background image

IM 05P01F31-11EN  page 6/10

■  Parameters to be set

Control Type

Parameter Symbol Name of Parameter

Setting Range

CNT

Control type

PID: PID control

ONOF: ON/OFF control (1 point of hysteresis)

ONOF2: ON/OFF control (2 points of hysteresis)

Note:  Some setpoints may not be displayed depending on the model and suffix codes.

Input Function

Parameter Symbol Name of Parameter

Setting Range

IN

PV input type

OFF: Disable

K1: -270.0 to 1370.0 

0

C / -450.0 to 2500.0

 

0

F

K2: -270.0 to 1000.0 

0

C / -450.0 to 2300.0

 

0

F

K3: -200.0 to 500.0 

0

C / -200.0 to 1000.0

 

0

F

J: -200.0 to 1200.0 

0

C / -300.0 to 2300.0

 

0

F

T1: -270.0 to 400.0 

0

C / -450.0 to 750.0

 

0

F

T2: 0.0 to 400.0 

0

C / -200.0 to 750.0

 

0

F

B: 0.0 to 1800.0 

0

C / 32 to 3300

 

0

F

S: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

R: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

N: -200.0 to 1300.0 

0

C / -300.0 to 2400.0

 

0

F

E: -270.0 to 1000.0 

0

C / -450.0 to 1800.0

 

0

F

L: -200.0 to 900.0 

0

C / -300.0 to 1600.0

 

0

F

U1: -200.0 to 400.0 

0

C / -300.0 to 750.0

 

0

F

U2: 0.0 to 400.0 

0

C / -200.0 to 1000.0

 

0

F

W: 0.0 to 2300.0 

0

C / 32 to 4200

 

0

F

PL2: 0.0 to 1390.0 

0

C / 32.0 to 2500.0

 

0

F

P2040: 0.0 to 1900.0 

0

C / 32 to 3400

 

0

F

WRE: 0.0 to 2000.0 

0

C / 32 to 3600

 

0

F

JPT1: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

JPT2: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

PT1: -200.0 to 850.0 

0

C / -300.0 to 1560.0

 

0

F

PT2: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

PT3: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

0.4-2V: 0.400 to 2.000 V

1-5V: 1.000 to 5.000 V

4-20: 4.00 to 20.00 mA

0-2V: 0.000 to 2.000 V

0-10V: 0.00 to 10.00 V

0-20: 0.00 to 20.00 mA

-1020: -10.00 to 20.00 mV

0-100: 0.0 to 100.0 mV

UNIT

PV input unit

-: No unit, C: Degree Celsius

-: No unit, - -: No unit, - - -: No unit, F: Degree Fahrenheit

RH

Maximum value of 

PV input range

Depends on the input type.

- For temperature input -

Set the temperature range that is actually controlled. 

(RL<RH)

- For voltage / current input -

Set the range of a voltage / current signal that is applied.

The scale across which the voltage / current signal is 

actually controlled should be set using the maximum value 

of input scale (SH) and minimum value of input scale (SL).

(Input is always 0% when RL = RH.)

RL

Minimum value of 

PV input range

SDP

PV input scale 

decimal point 

position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

SH

Maximum value of 

PV input scale

-19999 to 30000, (SL<SH), | SH - SL | ≤ 30000

SL

Minimum value of 

PV input scale

Note 1: SDP, SH, and SL are displayed only for voltage/current input.

Note 2: W: W-5%Re/W-26%Re (Hoskins Mfg.Co.), ASTM E988

Output Function

Parameter Symbol Name of Parameter

Setting Range

CT

Control output cycle 

time

0.5 to 1000.0 s

4.  Setting Alarm Type

The following operating procedure shows an example of changing the alarm-1 type 

(factory default: PV high limit alarm) to PV low limit alarm (setpoint: 02).

1.

2.

3.

4.

5.

6.

MODE menu is displayed.

 

Press the Right arrow key until ALRM menu appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

Hold down the key for 3 seconds.

Show the Operation Display.

ALRM menu is displayed.

Press the SET/ENTER key.

Energized/De-energized

Latch action

Stand-by action

Symbol

● 

To change the alarm type, change the last 2 digits of the 

   5-digit value.

● 

Stand-by action and excitation are turned on or off by 

   selecting 1 or 0. (See “  Setting Display of Alarm Type.”)

● 

For the latch action, see User ’s   Manual (IM 05P01F31-01EN).

The parameter AL1 (alarm-1 type) is 

displayed.

The last digit of the setpoint blinks.

Change the setpoint using the Up/Down arrow keys 

to increase and decrease the value and 

the Left/Right arrow keys to move between digits. 

The alarm-1 type setpoint 02 

(PV low limit) is registered.

After the setup is completed, 

press the DISP key once to 

return to the Operation Display.

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

Open 

(

unlit

)

Closed 

(lit)

SP or Target SP

PV

Deviation setpoint

Hysteresis

-

-

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Open 

(

unlit

)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Output

Hysteresis

Closed

(lit)

Hysteresis

Alarm setpoint Output

Alarm setpoint

Hysteresis

PV

Hysteresis

Alarm setpoint

PV

SP or Target SP

Hysteresis

PV

Deviation setpoint

SP or Target SP

Deviation 

setpoint

PV

Hysteresis Hysteresis

SP or Target SP

PV

Deviation setpoint

Hysteresis

SP or Target SP

PV

Hysteresis Hysteresis

Deviation 

setpoint

Closed 

(unlit)

SP or 

Target SP

Alarm setpoint

Hysteresis

SP or 

Target SP

Hysteresis

Alarm setpoint

Alarm setpoint

Hysteresis

PV

Alarm setpoint

Output

Hysteresis

Hysteresis

Alarm setpoint Output

No alarm (00)

Alarm Action (De-energized)

PV high limit (01)

Analog input PV high limit (19)

PV low limit (02)

Analog input PV low limit (20)

SP high limit (03)

Target SP high limit (09)

SP low limit (04)

Target SP low limit (10)

Deviation high limit (05)

Target SP deviation high 

limit (11)

Deviation low limit (06)

Target SP deviation low limit (12)

Deviation high and low 

limits (07)

Target SP deviation high and 

low limits (13)

Deviation within high and low 

limits (08) 

Target SP deviation within high 

and low limits (14)

Control output high limit (15)

Control output low limit (16)

Feedback input high limit (27)

Feedback input low limit (28)

PV velocity (29)

Fault diagnosis alarm (30)

FAIL (31)

Alarm Type (Alarm Setpoint)

Alarm Action (Energized)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Closed 

(lit)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(

unlit

)

Open 

(un

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Open 

(

lit

)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Closed 

(unlit)

Burnout of PV input, ADC failure, RJC error.

For the factory default, the contact output is turned ON in normal operation, 

OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF

Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Note 2:        Positive setpoint,        Negative setpoint

Setting Display of Alarm Type 

Stand-by Action

Energized (0) / De-energized (1)

Alarm type

Without (0) or With (1) 

Stand-by action

Latch action (0/1/2/3/4)

See 

User’s

 Manual (IM 05P01F31-01EN).

PV low limit 

alarm setpoint

Treated

as normal

ºC

Power-on

Time

The alarm output does not turn on

in this region even if the PV valule

is below PV low limit alarm setpoint.

Normal

Abnormal

The alarm output

turns on.

5.   Setting Alarm Setpoint

The following operating procedure shows an example of setting the alarm-1 setpoint 

of group 1 to 180.0.

Before setting the alarm setpoint, check the alarm type.

To change the alarm type, see “5. Setting Alarm Type.” 

1.
2.

3.

4.

5.

6.

Press the Right arrow key.

Press the SET/ENTER key.

SP menu is displayed.

Display the parameter and group that need to be changed.

Blinks during the change. 

Press the SET/ENTER key.

Press the Down arrow key until A1 appears.

Press the SET/ENTER key.

Show the Operation Display.
Display MODE menu with the same procedure as described in 

Setting Alarm Type.

Group

The parameter A1 is displayed.

A1 to A4 represent the alarm-1 to -4 setpoints.

Each parameter and group can be changed 

in the Parameter Setting Displays of alarms

using arrow keys.

Up/Down arrow keys: parameters

Left/Right arrow keys: groups

Change the setpoint using the Up/Down arrow 

keys to increase and decrease the value and 

the Left/Right arrow keys to move between digits.

The setpoint has been registered.

After the setup is completed, press 

the DISP key once to return to the 

Operation Display. 

Initializing parameter values

Parameters that you have changed can be initialized to factory default values or user 

default values. For details, see “Parameter Initialization” in the User’s Manual (IM 

05P01F31-01EN).

Changing the parameter display levels

This operation guide does not explain all the parameters. To display all the param-

eters, you need to change the parameter display level to professional setting mode. 

For details, see “Setting Security Functions” in the User’s Manual (IM 05P01F31-

01EN).

Summary of Contents for UT32A-R

Page 1: ...umented panel Mount the instrument in a location where its terminals will not inadvertently be touched Well ventilated locations Mount the instrument in well ventilated locations to prevent the instru...

Page 2: ...e set manually Reference junction compensation error 1 0 C 15 to 35 C 1 5 C 10 to 15 C and 35 to 50 C Applicable standards JIS IEC DIN ITS 90 for TC and RTD Analog Output Specifications Suffix code C...

Page 3: ...urrent as a spark removal surge suppression circuit into the line in parallel with the load After completing the wiring the terminal cover is recommended to use for the instrument Recommended Crimp on...

Page 4: ...IM 05P01F31 11EN page 4 10 Intentionally blank Intentionally blank...

Page 5: ...to easily set the basic function of the controller Turn on the controller to start the Quick setting function This function allows you to easily set the control type and input and quickly start the c...

Page 6: ...nt Open unlit SP or Target SP Alarm setpoint Hysteresis SP or Target SP Hysteresis Alarm setpoint Alarm setpoint Output Hysteresis Closed lit Hysteresis Alarm setpoint Output Alarm setpoint Hysteresis...

Page 7: ...arrow keys to display the required setpoint Blinks during the change The setpoint has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see U...

Page 8: ...Contact us for repair ERR SYS System data error System data is corrupted Faulty Contact us for repair PAR 0004 for user default value error only Setup parameter PA ER User parameter default value erro...

Page 9: ...13 Target SP deviation high and low limits 14 Target SP deviation within high and low limits 15 OUT high limit 16 OUT low limit 19 Analog input PV high limit 20 Analog input PV low limit 29 PV velocit...

Page 10: ...Ladder communication CO M Coordinated master station CO S Coordinated slave station MBASC Modbus ASCII MBRTU Modbus RTU CO S1 Coordinated slave station Loop 1 mode CO S2 Coordinated slave station Loo...