background image

 1  Introduction

The TC10-L is an FM (both FM3545 and FM3810) approved limit controller that can be configured either as a high limit or as a low limit 
controller by a user. 
The TC10-L features 
- universal input,
- two alarm outputs, 
- retransmission output, 
- a timer to count the total time the Set Point has been exceeded, 
- a register to retain the maximum (or the minimum) measure reached.
- The RS485 communication interface is available optionally.

 2  Limiter function

The relay of the output 2 operates in fail-safe mode (relay de-energized during shutdown condition) and latching mode.
OUT 2 turns OFF (in this document this condition will be named shutdown) when:
The instrument is configured as a high limiter (Hi.Lo = Hi) and the measured value is greater than limiter threshold [“SP” parameter].
The instrument is configured as a low limiter (Hi.Lo = Lo) and the measured value is lower than limiter threshold. 
Out 2 remains OFF until the condition which generated the shutdown, no longer exists and the Confirming action (rearm) has been 
performed.
During a shutdown (Out 2 is OFF) the upper display will be red.
Confirming action (rearm) can be performed in two different way:
- by pressing the 

  key [when “diS” parameter is set to “but”] but it will be accepted only when the condition which generated the 

shutdown, no longer exists (EX lamp is OFF) and the set point is shown on the lower display (see “normal display” in “Navigation access”) 
- by momentarily closing the digital input (by an external dry contact) [when diS parameter is set to “di”] but it will be accepted only 
when the condition which generated the shutdown, no longer exists.
We define also that the time duration of the shutdown condition, stored by the instrument, will be the time from Out 2 goes OFF (shut-
down start) and the condition that generate the shutdown no longer exists.
The confirmation action is not part of this time count. 
The time duration of the shutdown condition and max/min measured values are stored in memory and available for viewing (see “navi-
gation access”) until the next shutdown condition occurs.
These informations are lost at power down.

 2.1  High limit control

PV

SP

Process Value

(in eng. units)

Set Point

(a)

(Editing mode)

Limit
Control

High
Limiter

Exceeded
indication

EX

OUT

PK

HI

AL1

AL2

TC10-L

Output

(b)

(c)

(d)

(e)

The HI lamp (d) is ON
When a measured value (a) is higher than the set point (b),“EX” lamp (e) lights, “OUT” lamp (b) turns ON and the limit output relay (Out 2) 
is de-energized.
EX lamp (e) turns off when PV goes into normal condition, while the ”OUT” lamp (c) stays on as it is. 
The out (c) lamp turns off only when the EX lamp (e) is off and a confirming operation (rearm) has been done by an operator. 
The way to confirm are (according to the “diS” parameter):
- pressing  

  key for more than 3 seconds or 

- by DI1.
Output relay is de-energized whenever “OUT” lamp is on.
Check the “HYS” parameter value if the EX lamp (e) is not turn off when PV (a) is lower than SP (b).

SP

HYS

PV

(A)

(B)

(C)

(A)

(B)

(D)

EXCEEDED

LAMP

OUT

LAMP

lit

off

OUTPUT

RELAY

confirmation

(accepted)

confirmation

(not accepted)

lit

off

Energized

De-energized

OFF

OFF

OFF

Lit

Lit

OFF

Lit

ON

OFF

ON

OFF

Lit

OFF

When the EX lamp (e) is ON but PV (a) is lower than SP (b), the upper display will be in green colour and it shows that the PV is in the 
hysteresis area

SP

HYS

PV

(A)

(B)

(C)

EXCEEDED

LAMP

OUT

LAMP

lit

off

OUTPUT

RELAY

confirmation

(accepted)

lit

off

Energized

De-energized

Upper

display

colour

(D)

 2.2  Low limit control

The HI lamp (d) is OFF
When a measured value (a) is lower than the setpoint (b), “EX” lamp (e) lights, “OUT” lamp (c) turns ON and the limit output relay is  
de-energized then. 
“EX” (e) lamp turns off when PV goes into normal condition, while the “OUT” lamp (c) lamp stays on as it is. 
The out (c) lamp turns off only when the EX lamp (e) is off and a confirming operation (rearm) has been done by an operator. 
The way to confirm are (according to the “diS” parameter):
- pressing  

  key for more than 3 seconds or 

- by DI1.
The confirming operation is not accepted during PV exceeds SP (D) (during EXCEEDED lamp lights*). State of output relay is de-energized 
whenever “OUT” lamp is on.
Output relay is de-energized whenever “OUT” lamp is on.
Check the “HYS” parameter value if the EX lamp (e) is not turn off when PV (a) is lower than SP (b).

SP

HYS

PV

(A)

(B)

(C)

(A)

(B)

(D)

EXCEEDED

LAMP

OUT

LAMP

lit

off

OUTPUT

RELAY

confirmation

(accepted)

confirmation

(not accepted)

lit

off

Energized

De-energized

OFF

OFF

OFF

Lit

Lit

OFF

Lit

ON

OFF

ON

OFF

Lit

OFF

When the EX lamp (e) is ON but PV (a) is lower than SP (b), the upper display will be in green colour and it shows that the PV is in the 
hysteresis area

SP

HYS

PV

(A)

(B)

(C)

EXCEEDED

LAMP

OUT

LAMP

lit

off

OUTPUT

RELAY

confirmation

(accepted)

lit

off

Energized

De-energized

Upper

display

color

(D)

 2.3  Working at power on when r.nd is set to 0

(Limit output is de-energized at power on in any cases.)
The output relay is always de-energized (opened) at power-on,even if PV does not exceed SP(A). The output (OUT) display lamp is lit. 
If the PV does not exceed SP, after the confirming operation,  output relay will be energized (closed) and the output (OUT) display lamp 
turns off .

SP

HYS

PV

(A)

(B)

(C)

(A)

(B)

(D)

EXCEEDED

LAMP

OUT

LAMP

lit

off

OUTPUT

RELAY

confirmation

(accepted)

confirmation

(not accepted)

lit

off

Energized

De-energized

OFF

OFF

OFF

Lit

OFF

Lit

OFF

ON

OFF

Lit

OFF

Power

ON

OFF

 2.4  Working at power on when r.nd is set to 1

(Limit output is energized at power on when PV doesn’t exceed SP)
The state of output relay is energized (closed) and the output (OUT) display lamp turns off if the PV does not exceed SP at power-on

SP

HYS

PV

(A)

(B)

(D)

(C)

EXCEEDED

LAMP

OUT

LAMP

lit

off

OUTPUT

RELAY

confirmation

(accepted)

lit

off

Energized

De-energized

OFF

OFF

OFF

Lit

ON

OFF

Lit

OFF

Power

ON

OFF

OFF

ON

OFF

2.5  Note about sensor failure (burnout)

Sensor failure shall result in process shutdown for a limit switch; an alarm or process shutdown for a supervisory switch. 
Upscale burnout is required for a high limit switch.
Down scale burnout for a low limit switch.

Instrument operativity

Reviews: