<2. Overview>
2-3
IM 21B03D01-01E
2.3 Model and Suffix Codes
Model
Suffix Code
Description
PK200
. . . . . . . . . . . . .
Input Signal
-A . . . . . . . . . . .
-C . . . . . . . . . . .
4 to 20mA DC
4 to 20mA/10 to 50mA DC selection type
Output Signal
1 . . . . . . . . .
2 . . . . . . . . .
3 . . . . . . . . .
4 . . . . . . . . .
5 . . . . . . . . .
6 . . . . . . . . .
7 . . . . . . . . .
8 . . . . . . . . .
9 . . . . . . . . .
Output signal Pa calibration
20 to 100kPa
scale 0 to 200kPa
Output signal Pa calibration
40 to 200kPa
scale 0 to 400kPa
Output signal kgf/cm
2
calibration
0.2 to 1.0kgf/cm
2
scale 0 to 2kgf/cm
2
Output signal kgf/cm
2
calibration
0.4 to 2.0kgf/cm
2
scale 0 to 4kgf/cm
2
Output signal bar calibration
0.2 to 1.0bar
scale 0 to 2bar
Output signal bar calibration
0.4 to 2.0bar
scale 0 to 4bar
Output signal P calibration
3 to 15psi
scale 0 to 30Psi
Output signal P calibration
6 to 30psi
scale 0 to 60Psi
Output signal P calibration
3 to 27psi
scale 0 to 60Psi
Connections
1 . . . . . .
2 . . . . . .
3 . . . . . .
4 . . . . . .
Air connection: Rc 1/4, Electrical connection: G1/2 female
Air connection: Rc 1/4, Electrical connection: G3/4 female
Air connection: 1/4 NPT female, Electrical connection: 1/2NPT female
Air connection: 1/4 NPT female, Electrical connection: 3/4NPT female
Option
/
See section 2.4.
2.4 Options
• Option Code /JF3: JIS Flameproof
TIIS flameproof Exd II B+H
2
T6X
• Option Code /G11: Packing adapter for TIIS Flameproof
Electrical connection: G1/2 female, Applicable cable
O.D.: 8 to 12mm
• Option Code /G21: Packing adapter for TIIS Flameproof
Electrical connection: G3/4 female, Applicable cable
O.D.: 10 to 16mm
• Option Code /FF1: FM Explosionproof
• Option Code /JS3: TIIS Intrinsically Safe
Applicable only with input signal code-A.
• Option Code /CS1: CSA Intrinsically Safe
• Option Code /SCF-:
Special Color Finished on converter cover
Allows the paint color of only a converter cover to be selectable by specifying the color in the
specification item with reference to GS22D01F01-00EN.
• Option Code /X1: Epoxy Paint
Epoxy resin-baked coating.
Not applicable for special color finished.
• Option Code /L: Lightning Protector
Installed in the terminal box to protect internal circuitry from high voltage surges such as those caused
by lightning induced.
• Option Code /AM: AUTO/MANUAL Switch
Mounted on front of housing, in manual mode, output signal is varied by adjusting the external supply
pressure regulator.
• Option Code /GW: Double Scale Pressure Gauge
Double scales are kPa and kgf/cm
2
.
• Option Code /SS: Stainless Steal Screw and Bracket Screw and bracket, both are made of stainless steal.
• Option Code /RA: Reverse Action
Increasing of input signal to make output pressure decrease.
三千控制阀网