Time Event
The time event feature begins countdown when a program starts running, and after the elapse of a preset time,
output an on-time event (contact output ON) or off-time event (contact output OFF).
The time of time event is not elapsed during “Hold” or “Wait” status. When the “Advance” is executed, remaining
time in the segment is canceled.
TM1
TM4
TM3
TM2
TM5
ON time
OFF time
SEG1
SEG2
SEG3
SEG4
SEG5
SP1
SP2
SP3
SP4
SP5
Time event 1
ON time
OFF time
Time event 2
NOTE
(1) When you don’t want “event-OFF” at the end of program operation.
Set “OFF” to time event 1/2 off time (EOF1 or EOF2).
(2) When you want “event-ON” at the start of program operation.
Set “0.00” to time event 1/2 on time (EON1 or EON2).
(3) When the time of events on/off time exceeds the setting time of program, these events does not work.
(4) Digital (Contact) output is OFF, when controller is in RESET mode.
(5) The previous event status are kept when controller is in Hold mode.