IM 5E1E70-01E
15
(SP value display)
(SP value display)
(SP value display)
Target
setpoint
“Target setpoint”, “Segment No. at present” and
“Remaining segment time” are not parameters to be set.
You can confirm the value of these.
SSP
CTL
Control mode
ONF: On/off control
PID: PID control
OFF: Not Hold
ON: Hold
PID
AT
Auto-tuning
OFF: Stop auto-tuning
ON: Start auto-tuning
OFF
P
Proportional
band
1
°
C/
°
F to the temperature that corresponds to 100% of the
measurement range span
5% of measurement
range span
I
Integral time
1 to 3600 seconds;
0: no integral action
240 seconds
D
Derivative
time
1 to 3600 seconds;
0: no derivative action
60 seconds
MR
Manual reset
–100 to 100%
50.0%
HYS
Hysteresis for
on/off control
0
°
C/
°
F to the temperature that corresponds to 100% of the
measurement range span
0.5% of
measurement range
CT
Cycle time of
control output
1 to 240 seconds
30 seconds
FL
Input filter
OFF, 1 to 120 seconds
OFF
BS
PV bias
–100 to 100% of measurement range span
0% of instrument
range span
LOC
Key lock
0: No key lock
1: No key lock
*note
2: Prevents all parameter changing operations
–1: Set to enter the Setup parameter setting display
*Note: Both “0” and “1” are No key lock.
0
Segment No.
at present
Set value
Remaining
segment time
Set value
(2) Operating Parameters
HOLD
Program hold
OFF
OFF: Not execute advance
ON: Execute advance
ADV
Segment
advance
OFF
■
Parameter Lists
(1) Target Setpoint (SP) and Timer Setting 1 and 2
Code
Name
Setting range and unit
Default
User setting
Code
Setting range and unit
Default
User setting
Name