YOKOGAWA vigilantplant YTA50 User Manual Download Page 2

The YTA50 is a head mount type of temperature transmitter that
accepts thermocouple or RTD input and converts it to a 4 to 20
mA DC signal for transmission. The YTA50 conforms to the
standard DIN form B head mounting.
It is imperative that usres observe the instructions in this
manual to ensure the protection and safety of operators.

1.

MODEL AND SUFFIX CODES

Temperature Transmitter (Head Mount Type)

T01E.EPS

Model Suffix code

Descriptions

YTA50

..................

Output
Signal

Optional
Specifications

-A

 .............

/KS2

EEx ia llC T1-6
Amb. Temperature
T1-4: -40 to 85

°

C

T5-6: -40 to 60

°

C

CENELEC ATEX/FM intrinsically
safe approval combination

CENELEC:
EEx ia llC T1-6
FM: IS Class I, Div.1,
Groups A, B, C & D

/DS2

CENELEC ATEX intrinsically
safe approval

4 to 20 mA DC 

2.

WARRANTY

The warranty period of the instrument is as of condition shown
when purchasing. Any trouble arising during the warranty period
shall be replaced at free of charge.
The following problems or troubles shall not be eligible of
charge-exempt repair.

• Caused by improper usage or storage of the customer which

exceeds the specification requirements.

• Caused by mishandling or modification.
• Caused by fire, earthquake or other acts of God that are not

directly a result of problems of the instrument.

3.

HANDLING PRECAUTIONS

(1) Read this manual thorughly and carefully before handling

the instruments. Observe the instructions.

(2) Store the product in location that meets the following

requirements.

• No exposure to rain or water
• No major mechanical vibration or shock
• Humidity and Temperature limitations
• Ordinary conditions(25

°

C, 65%) is preferable.

Otherwise, as of specified in “Standard Specifications.”

(3) Avoid corrosive atmosphere for storage and installation.
(4) For safe installation of the transmitter in hazardous area,

the following must be observed. The module must only be
installed by qualified personnels who are familiar with the
national and international laws, directives, and standards
that apply to this area.

(5) Yokogawa will not be liable for malfunctions or damage

resulting from any modification made to this instrument by
the customer.

4.

STANDARD SPECIFICATIONS

Accuracy

See table in the right.

Cold Junction Compensation Accuracy(For T/C only)

±

1

°

C(

±

1.8

°

F)

Ambient Temperature Effects (per 10

°

C Change)

See table in the right

T/C

RTD

DC Voltage [mV]
Resistance [

]

B
E
J
K
N
R
S
T
L
U
W3
W5
Pt100
Ni100

IEC584

DIN43710

ASTM E988-90

IEC751

DIN43760

400 to 1820

-100 to 1000
-100 to 1200
-180 to 1372
-180 to 1300

-50 to 1760
-50 to 1760

 -200 to 400
 -100 to 900
 -200 to 600

0 to 2300
0 to 2300

 -200 to 850

-60 to 250

-10 to 800 mV

0 to 5000

200

50
50
50

100
200
200

50
50
75

200
200

25
25

5 mV

30

±

0.1% or 

±

2.0

°

C

±

0.1% or 

±

1.0

°

C

±

0.1% or 

±

2.0

°

C

±

0.1% or 

±

1.0

°

C

±

0.1% or 

±

2.0

°

C

±

0.1% or 

±

0.2

°

C

±

0.1% or 

±

0.01mV

±

0.1% or 

±

0.1

Type

Standard

Input

ranges 

°

C

Accuracy *

1

Minimum

span 

°

C

T02E.EPS

Temperature

effect *

1

 

±

0.1% or 

±

2.0

°

C

±

0.1% or 

±

0.5

°

C

±

0.1% or 

±

2.0

°

C

±

0.1% or 

±

0.5

°

C

±

0.1% or 

±

2.0

°

C

±

0.1% or 

±

0.1

°

C

±

0.1% or 

±

10

V

±

0.1% or 

±

0.1

*1 

: The value whichever is greater.  value in % indicates the

       % of span.

Power Supply Effects

±

0.005% of FS per Volt

RFI Effects

Tested per EN 61326, field intensity up to 10 V/m.

EMC Conformity  

EN 61326

Maximum Zero Offset

±

50% of the maximum temperature

Input Signal Source Resistance (for T/C input)

10 M

, or 3 k

 at power-off

Input Lead Wire Resistance (for RTD input)

 per wire or lower

Burnout

High (21.6 mA or more) or Low (3.6 mA or less)

Output

Two wire 4 to 20 mA DC

Response Time

1 to 60 sec (as specified upon shipment)

Ambient Temperature Limits

 (Option code may affect limit.)

–40 to 85

°

C (–40 to 185

°

F)

Ambient Humidity Limits

5 to 90% RH at 40

°

C (104

°

F)

Supply Voltage

7 to 35 V DC
7 to 30 V DC for Intrinsically safe type

Load Resistance

 (Limitation)

0 to (E–7)/0.023 [

],   where E is power supply voltage.

Ex. 739 

 max. @ 24 V DC

Isolation

Input/output isolated to 1500 V AC.

Mounting

DIN form B head mounting

Terminals

M3 screws

Weight

50 g(0.11 lb)