YOKOGAWA vigilantplant YTA50 User Manual Download Page 3

5.

BLOCK DIAGRAM

mV

mV

TC

MUX

CPU

4 mA

7–35VDC

supply -

4–20 mA

Comm.

EEPROM

A / D

D / A

PGA

Int.
CJC

RTD.lin.R

-Wire

+

-

+

-

4    3    2

6

2

1

5

4

3

0_16

mA

F01E.EPS

A

6.

WIRING

See wiring diagram.   For output signal, use twisted pair or
cables with performance equivalent to 600V vinyl insulate cable.
For wiring in high or low temperature, use a wire or cable
suitable for such temperature.  Use cables and wires which
meet atmospheric conditions. Take necessary measure to avoid
corrosion or damage of cables and wires.

Important

When mounting on a sensor head, do not overtighten the
screws.

 DIMENSIONS

F02E.EPS

Unit: mm
(Approx. inch)

20.2

 (0.80)

ø

(0.24)

33 (1.30)

ø

44 (1.73)

2

1

3

4

6

5

 WIRING DIAGRAM

T/C or 

DC milivolts

Two-wire

 RTD or ohm

Three-wire

RTD or ohm

Four-wire

RTD or ohm

1

2

3

4

5

6

(–)

(+)

(B)

(B)

1

2

3

4

5

6

(B)

(B)

1

2

3

4

5

6

(B)

(A)

SUPPLY

1

2

3

4

5

6

(A)

(A)

(A)

(–)

(+)

SUPPLY

(–)

(+)

SUPPLY

(–)

(+)

SUPPLY

(–)

(+)

F03E.EPS

7.

APPROVAL OPTIONS

CENELEC ATEX Intrinsically safe model (/KS2, /DS2)

ATEX Certificate: KEMA 06 ATEX 0191 X
Applicable Standard: EN 50014, EN 50020, EN 50284

 II 1 GD, T80

°

C...T105

°

C

EEx ia IIC T6

Non-Hazardous Location

Hazardous Location

YTA50

Safety

Barrier

F04E.EPS

[ Installation diagram ]

Intrinsically safety rating(maximum value)

Output/Power supply :
Ui=30 V, Ii=120 mA, Pi=0.84 W, Ci<1 nF, Li<10 

µ

H

Sensor :
Uo=9.6 V, Io=25 mA, Po=60 mW, Co<2.4 

µ

F, Lo<33 mH

Applicable in Zone

0, 1, 2, 20, 21, or 22

Maximum Ambient Temperature for gas-proof

For T4: 85

°

C,   For T5/T6: 60

°

C

Maximum Surface Temperature for dust-proof

For T4: T105

°

C (Ambient Temperature: –40 to 85

°

C)

For T6: T85

°

C (Ambient Temperature: –40 to 60

°

C)

FM Intrinsically safe model (/DS2)

Applicable Standard: FM 3600, FM 3610, FM 3611, FM 3810
Installation diagram

see note 1,2

see note 1,2

Non-hazardous 
Locations

Hazardous Locations

YTA50

Safety

barrier

Class I, 
Div.1,Groups A,B,C,D

Power supply

buit into 

receiver

Seperate

Power supply

+  

-

    

Seperate

Power supply

-

   +    

Receiver

Non-hazardous 
Locations

Hazardous Locations

YTA50

Safety

barrier

F05E.EPS

[ Connection with power supply buit in receiver ]

[ Connection with seperate power supply and receiver ]

Class I, 
Div.1,Groups A,B,C,D

+

-

+

-

-

+

-

+

Output : standard 4 to 20 mA loop

Note
1. Maximum entity paramters ;
V

MAX

=30 VDC, I

MAX

=120 mA, P

MAX

=0.84 W, C

I

=1 nF, L

I

=10 

µ

H

2. Maximum power P

MAX

=0.84 W is limited by the resistor in the

barrier.
If V

oc

=28 V, the resistor shall be more than 233.3

.

If V

oc

=30 V, the resistor shall be more than 250.0

.

Reviews: