required refrigerant The UPG TXV is a true bolt on which does not require...

Page 2: ... 21 21 1 2 17 13 32 20 AHR48D3XH21 57 24 1 2 26 20 29 32 23 1 2 7 8 AHR60D3XH21 57 24 1 2 26 20 29 32 23 1 2 1 All dimensions are in inches 2 Actual size conduit size COIL TECHNICAL DATA Models Application Refrig Conn Types Face Area Sq Ft Rows Deep Fins Per In Coil Size Tube Geometry Tube Dia Fin Type AHR18B Cooling Heat Pump Sweat 3 4 2 14 2 14 x 17 5 1 x 0 866 3 8 Enhanced AHR22B Cooling Heat P...

Page 3: ...50 7 41 5 80 67 58 0 49 5 39 9 31 2 75 62 47 1 38 9 30 4 21 1 70 57 37 1 33 1 28 2 23 9 AHR34C 1000 85 72 35 0 31 8 28 4 24 7 80 67 32 2 29 1 25 7 22 3 75 62 26 4 23 4 21 0 17 1 70 57 21 4 18 6 20 2 12 1 AHR36B 1060 85 72 71 1 62 4 51 5 44 3 80 67 59 2 51 0 42 0 32 7 75 62 48 0 39 6 30 8 21 8 70 57 37 3 32 8 28 3 24 0 1245 85 72 83 2 66 7 60 1 48 9 80 67 66 0 59 5 47 8 37 1 75 62 55 0 45 2 35 5 24...

Page 4: ...ATION FACTORS RATED CFM VS ACTUAL CFM Of Rated Airflow CFM 80 90 100 110 120 Capacity Factor 0 96 0 98 1 00 1 02 1 03 PHYSICAL ELECTRICAL DATA COOLING ONLY Models AHR18B AHR22B AHR24B AHR29C AHR30B AHR34C AHR36B AHR42C AHR48D AHR60D Blower Diameter x Width 10 x 8 10 x 8 10 x 8 10 x 10 10 x 8 10 x 10 10 x 8 10 x 10 10X10 10X10 Motor HP 1 4 HP 1 3 HP 1 4 HP 1 2 HP 3 4 HP 1 2 HP 3 4 HP 3 4 HP 3 4 HP ...

Page 5: ... 2kW High High High 6HK 1 2 6502506 6HK16502525 24kW High 1 0 1 0 no circuit breaker OR 1 with circuit breaker 2 1 2 1 with circuit breaker no breaker jumper bar OR 2 with circuit breaker breaker jumper bar ELECTRIC HEAT PERFORMANCE DATA 208 230 1 60 208 230 3 60 Heater Models1 2 Nominal kW 240V Total Heat3 kW Staging kW MBH W1 Only W1 W2 208V 230V 208V 230V 208V 230V 208V 230V 1PH 6HK 0 1 6500206...

Page 6: ...42C 6HK 0 1 6500206 10 0 14 6 16 3 15 20 12 12 6HK 0 1 6500506 20 0 25 4 28 8 30 30 10 10 6HK 0 1 6500806 32 0 38 4 43 8 40 45 8 8 6HK 0 1 6501006 40 0 47 1 53 8 50 60 6 6 6HK 1 2 6501306 52 0 60 1 68 8 70 70 6 4 6HK 1 2 6501506 60 0 68 8 78 8 70 80 4 4 AHR36B AHR48D 6HK 0 1 6500206 10 0 14 6 16 3 15 20 12 12 6HK 0 1 6500506 20 0 25 4 28 8 30 30 10 10 6HK 0 1 6500806 32 0 38 4 43 8 40 45 8 8 6HK 0...

Page 7: ...25 60 50 25 6 6 10 6 8 10 1 MOP Maximum Overcurrent Protection device must be HACR type circuit breaker or time delay fuse 2 Stated sizes are for 75 C copper wire only If wire other than non plated 75 C ambient copper wire is used consult applicable tables of the NEC and local codes 3 1st Circuit includes the blower motor amps ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY 208 230 3 60 Air Handler...

Page 8: ...R MULTI SOURCE POWER SUPPLY 208 230 3 60 Air Handler Models Heater Models Total Heater Amps 240V Min Circuit Ampacity MOP1 Min Wire Size AWG 2 208V 230V 208V 230V 208V 230V Circuit Circuit Circuit 1st3 2nd 1st3 2nd 1st3 2nd 1st3 2nd 1st3 2nd 1st3 2nd AHR36B AHR48D 6HK16502025 46 2 28 8 25 0 32 6 28 9 30 25 35 30 10 10 8 10 AHR60D 6HK16502025 46 2 28 8 25 0 32 6 28 9 30 25 35 30 10 10 8 10 6HK16502...

Page 9: ...1055361 BTG B 0913 Johnson Controls Unitary Products 9 TYPICAL THERMOSTAT CONNECTIONS ...

Page 10: ...45 1545 1360 1200 1050 Medium 1535 1480 1415 1280 1155 1010 870 Low 1225 1195 1095 1025 925 825 680 AHR48D High 1890 1830 1755 1650 1565 1450 1285 Medium 1515 1480 1450 1380 1295 1115 985 Low 1170 1165 1140 1100 965 860 745 AHR60D High 1911 1841 1757 1668 1564 1439 1233 Medium 1556 1507 1450 1388 1266 1246 989 Low 1211 1181 1151 1062 992 911 827 230 Volt AHR18B High 1145 1100 1055 1005 930 845 725...

Page 11: ...1753 1640 1522 1296 Medium 1733 1672 1609 1527 1431 1272 1220 Low 1388 1359 1313 1255 1133 1004 912 1 Air handler units have been tested to UL 1995 CSA 22 2 standards up to 0 30 wc external static pressure Dry coil conditions only tested without filters For optimal performance external static pressures of 0 2 to 0 5 are recommended Applications above 0 6 are not recommended Airflow data shown is f...

Page 12: ... change without notice Published in U S A 1055361 BTG B 0913 Copyright 2013 by Johnson Controls Inc All rights reserved Supersedes 1055361 BTG A 0713 York International Corp 5005 York Drive Norman OK 73069 NOTES ...