5.
BLOCK DIAGRAM
mV
mV
TC
MUX
CPU
4 mA
7–35VDC
supply -
4–20 mA
Comm.
EEPROM
A / D
D / A
PGA
Int.
CJC
RTD.lin.R
-Wire
+
-
+
-
4 3 2
6
2
1
5
4
3
0_16
mA
F01E.EPS
A
6.
WIRING
See wiring diagram. For output signal, use twisted pair or
cables with performance equivalent to 600V vinyl insulate cable.
For wiring in high or low temperature, use a wire or cable
suitable for such temperature. Use cables and wires which
meet atmospheric conditions. Take necessary measure to avoid
corrosion or damage of cables and wires.
Important
When mounting on a sensor head, do not overtighten the
screws.
■
DIMENSIONS
F02E.EPS
Unit: mm
(Approx. inch)
20.2
(0.80)
ø
6
(0.24)
33 (1.30)
ø
44 (1.73)
2
1
3
4
6
5
■
WIRING DIAGRAM
T/C or
DC milivolts
Two-wire
RTD or ohm
Three-wire
RTD or ohm
Four-wire
RTD or ohm
1
2
3
4
5
6
(–)
(+)
(B)
(B)
1
2
3
4
5
6
(B)
(B)
1
2
3
4
5
6
(B)
(A)
SUPPLY
1
2
3
4
5
6
(A)
(A)
(A)
(–)
(+)
SUPPLY
(–)
(+)
SUPPLY
(–)
(+)
SUPPLY
(–)
(+)
F03E.EPS
7.
APPROVAL OPTIONS
CENELEC ATEX Intrinsically safe model (/KS2, /DS2)
ATEX Certificate: KEMA 06 ATEX 0191 X
Applicable Standard: EN 50014, EN 50020, EN 50284
II 1 GD, T80
°
C...T105
°
C
EEx ia IIC T6
Non-Hazardous Location
Hazardous Location
YTA50
Safety
Barrier
F04E.EPS
[ Installation diagram ]
Intrinsically safety rating(maximum value)
Output/Power supply :
Ui=30 V, Ii=120 mA, Pi=0.84 W, Ci<1 nF, Li<10
µ
H
Sensor :
Uo=9.6 V, Io=25 mA, Po=60 mW, Co<2.4
µ
F, Lo<33 mH
Applicable in Zone
0, 1, 2, 20, 21, or 22
Maximum Ambient Temperature for gas-proof
For T4: 85
°
C, For T5/T6: 60
°
C
Maximum Surface Temperature for dust-proof
For T4: T105
°
C (Ambient Temperature: –40 to 85
°
C)
For T6: T85
°
C (Ambient Temperature: –40 to 60
°
C)
FM Intrinsically safe model (/DS2)
Applicable Standard: FM 3600, FM 3610, FM 3611, FM 3810
Installation diagram
see note 1,2
see note 1,2
Non-hazardous
Locations
Hazardous Locations
YTA50
Safety
barrier
Class I,
Div.1,Groups A,B,C,D
Power supply
buit into
receiver
Seperate
Power supply
+
-
Seperate
Power supply
-
+
Receiver
Non-hazardous
Locations
Hazardous Locations
YTA50
Safety
barrier
F05E.EPS
[ Connection with power supply buit in receiver ]
[ Connection with seperate power supply and receiver ]
Class I,
Div.1,Groups A,B,C,D
+
-
+
-
-
+
-
+
Output : standard 4 to 20 mA loop
Note
1. Maximum entity paramters ;
V
MAX
=30 VDC, I
MAX
=120 mA, P
MAX
=0.84 W, C
I
=1 nF, L
I
=10
µ
H
2. Maximum power P
MAX
=0.84 W is limited by the resistor in the
barrier.
If V
oc
=28 V, the resistor shall be more than 233.3
Ω
.
If V
oc
=30 V, the resistor shall be more than 250.0
Ω
.