<5. Function Test>
75
TI 34P02K35-02E Jun. 6, 2018-00
5.1.3 Precautions of Testing When Using Target Equipment
Target equipment is delivered after completion of user acceptance test for use in the
factory. Therefore, it is important to ensure that all settings are properly done and
avoid failures due to oversight.
● FCN-500 Equipment Setup
Install power supply module, CPU module, various I/O modules, communication
module, E2 bus interface module and SB bus repeat module in the base module
based on hardware specifications. Perform equipment setup as described in Section
2.1, "Checking Hardware Specification."
Some equipment setup is done using Resource Configurator, while others are done
on the hardware itself. The first kind of setup is done after installing target
equipment and starting the FCN-500; while the second kind of hardware setup
described below is done at installation before starting the FCN-500.
• Unit number setting of base module
FCN-500 uses the same base module hardware for control units (unit 1) and
expansion units (unit 2 to 9).
When using the E2 bus, set the unit number with the rotary switch of the E2 bus
interface module. It is unnecessary to change the setting of hardware switch on
the base module as Unit 1.
When using the SB bus, whether a base module is to be used as a control unit
or expansion unit is defined using a hardware switch on the base module.
Before shipment, all base modules are set to unit 1 (for control unit) so during
installation, you need to set the switch of each base module to be used as an
expansion unit.
If a system has only one base module with no expansion unit, unit number setup
is not required.
SEE ALSO
For details on how to set the switch of a base module, see Section A1.2, “Base Module” of IM
“STARDOM FCN/FCJ Guide.”
• Single/Duplexed CPU module setting of base module
Whether an FCN-500 uses a single CPU module or duplexed CPU modules is
also defined using the resource configurator and a hardware switch of the base
module.
The factory default setting is for a single CPU and must be changed accordingly
when using duplexed CPU modules.
SEE ALSO
For details on how to set the switch of a base module, see Section A1.2, “Base Module” of IM
“STARDOM FCN/FCJ Guide.”